Jatuh tegangan kontrol 24 V DC: PLC, sensor, relay, dan solenoid
Hitung kabel kontrol 24 V DC untuk PLC, sensor, relay, dan solenoid dengan NEC 725, IEC 60204-1, IEC 61131, dan contoh angka.
Rangkaian kontrol 24 V DC memberi daya ke input PLC, sensor, coil relay, dan solenoid. Kehilangan 2 V berarti 8,3%, cukup untuk membuat beban jauh gagal.
Ringkasan
- 24 V DC: 2 V = 8.3% voltage loss.
- Untuk DC dua kabel, gunakan panjang pergi dan kembali. Beban 150 ft dari catu daya berarti jalur listrik sekitar 300 ft.
- Use 3% to 5% as a practical design target.
- Check NEC 725, IEC 60204-1, and IEC 61131-2 beside the math.
Jatuh tegangan kontrol 24 V DC: PLC, sensor, relay, dan solenoid
Untuk DC dua kabel, gunakan panjang pergi dan kembali. Beban 150 ft dari catu daya berarti jalur listrik sekitar 300 ft.
Solenoid 0,7 A sejauh 150 ft dengan tembaga 18 AWG turun sekitar 1,34 V; tegangan beban sekitar 22,66 V.
NEC 725 mencakup Class 1/2/3; IEC 60204-1 untuk mesin dan IEC 61131-2 untuk PLC I/O.
NEC and IEC references define the installation context; delivered voltage is still a circuit-performance calculation.
24 V DC load comparison
| Device | Current | 150 ft, 18 AWG | Decision |
|---|---|---|---|
| PLC input | 3-10 mA | <0.02 V | Noise and threshold matter most |
| Sensor | 20-60 mA | 0.04-0.12 V | Check output loading |
| Relay coil | 80-200 mA | 0.15-0.38 V | Check pickup voltage |
| Solenoid | 300-700 mA | 0.57-1.34 V | Often controls wire size |
| Valve group | 1-3 A | 1.9-5.7 V | Consider larger feed or local supply |
Practical checks
Calculate the worst simultaneous current, include shared 0 V conductors, compare 18 AWG, 16 AWG, and 14 AWG, then decide whether a local 24 V supply is cleaner than a larger cable. A 24 V circuit should be checked at the device terminals, not only at the power supply.
Catat tegangan, jarak, ukuran kabel, arus serentak, dan tegangan minimum di beban.