AC Voltage DropCalculator
Professional AC voltage drop calculator using NEC Chapter 9 Table 9 values. Accounts for resistance, reactance, power factor, and conduit type for accurate single-phase and three-phase calculations.
AC Circuit Parameters
NEC Chapter 9 Table 9 values
Calculation Results
≤2% on this segment — below the 3% planning target (upstream drop not included)
AC Voltage Drop Formula
Where Z (effective impedance):
Z = R×cos(φ) + XL×sin(φ)
NEC Chapter 9
This calculator uses NEC Chapter 9 Table 9 values (75 °C, 60 Hz, three single conductors in conduit). R and XL are both read from the column for the raceway you select.
- •Steel conduit raises reactance (XL) by about 25% over PVC or aluminum conduit, e.g. 0.055 vs 0.044 Ω/1000 ft for 1/0
- •PVC and aluminum conduit share one XL column; aluminum conduit can show slightly higher R in larger copper sizes
- •Reactance becomes significant in larger conductors
Power Factor Guide
- Resistive loads:1.0
- Motors (loaded):0.80-0.90
- Motors (starting):0.20-0.40
- LED lighting:0.90-0.95
- Fluorescent:0.85-0.95
AC Voltage Drop Calculation Explained
AC vs DC Calculations
AC voltage drop calculations are more complex than DC because conductors exhibit both resistance and reactance (inductive impedance) when carrying alternating current. The effective impedance depends on the power factor of the load and the physical arrangement of the conductors.
How Conduit Type Changes AC Voltage Drop
The raceway changes both terms. In Table 9, steel conduit mainly raises reactance: for 1/0 copper XL is 0.055 Ω/1000 ft in steel versus 0.044 in PVC or aluminum. Resistance shifts less, and in larger copper sizes aluminum conduit lists the highest R (250 kcmil: 0.052 PVC, 0.054 steel, 0.057 aluminum). So the worst raceway depends on conductor size and power factor: with the default 1/0 copper, 480 V three-phase, 100 A, 200 ft and 0.85 PF, this calculator gives 4.34 V in PVC, 4.54 V in steel and 4.63 V in aluminum conduit.
Three-Phase Considerations
Three-phase systems use the √3 (1.732) multiplier instead of 2 used in single-phase calculations. This accounts for the phase relationships between conductors in a balanced three-phase system.
For unbalanced three-phase loads, calculations become more complex and may require analysis of each phase individually. This calculator assumes balanced loading conditions.
Is 3% or 5% AC Voltage Drop Acceptable?
The NEC 2023 210.19 Informational Note and 215.2(A)(2) Informational Note No. 2 recommend no more than 3% drop on a branch circuit or feeder and no more than 5% combined. They are recommendations, not enforceable requirements; see the NEC voltage drop standards page.
If a run is over your target, the usual fixes are a larger conductor, a shorter route, parallel sets or a higher system voltage. Example from this calculator: 208 V three-phase, 100 A, 300 ft, copper in PVC at 0.85 PF gives 6.50 V (3.13%) on 1/0 and 5.59 V (2.69%) on 2/0. Then check the larger size against ampacity and conduit fill.
Assumptions and Limits of This AC Voltage Drop Model
The result is only as good as the conditions behind Table 9. Check these before you rely on a number:
- •Lagging power factor only. Z = R·cos φ + XL·sin φ treats the load as inductive (motors, transformers, most mixed loads). With a leading power factor, for example an over-corrected capacitor bank, the reactive term subtracts. With the default inputs (480 V three-phase, 100 A, 200 ft, 1/0 copper in steel conduit, PF 0.85) the drop is 4.54 V lagging. At PF 0.85 leading the same formula gives 2.53 V (2.545 V by an exact phasor solution). The calculator has no leading-PF mode: it always reports the lagging value, which is on the high side for a leading load.
- •Approximate formula. The Table 9 method drops a small second-order term. For the default case the exact phasor solution gives 4.537 V, the same as this calculator to three decimals; for the 208 V, 300 ft example above it is 6.51 V against 6.50 V. The gap depends on power factor, the R/XL ratio, current, length and voltage, not only on the size of the drop: a 120 V single-phase circuit at 15 A, 72.5 ft of 14 AWG copper in PVC and PF 0.5 reads 2.90% here but 3.02% exactly. When a result sits right at a design limit, check it with a full phasor or software calculation.
- •Table 9 conditions. 75 °C conductor temperature, 60 Hz, 600 V cable, three single conductors in one conduit. The values do not describe cable tray, direct burial, multiconductor cable, 50 Hz systems or conductors running cooler than 75 °C at part load.
- •Balanced, linear load. Three-phase results assume equal current in each phase. Unbalanced loads, neutral current and harmonics from non-linear loads are not modeled.
- •Parallel sets. R and XL are divided by the number of sets, which assumes the sets share current equally.
- •Data edition. Table 9 R and XL values are transcribed from the 2017 edition page; the other references on this site follow NEC 2023. Use the edition your jurisdiction adopted where they differ.
Source and method: R and XL from NEC Chapter 9, Table 9 (2017 edition, printed page 70-690), checked cell by cell on 2026-11-08; exact figures solve |Vr + I·Z| = Vs at the source voltage with constant load current. Code text: NFPA 70 (free read-only access).
For commercial distribution, use the 208V voltage drop calculator for line-to-line loads and the 277V calculator for lighting branches on a 480Y/277V system.