Electrical Glossary
Comprehensive definitions of electrical terms related to voltage drop calculations, wire sizing, and NEC standards. Essential reference for electrical professionals and engineers.
Ampacity
Electrical FundamentalsThe maximum amount of electrical current a conductor can carry continuously without exceeding its temperature rating. Ampacity depends on conductor size, insulation type, installation method, ambient temperature, and number of conductors in a raceway.
AWG (American Wire Gauge)
Wire & ConductorsA standardized wire gauge system used in North America for measuring the diameter of electrically conducting wire. Lower AWG numbers indicate larger wire diameters. For example, 10 AWG is larger than 14 AWG. Each decrease of 3 gauge numbers doubles the cross-sectional area.
Branch Circuit
Circuit TypesThe circuit conductors between the final overcurrent protection device and the outlet(s). Branch circuits supply current to lighting, receptacles, and equipment. NEC recommends maximum 3% voltage drop for branch circuits.
Circular Mil
Wire & ConductorsA unit of area equal to the area of a circle with a diameter of one mil (0.001 inch). Used to express wire cross-sectional area. One circular mil = π/4 square mils ≈ 0.7854 square mils.
Conductor
Wire & ConductorsA material that allows electrical current to flow through it with relatively low resistance. Common electrical conductors include copper and aluminum. Conductor size directly affects voltage drop - larger conductors have lower resistance.
Conduit
InstallationA tube or trough used to protect and route electrical wiring. Types include EMT (Electrical Metallic Tubing), IMC (Intermediate Metal Conduit), RMC (Rigid Metal Conduit), and PVC (Polyvinyl Chloride). Steel conduit can increase impedance in AC systems due to magnetic effects.
Current (Amperes)
Electrical FundamentalsThe rate of flow of electric charge, measured in amperes (A). Current is one of the primary factors in voltage drop calculations. Higher current results in greater voltage drop for a given conductor size and length.
I = P / (V × PF)Derating
InstallationThe process of reducing the ampacity of a conductor due to factors such as ambient temperature above 30°C, number of current-carrying conductors in a raceway, or continuous loading. Derating ensures conductors operate within safe temperature limits.
Feeder
Circuit TypesAll circuit conductors between the service equipment (or source of separately derived system) and the final branch-circuit overcurrent device. Feeders supply branch circuit panels or large equipment. Total voltage drop (feeder + branch) should not exceed 5%.
Ground Fault
SafetyAn unintentional electrical path between a current-carrying conductor and a grounded surface. Ground faults can cause equipment damage, fires, and electrical shock. GFCI protection is required in certain locations per NEC.
Impedance
Electrical FundamentalsThe total opposition to current flow in an AC circuit, combining resistance (R) and reactance (X). Impedance is measured in ohms. For voltage drop calculations, impedance is more accurate than resistance alone for AC systems, especially with large conductors in steel conduit.
Z = √(R² + X²)kcmil (Thousand Circular Mils)
Wire & ConductorsA unit of measurement for conductor cross-sectional area, where 1 kcmil = 1,000 circular mils. Used for large conductors (typically 250 kcmil and above). Formerly abbreviated MCM (thousand circular mils).
Load
Electrical FundamentalsAny device or equipment that consumes electrical power. Load can be measured in amps, watts, VA, or horsepower. Accurate load calculation is essential for proper wire sizing and voltage drop analysis.
NEC (National Electrical Code)
Standards & CodesA set of standards for safe electrical installation in the United States, published by NFPA. NEC provides guidelines for voltage drop limits: 3% for branch circuits and 5% total (feeder + branch). Updated every three years.
Ohm's Law
Electrical FundamentalsThe fundamental relationship between voltage (V), current (I), and resistance (R): V = I × R. This law is the basis for all voltage drop calculations. Voltage drop equals current times resistance of the conductor.
V = I × ROvercurrent Protection
SafetyDevices (circuit breakers or fuses) that automatically interrupt current flow when it exceeds a safe level. Overcurrent protection prevents conductor overheating and fire hazards. Sized based on conductor ampacity per NEC.
Parallel Conductors
Wire & ConductorsTwo or more conductors of the same size, material, and length connected together to increase current-carrying capacity and reduce voltage drop. Per NEC, parallel conductors must be 1/0 AWG or larger and installed with specific arrangements.
Power Factor
AC CircuitsThe ratio of real power (watts) to apparent power (VA) in an AC circuit. Power factor ranges from 0 to 1. A power factor of 1.0 indicates a purely resistive load. Inductive loads (motors, transformers) have lagging power factor, which affects voltage drop calculations.
PF = kW / kVAReactance
AC CircuitsOpposition to AC current flow caused by inductance or capacitance, measured in ohms. Inductive reactance (XL) increases with frequency; capacitive reactance (XC) decreases with frequency. Reactance contributes to total impedance in AC circuits.
XL = 2πfLResistance
Electrical FundamentalsOpposition to current flow in a conductor, measured in ohms (Ω). Resistance depends on conductor material, cross-sectional area, length, and temperature. Copper has lower resistance than aluminum for the same size.
R = ρL/AService
Circuit TypesThe conductors and equipment for delivering electrical energy from the utility supply to the premises wiring. Service includes the service drop (overhead) or service lateral (underground), meter, and main disconnect.
Single-Phase
AC CircuitsAn AC power system with one phase conductor and a neutral. Common in residential (120V and 240V) and light commercial applications. Voltage drop formula uses factor of 2 for single-phase circuits: Vd = 2 × I × L × R / 1000.
Temperature Rating
Wire & ConductorsThe maximum temperature at which a conductor's insulation can operate continuously without degradation. Common ratings: 60°C, 75°C, and 90°C. Higher temperature ratings allow greater ampacity but don't change the conductor's resistance for voltage drop calculations.
Three-Phase
AC CircuitsAn AC power system with three phase conductors, 120° apart. More efficient for large loads and motors. Voltage drop formula uses factor of √3 (1.732): Vd = √3 × I × L × R / 1000. Common voltages: 208V, 480V.
Voltage Drop
Electrical FundamentalsThe reduction in voltage between the source and load due to conductor resistance. Expressed in volts or as a percentage of source voltage. NEC recommends 3% max for branch circuits and 5% total. Excessive drop causes equipment issues and energy waste.
Vd% = (Vd / Vsource) × 100