Batch Voltage Drop Tool

Voltage Drop BatchCalculator

Paste rows from Excel, Google Sheets, or CSV to calculate voltage drop for multiple AC and DC circuits in one pass.

Paste spreadsheet rows

Excel, Google Sheets, CSV, or tab-delimited input

Results

One-way length input, line-to-load output

Valid rows
4
Within target
1
Over target
3
Average drop
3.50%
Worst row: Battery string A at 5.29% drop.
CircuitSystemWireLengthDropDrop %Load VMethodStatus
Parking lot pole 1
16A at 120V
AC 1-phase8 Cu180 ft4.36 V3.63%115.6 VTable 9 Zeff, PF 0.95, pvcOver target
Rooftop RTU-3
42A at 480V
AC 3-phase6 Cu260 ft8.61 V1.79%471.4 VTable 9 Zeff, PF 0.88, steelWithin target
Battery string A
55A at 48V
DC4 Cu75 ft2.54 V5.29%45.5 VDC loop resistanceOver target
Gate operator feeder
24A at 240V
AC 1-phase4 Al340 ft7.83 V3.26%232.2 VTable 9 Zeff, PF 0.90, pvcOver target