Styrekabler 18 min May 4, 2026

24 V DC spaendingsfald i styrekredse: PLC, sensorer, relaer og solenoider

Beregn 24 V DC styrekabler til PLC, sensorer, relaer og solenoider med NEC 725, IEC 60204-1 og taleksempler.

Hommer Zhao
24 V DC PLC Spaendingsfald NEC 725 IEC 60204

En 24 V DC styrekreds forsyner PLC-indgange, sensorer, relae-spoler og solenoider. 2 V tab er 8,3% og kan give ustabil indkobling.

Kort

  • 24 V DC: 2 V = 8.3% voltage loss.
  • Ved toleder-DC bruges frem- og returlaengde. En last 150 ft vaek giver cirka 300 ft elektrisk ledervej.
  • Use 3% to 5% as a practical design target.
  • Check NEC 725, IEC 60204-1, and IEC 61131-2 beside the math.

24 V DC spaendingsfald i styrekredse: PLC, sensorer, relaer og solenoider

Ved toleder-DC bruges frem- og returlaengde. En last 150 ft vaek giver cirka 300 ft elektrisk ledervej.

En 0,7 A solenoide pa 150 ft med 18 AWG kobber taber cirka 1,34 V; lasten ser omkring 22,66 V.

NEC 725 omhandler Class 1/2/3; IEC 60204-1 og IEC 61131-2 bruges til maskiner og PLC-I/O.

NEC and IEC references define the installation context; delivered voltage is still a circuit-performance calculation.

24 V DC load comparison

DeviceCurrent150 ft, 18 AWGDecision
PLC input3-10 mA<0.02 VNoise and threshold matter most
Sensor20-60 mA0.04-0.12 VCheck output loading
Relay coil80-200 mA0.15-0.38 VCheck pickup voltage
Solenoid300-700 mA0.57-1.34 VOften controls wire size
Valve group1-3 A1.9-5.7 VConsider larger feed or local supply

Practical checks

Calculate the worst simultaneous current, include shared 0 V conductors, compare 18 AWG, 16 AWG, and 14 AWG, then decide whether a local 24 V supply is cleaner than a larger cable. A 24 V circuit should be checked at the device terminals, not only at the power supply.

Dokumenter spaending, afstand, lederstorrelse, samtidig strom og minimum spaending ved lasten.

Start Calculating

Ready to apply these concepts to your project? Use our professional voltage drop calculator.

Open Calculator