Electrical Design 17 min April 30, 2026

Three-phase voltage drop: balanced load, imbalance, at neutral current

Praktikal na gabay para sa 208 V, 400 V, at 480 V systems na may balanced at unbalanced examples, neutral current, at NEC/IEC checks.

Hommer Zhao
Three phase Voltage drop Neutral NEC 215.2 IEC 60364

Ang uri ng load ang magdidikta ng calculation. Ang 400 V motor ay line-to-line; ang 120 V, 230 V, o 277 V branch ay kailangang i-check bilang line-to-neutral.

Three-phase voltage drop: balanced load, imbalance, at neutral current

Para sa balanced three-phase load, gamitin ang line voltage, current, at one-way distance. Ikumpara ito sa project target gaya ng 3% branch at 5% total.

Kung 38 A, 24 A, at 18 A ang phase currents, ang 38 A phase ang magkokontrol sa wire size. Hindi sapat ang average, lalo na kung may electronic loads at neutral current.

LoadVoltageMethodCheck
480 V motor480 V line-lineBalanced 3-phaseRunning drop + starting dip
208Y/120 V receptacle120 V line-neutralSingle-phase legWorst phase and neutral
400 V pump400 V line-lineBalanced 3-phaseIEC 60364-5-52 method
277 V lighting277 V line-neutralSingle-phase branchDriver input range
Mixed 208 V panel208 V + 120 V checksHybrid reviewUnbalance and farthest load

NEC / IEC checkpoints

NEC 210.19(A), NEC 215.2(A), NEC 310.15(C)(1), NEC 310.15(E), NEC 430, and IEC 60364-5-52 should be reviewed beside the numeric voltage-drop result. Voltage drop is a performance check; ampacity, temperature, grouping, terminal ratings, and equipment rules still control whether the installation is acceptable.

Kalkulahin muna ang three-phase feeder, pagkatapos ang pinakamalayong line-to-neutral branch.

Start Calculating

Ready to apply these concepts to your project? Use our professional voltage drop calculator.

Open Calculator