Kawalan elektrik 18 min May 4, 2026

Susut voltan kawalan 24 V DC: PLC, sensor, geganti dan solenoid

Kira kabel kawalan 24 V DC untuk PLC, sensor, geganti dan solenoid dengan NEC 725, IEC 60204-1 dan contoh nombor.

Hommer Zhao
24 V DC PLC Susut voltan NEC 725 IEC 60204

Litar kawalan 24 V DC membekalkan input PLC, sensor, gegelung geganti dan solenoid. Kehilangan 2 V ialah 8.3% dan boleh mengganggu beban jauh.

Ringkasan

  • 24 V DC: 2 V = 8.3% voltage loss.
  • Untuk DC dua wayar, kira pergi dan balik. Beban 150 ft dari bekalan bermaksud laluan elektrik sekitar 300 ft.
  • Use 3% to 5% as a practical design target.
  • Check NEC 725, IEC 60204-1, and IEC 61131-2 beside the math.

Susut voltan kawalan 24 V DC: PLC, sensor, geganti dan solenoid

Untuk DC dua wayar, kira pergi dan balik. Beban 150 ft dari bekalan bermaksud laluan elektrik sekitar 300 ft.

Solenoid 0.7 A pada 150 ft dengan kuprum 18 AWG susut kira-kira 1.34 V; beban menerima sekitar 22.66 V.

NEC 725 meliputi Class 1/2/3; IEC 60204-1 dan IEC 61131-2 berkaitan mesin dan PLC I/O.

NEC and IEC references define the installation context; delivered voltage is still a circuit-performance calculation.

24 V DC load comparison

DeviceCurrent150 ft, 18 AWGDecision
PLC input3-10 mA<0.02 VNoise and threshold matter most
Sensor20-60 mA0.04-0.12 VCheck output loading
Relay coil80-200 mA0.15-0.38 VCheck pickup voltage
Solenoid300-700 mA0.57-1.34 VOften controls wire size
Valve group1-3 A1.9-5.7 VConsider larger feed or local supply

Practical checks

Calculate the worst simultaneous current, include shared 0 V conductors, compare 18 AWG, 16 AWG, and 14 AWG, then decide whether a local 24 V supply is cleaner than a larger cable. A 24 V circuit should be checked at the device terminals, not only at the power supply.

Rekod voltan, jarak, saiz wayar, arus serentak dan voltan minimum pada beban.

Start Calculating

Ready to apply these concepts to your project? Use our professional voltage drop calculator.

Open Calculator