Wire Sizing Methods: Ampacity vs Voltage Drop
Learn the two primary methods for sizing electrical conductors: ampacity-based and voltage drop-based. Understand when each method controls and how to apply both.
Two Methods, One Goal
Electrical conductors must be sized to safely carry the required current while maintaining acceptable voltage at the load. Two primary methods govern conductor sizing: ampacity (current-carrying capacity) and voltage drop. Understanding when each method controls the design is essential for creating efficient, code-compliant, and cost-effective electrical systems. This guide explains both methods and provides practical guidance for professional electrical design.
In many installations, particularly those with short conductor runs, ampacity requirements determine the minimum wire size. However, for longer circuits or those with tight voltage tolerance requirements, voltage drop often mandates larger conductors than ampacity alone would require. Professional designers must check both criteria and use the larger size.
Ampacity-Based Sizing
Ampacity is the maximum current a conductor can carry continuously without exceeding its temperature rating. NEC Article 310 provides ampacity tables based on conductor size, insulation type, installation method, and ambient temperature. This method ensures conductors don't overheat and is a mandatory code requirement.
NEC Ampacity Table 310.16 (Excerpt)
| Size (AWG) | 60°C | 75°C | 90°C |
|---|---|---|---|
| 14 | 15A | 20A | 25A |
| 12 | 20A | 25A | 30A |
| 10 | 30A | 35A | 40A |
| 8 | 40A | 50A | 55A |
| 6 | 55A | 65A | 75A |
Voltage Drop-Based Sizing
Voltage drop sizing ensures the load receives adequate voltage for proper operation. While not a mandatory NEC requirement (it's an informational note), voltage drop limits are essential for equipment performance and energy efficiency. For long runs, voltage drop often requires larger conductors than ampacity alone would dictate.
When Ampacity Controls
- • Short conductor runs (<50 ft typical)
- • High current, short distance
- • Hot ambient environments
- • Multiple conductors in conduit
When Voltage Drop Controls
- • Long conductor runs (>100 ft)
- • Feeders to remote panels
- • Sensitive equipment circuits
- • Low voltage systems (12V, 24V)
The Design Process
- 1Determine load current — Calculate the expected current based on load characteristics and apply any required factors (continuous load multiplier, etc.)
- 2Size for ampacity — Select the minimum wire size that provides adequate ampacity per NEC Table 310.16, including derating factors
- 3Calculate voltage drop — Using the ampacity-sized conductor, calculate the expected voltage drop percentage
- 4Upsize if needed — If voltage drop exceeds limits, increase conductor size until requirements are met
- 5Document both — Record the controlling factor in your design documentation
Size Your Conductors
Our wire sizing calculator considers both ampacity and voltage drop requirements to recommend the optimal conductor size for your application. Get instant results with NEC compliance verification.
Wire Size Calculator