Transformer Secondary Tool
Transformer SecondaryCalculator
Calculate transformer secondary full-load current, conductor voltage drop, and a practical conductor recommendation for panelboard and MCC secondary runs.
Estimate secondary full-load current, conductor voltage drop, and the first conductor that meets a target drop. This is an engineering check only; transformer secondary conductor protection still requires NEC 240.21(C), 450.3, 310.16, and local amendments.
Secondary Inputs
kVA, secondary voltage, route length, and conductor choice
Calculated Results
Secondary current and selected conductor drop
Full-load current
124.9 A
Design current
124.9 A
Selected drop
2.90 V
Drop percent
1.40%
Selected conductor status
The selected 1/0 copper conductor leaves about 205.1 V at the secondary load terminals. First conductor meeting 3.0% drop is 1.
Conductor Comparison
Nearby sizes using NEC Chapter 9 Table 8 resistance
| Conductor | Resistance | Drop | Drop % | Load voltage | Status |
|---|---|---|---|---|---|
| 1 Cu | 0.1540 ohm/kft | 3.66 V | 1.76% | 204.3 V | Meets target |
| 2 Cu | 0.1940 ohm/kft | 4.62 V | 2.22% | 203.4 V | Meets target |
| 3 Cu | 0.2450 ohm/kft | 5.83 V | 2.80% | 202.2 V | Meets target |