Sut ap mach dieu khien 24 V DC: PLC, cam bien, relay va van dien tu
Tinh day dieu khien 24 V DC cho PLC, cam bien, relay va solenoid voi NEC 725, IEC 60204-1 va vi du so.
Mach 24 V DC cap nguon cho ngo vao PLC, cam bien, cuon relay va van dien tu. Mat 2 V la 8,3% cua 24 V nen thiet bi xa co the loi.
Tóm tắt
- 24 V DC: 2 V = 8.3% voltage loss.
- Mach DC hai day phai tinh chieu dai di va ve. Thiet bi cach 150 ft thi dong di qua khoang 300 ft day dan.
- Use 3% to 5% as a practical design target.
- Check NEC 725, IEC 60204-1, and IEC 61131-2 beside the math.
Sut ap mach dieu khien 24 V DC: PLC, cam bien, relay va van dien tu
Mach DC hai day phai tinh chieu dai di va ve. Thiet bi cach 150 ft thi dong di qua khoang 300 ft day dan.
Van dien tu 0,7 A cach 150 ft dung 18 AWG dong co sut ap khoang 1,34 V, con khoang 22,66 V tai tai.
NEC 725 cho mach Class 1/2/3; IEC 60204-1 cho may; IEC 61131-2 cho I/O PLC.
NEC and IEC references define the installation context; delivered voltage is still a circuit-performance calculation.
24 V DC load comparison
| Device | Current | 150 ft, 18 AWG | Decision |
|---|---|---|---|
| PLC input | 3-10 mA | <0.02 V | Noise and threshold matter most |
| Sensor | 20-60 mA | 0.04-0.12 V | Check output loading |
| Relay coil | 80-200 mA | 0.15-0.38 V | Check pickup voltage |
| Solenoid | 300-700 mA | 0.57-1.34 V | Often controls wire size |
| Valve group | 1-3 A | 1.9-5.7 V | Consider larger feed or local supply |
Practical checks
Calculate the worst simultaneous current, include shared 0 V conductors, compare 18 AWG, 16 AWG, and 14 AWG, then decide whether a local 24 V supply is cleaner than a larger cable. A 24 V circuit should be checked at the device terminals, not only at the power supply.
Ghi lai dien ap, khoang cach, co day, dong dong thoi va dien ap toi thieu tai thiet bi.