VOLTAGEDROPCALCULATOR
Load Current Tool

kVA to AmpsCalculator

Convert kVA or kW into design current for DC, single-phase, and three-phase circuits before checking voltage drop and wire size.

Convert transformer, generator, UPS, or equipment kVA into circuit current before running a voltage-drop or wire-sizing calculation. For real-power entries, the calculator uses power factor to estimate the equivalent kVA. Final overcurrent protection and conductor ampacity still require the applicable NEC articles, equipment markings, and local amendments.

Calculator Inputs

Load, voltage, phase, and design margin

Voltage presets
Calculated Current
124.91A

Based on 45 kVA at 208 V three-phase.

Continuous Load
156.13 A
Real Power
40.50 kW
Formula
Amps = kVA x 1000 / (sqrt(3) x volts)
Apparent Power
45.00 kVA
Design Notes
  • kVA already includes voltage and current. Power factor is only needed when starting from kW.
  • Three-phase current uses line-to-line voltage and the square-root-of-three multiplier.
  • Use the calculated current as an input, then verify voltage drop, ampacity, termination ratings, and equipment instructions.
Continue the Electrical Calculation