REFERENCE//NEC WIRE TABLES

WIRE SIZE REFERENCE TABLES

Complete reference tables for wire sizing, ampacity, resistance, and voltage drop calculations. Data sourced from NEC Chapter 9 tables and industry standards for accurate electrical design.

SELECT TABLE

Wire Ampacity Table

Based on NEC Table 310.16 - Allowable ampacities at 30°C ambient

NEC 310.16
SizeCMCopperAluminum
75°C90°C75°C90°C
144,11015A15A
126,53020A20A15A15A
1010,38030A30A25A25A
816,51040A45A35A40A
626,24055A60A45A50A
441,74070A80A60A65A
352,62085A95A70A75A
266,36095A105A80A90A
183,690110A125A95A100A
1/0105,600125A145A110A120A
2/0133,100145A165A125A135A
3/0167,800165A195A145A155A
4/0211,600195A230A170A180A
250250,000215A255A190A205A
300300,000240A285A210A230A
350350,000260A310A230A250A
400400,000280A335A250A270A
500500,000320A380A280A310A
600600,000350A420A310A340A
750750,000385A475A350A385A
10001,000,000445A545A400A445A

Note: Ampacities are for not more than 3 current-carrying conductors in raceway or cable. For 4-6 conductors, apply 80% derating. For 7-9 conductors, apply 70% derating.