Service Planning Tool

Service Entrance Calculator

Calculate service entrance conductor voltage drop, load voltage, and practical conductor sizes for feeder and service planning.

Estimate voltage drop on customer-owned service conductors before a meter-main, CT cabinet, or service switchboard location is locked in. This planning check does not replace utility coordination, available-fault-current review, or final NEC service-equipment design.

Service Inputs

current, voltage, route length, and conductor choice

Utility boundary reminder
This tool is meant for the customer-owned portion of the service path. If the service-point voltage is already low, upsizing your conductors only fixes the part you control.
Worked Example

200A meter-main, 160A load, 150 ft

4/0 Al lands near 4.80V of drop, about 2.0% at 240V. Moving to 250 kcmil Al cuts that to about 4.07V, about 1.7%.

Worked Example

320A service section, 260A load, 210 ft

350 kcmil Al lands near 6.60V, about 2.75% at 240V. 500 kcmil Al drops near 4.63V, about 1.93%.

Worked Example

208Y/120V three-phase, 300A, 180 ft

Two parallel 3/0 Cu sets land near 3.58V, about 1.72% at 208V. That is often easier to live with than a single larger set in a crowded route.

Related Tools