Agricultural 13 min read Central Valley, CA

Agricultural Irrigation: Remote Pump Station Design

Engineering power distribution for a 500-acre farm irrigation system with pump stations located up to 2,000 feet from the main electrical service.

irrigation pumpagricultural electricalremote powerfarm electricalwell pumpfarm motor

Voltage drop reduced from 11.2% to 2.8%

Pump motor life extended 3-4×

Energy savings of 8% annually

ROI achieved in 2.3 years

Challenge

Powering irrigation pumps 1,500-2,000ft from service with acceptable voltage drop

Solution

Higher voltage distribution (480V vs 240V) with strategic transformer placement

Project Overview

A 500-acre almond orchard in California's Central Valley required a complete irrigation system upgrade. The operation included four deep well pumps ranging from 50HP to 100HP, positioned at distances from 800 to 2,000 feet from the utility service entrance. The existing electrical infrastructure, installed decades earlier, had become increasingly problematic as the operation expanded and pump sizes increased.

Agricultural electrical systems present unique challenges because of the distances involved. Unlike urban or suburban installations where most loads are within 200 feet of the electrical service, farm equipment is often located at the far reaches of the property. Well pumps, grain handling equipment, and irrigation systems may be 1,000 feet or more from the main electrical panel. At these distances, even modest loads can experience significant voltage drop if conductors are not properly sized.

The farm had experienced persistent problems including premature motor failures, reduced pump efficiency, and high energy bills. An engineering assessment revealed that the root cause was excessive voltage drop in the original 240V single-phase distribution system. This case study documents the solution that transformed the irrigation system's performance and reliability.

The Challenge: Long-Distance Power Distribution

Original System Analysis

System Configuration
  • • Voltage: 240V single-phase
  • • Conductors: #2 AWG copper underground
  • • Longest run: 2,000 feet
Measured Voltage Drop
  • • Well #1 (800ft): 7.2% drop
  • • Well #2 (1,200ft): 8.9% drop
  • • Well #3 (1,500ft): 9.8% drop
  • • Well #4 (2,000ft): 11.2% drop

The voltage drop at the farthest pump exceeded 11%, meaning the motor received only 213V instead of the rated 240V. At this reduced voltage, the motor drew significantly higher current to produce the required power, leading to overheating, reduced efficiency, and shortened lifespan. The pump at Well #4 had required motor replacement three times in five years.

The Solution: 480V Three-Phase Distribution

The engineering solution leveraged a fundamental principle of electrical distribution: higher voltage means lower current for the same power. By converting to a 480V three-phase distribution system, current would be reduced by approximately 75% compared to the 240V single-phase system, dramatically reducing voltage drop.

New System Design

  • Main Distribution: 480V three-phase from utility transformer
  • Feeder Conductors: 4/0 AWG aluminum underground
  • Step-Down Transformers: 480V to 240V at each pump location
  • New Motors: Premium efficiency 480V three-phase

Voltage Drop Comparison

Old 240V SystemWell #4 @ 2,000ft11.2% drop
New 480V SystemWell #4 @ 2,000ft2.8% drop

Results and Economic Benefits

3-4×
Motor Life Extension

Proper voltage = cooler operation

8%
Energy Savings

Reduced I²R losses

2.3 yrs
Payback Period

Investment recovered quickly