Industrial Motor Feeder: 500HP Chiller Installation
Engineering a 500HP chiller motor feeder with voltage drop optimization for a manufacturing facility, balancing starting current requirements with running efficiency.
1.8% running voltage drop achieved
Eliminated voltage sag during motor starting
Reduced energy losses by 3% annually
$12,000 annual energy savings
Challenge
500HP motor requiring 600ft feeder run with strict voltage drop limits for motor starting
Solution
Parallel 500 kcmil conductors with VFD to manage starting current and voltage drop
Project Overview
A major manufacturing facility in Houston, Texas required installation of a new 500HP centrifugal chiller to expand cooling capacity for their production process. The chiller's motor, operating at 480V three-phase, would be located in a new mechanical building approximately 600 feet from the main electrical distribution switchgear. This project presented significant voltage drop challenges that required careful engineering analysis to ensure reliable motor operation.
Large industrial motors present unique electrical challenges because they operate in two distinct modes: starting and running. During normal operation, the motor draws its rated full load current (FLC) continuously. However, during starting, the motor can draw 6 to 8 times its full load current for 10 to 15 seconds until it reaches operating speed. This high starting current creates a temporary but significant voltage drop that can affect the motor's ability to develop adequate starting torque and can disturb other equipment on the same electrical system.
The facility's engineering team recognized that this installation required more than a simple ampacity-based conductor selection. They needed to consider voltage drop during both running and starting conditions, evaluate the impact on other facility loads, and determine whether motor starting methods such as VFDs or soft starters should be incorporated into the design. This case study examines the complete engineering analysis that led to a successful installation.
Technical Requirements and Challenges
Motor Starting Conditions
- • Full Load Current: 590A at 480V
- • Starting Current (DOL): 3,540A (6× FLC)
- • Starting Duration: 10-15 seconds
- • Starting Torque Required: 150% FLT
- • Voltage Tolerance: Motor requires minimum 80% voltage for adequate starting torque
Running Conditions
- • Full Load Current: 590A
- • Typical Operating Load: 530A (90% load)
- • Operating Hours: 8,760 hrs/year (24/7)
- • Target Running VD: <3% for efficiency
- • Energy Cost: $0.08/kWh industrial rate
The 600-foot distance from the switchgear to the motor location creates substantial conductor resistance. For a motor of this size operating at 480V three-phase, the running current of 590 amps is significant. If conductors are sized only for ampacity, the voltage drop during normal operation could exceed acceptable limits, reducing motor efficiency and increasing operating costs. During starting, the situation becomes even more critical—the 3,540-amp starting current would cause dramatic voltage sag throughout the facility's electrical system.
The engineering team established design criteria requiring less than 3% voltage drop during normal running conditions and limiting starting voltage drop to prevent interference with other facility loads. They also needed to ensure the motor received at least 80% of nominal voltage during starting to develop adequate torque for the centrifugal compressor load.
Initial Analysis: Direct-On-Line Starting
The engineering team first analyzed a conventional direct-on-line (DOL) starting approach to understand the baseline requirements. Using 500 kcmil copper conductors, which provide adequate ampacity for the 590A load:
DOL Starting Analysis: 500 kcmil Copper
Running Voltage Drop (590A):
Vd = (√3 × 590 × 600 × 0.0258) / 1000 = 15.8V
Running Vd% = 15.8 / 480 × 100 = 3.3%
Starting Voltage Drop (3,540A):
Vd = (√3 × 3540 × 600 × 0.0258) / 1000 = 94.8V
Starting Vd% = 94.8 / 480 × 100 = 19.8%
Motor voltage during start: 385V (80.2% of nominal)
The analysis revealed two significant problems with the DOL approach. First, the running voltage drop of 3.3% exceeds the target 3% limit, resulting in slightly reduced motor efficiency and increased energy consumption over the 24/7 operating schedule. Second, and more critically, the nearly 20% voltage drop during starting would cause unacceptable voltage sag throughout the facility, potentially affecting production equipment, lighting, and other sensitive loads.
The Optimized Solution: VFD with Parallel Conductors
The engineering team developed an optimized solution incorporating two key elements: a Variable Frequency Drive (VFD) to eliminate the starting current problem, and parallel conductors to reduce running voltage drop while optimizing cost.
VFD Benefits for This Application
- • Soft Starting: Limits starting current to 100-150% of FLC instead of 600%
- • Speed Control: Allows chiller capacity modulation for energy savings
- • Power Factor Correction: Unity power factor reduces current draw
- • Starting Voltage Drop: Reduced from 19.8% to approximately 3.3%
- • Facility Impact: Eliminates voltage sag affecting other loads
With the VFD managing starting current, the conductor sizing could be optimized for running conditions only. The team selected three sets of 500 kcmil copper conductors per phase (3 parallel runs), which reduces the effective resistance by a factor of three:
Final Design: 3 Sets of 500 kcmil per Phase
Effective Resistance: 0.0258 / 3 = 0.0086 Ω/kft
Running Vd = (√3 × 590 × 600 × 0.0086) / 1000 = 5.27V
Running Vd% = 5.27 / 480 × 100 = 1.1%
VFD Starting Vd (at 150% FLC = 885A):
Starting Vd = (√3 × 885 × 600 × 0.0086) / 1000 = 7.9V
Starting Vd% = 1.6% - Excellent!
Economic Analysis
From reduced I²R losses in conductors
Total system efficiency gain
For VFD and conductor upgrade
The economic analysis demonstrated compelling benefits for the optimized design. The reduced voltage drop translates directly to lower energy losses in the conductors. With 590A flowing through conductors 24/7, even small resistance reductions yield significant savings. The VFD also enables chiller capacity modulation, allowing the system to match cooling output to actual demand rather than cycling on and off, further reducing energy consumption.
Key Takeaways for Industrial Motor Feeders
- Always analyze both starting and running conditions—motor starting current can be 6-8 times higher than running current.
- Consider VFDs or soft starters for large motors—they eliminate starting voltage drop problems and provide additional benefits.
- Parallel conductors provide a cost-effective way to reduce resistance for high-current feeders.
- Calculate lifetime energy costs—conductor upgrades often pay for themselves through reduced losses.
Analyze Your Motor Feeder
Planning a motor feeder installation? Our voltage drop calculator supports three-phase calculations for industrial applications, including parallel conductor configurations.
Calculate Motor FeederRelated Case Studies
Commercial HVAC Retrofit: Rooftop Unit Upgrade
Retrofitting aging HVAC equipment in a retail complex while addressing voltage drop issues that had plagued the original installation for years.
AgriculturalAgricultural Irrigation: Remote Pump Station Design
Engineering power distribution for a 500-acre farm irrigation system with pump stations located up to 2,000 feet from the main electrical service.