Raceway Planning Tool

Conduit FillCalculator

Estimate raceway fill for common THHN/THWN-2 conductor groupings before you finalize conduit size and layout.

Estimate conduit fill for common THHN/THWN-2 conductor groupings using standard single-conductor areas and the familiar NEC Chapter 9 fill limits: 53% for one conductor, 31% for two, and 40% for three or more. Verify compact-stranded cable dimensions, cable assemblies, nipples, and any manufacturer-specific data before issuing final drawings or installing material.

Conduit Inputs

common THHN/THWN-2 conductors in a selected raceway

Phase / hot conductors

Identical insulated conductors in the same raceway

Neutral conductors

Identical insulated conductors in the same raceway

Equipment grounding conductors

Identical insulated conductors in the same raceway

Fill Summary

Area-based raceway check

Selected raceway exceeds fill limits

EMT 1" is at 123.2% of the allowable fill area for 5 conductors.

Conductors occupy 49.3% of the 0.864 in² internal area; the NEC Chapter 9 Table 1 limit for this count is 40.0%. Internal areas are NEC Chapter 9 Table 4 values.

Method: fill % = total conductor area ÷ the NEC Chapter 9 Table 4 total (100%) internal area, compared with the Chapter 9 Table 1 limit of 53% for one conductor, 31% for two and 40% for more than two. The allowable area shown is that 100% area × the limit; Table 4 also prints a rounded 40% column that can differ by up to 0.0006 in², so check the printed column when a result is that close to the limit. Not covered: conduit nipples 24 in or shorter (Chapter 9 Note 4 allows 60%), cables and compact or non-THHN insulation.

Total conductor area
0.426 in²
Allowable fill area
0.346 in²
Fill rule used
40.0%
Recommended trade size
1-1/4"

Conductor breakdown

Phase / hot conductors
3 × 3 AWG at 0.0973 in² each
0.292 in²
Neutral conductors
1 × 3 AWG at 0.0973 in² each
0.097 in²
Equipment grounding conductors
1 × 8 AWG at 0.0366 in² each
0.037 in²

Raceway sizes

1/2"
Allowable area 0.122 in² (100% area × limit)
140.1% / 40.0%
Over
3/4"
Allowable area 0.213 in² (100% area × limit)
79.9% / 40.0%
Over
1"
Allowable area 0.346 in² (100% area × limit)
49.3% / 40.0%
Over
1-1/4"
Allowable area 0.598 in² (100% area × limit)
28.5% / 40.0%
Pass
1-1/2"
Allowable area 0.814 in² (100% area × limit)
20.9% / 40.0%
Pass
2"
Allowable area 1.342 in² (100% area × limit)
12.7% / 40.0%
Pass
2-1/2"
Allowable area 2.343 in² (100% area × limit)
7.3% / 40.0%
Pass
3"
Allowable area 3.538 in² (100% area × limit)
4.8% / 40.0%
Pass
3-1/2"
Allowable area 4.618 in² (100% area × limit)
3.7% / 40.0%
Pass
4"
Allowable area 5.901 in² (100% area × limit)
2.9% / 40.0%
Pass
Field Notes
  • This tool assumes individual THHN/THWN-2 insulated conductors, not multiconductor cable, MC cable, or manufacturer-specific compact cable dimensions.
  • Raceway fill is only one check. Final design still needs ampacity, temperature correction, bundling, termination, and pulling-tension review.
  • Conduit nipples 24 in or shorter may be filled to 60% under Chapter 9 Note 4; this tool does not apply that allowance or other special conditions. Treat this as a planning and coordination tool, not automatic approval.