Illustrative example · Agricultural

This is an illustrative engineering example built from stated assumptions, not a record of a specific installed project.

Agricultural Irrigation: Remote Pump Station Design

Hypothetical setting: Central Valley, CA

Compare hypothetical supply options for a pump 2000ft from the service. Assume 240V single-phase at 100A and unity power factor: P = V × I = 24000W. For the same assumed input power at 480V three-phase, I = 24000 / (√3 × 480) = 28.867513A.

240V comparison

77.60 V · 32.33%

480V comparison

10.00 V · 2.08%

Conditions: the 240V option is a hypothetical case that exceeds a 3% target. Both options assume equal input power, unity power factor and steady-state current; conductor ampacity limits are checked separately.

Challenge

Compare voltage and conductor options over a long route using equal assumed input power.

Comparison approach

Compare 2 AWG copper at 240V with 4/0 AWG aluminum at 480V three-phase; use unrounded current in the calculation.

Stated inputs and calculation method

All lengths below are one-way feet. Resistance R is in Ω per 1000ft from the site’s 75°C resistance table. N is the number of identical parallel sets. The AC examples use a resistive estimate at unity power factor, without reactance or source impedance.

DC / single-phase: Vd = 2 × I × L × R / (1000 × N). Three-phase: Vd = √3 × I × L × R / (1000 × N).

Vd% = Vd / V × 100; load voltage = V − Vd.

Results are calculated before rounding; displayed voltages and percentages use two decimal places. These are conductor-drop estimates, not field measurements or full installation approvals.

Site wire tables

Worked voltage-drop comparisons

240V comparison

240 V · I = 100 A · L = 2000 ft · 2 AWG · copper · N = 1

Table resistance: R = 0.194 Ω/1000ft; R/N = 0.194 Ω/1000ft.

Vd = 2 × 100 × 2000 × 0.194 / (1000 × 1) = 77.60 V

Vd% = 77.60 / 240 × 100 ≈ 32.33%

Calculated load voltage: 240 − 77.60 = 162.40 V

480V comparison

480 V · I = 28.867513 A · L = 2000 ft · 4/0 AWG · aluminum · N = 1

Table resistance: R = 0.1 Ω/1000ft; R/N = 0.1 Ω/1000ft.

Vd = √3 × 28.867513 × 2000 × 0.1 / (1000 × 1) = 10.00 V

Vd% = 10.00 / 480 × 100 ≈ 2.08%

Calculated load voltage: 480 − 10.00 = 470.00 V

Engineering interpretation and limits

Equal assumed electrical input power does not establish equal pump output. Actual motor efficiency, power factor, starting current and equipment voltage ratings are needed for a design.

The long-run comparison illustrates why higher voltage can reduce current and percentage drop. Transformer losses, upstream impedance and starting behavior are outside this calculation.

Verify burial method, conductor protection, grounding and motor protection separately. No pump replacement record, annual savings or return on investment is asserted.

Economic evaluation requires real inputs

Any savings estimate needs actual electricity prices, operating hours and the load profile. Installed cost, maintenance and equipment life need project evidence. No savings amount, payback period or customer outcome is claimed for this example.

Apply the method to your inputs

Enter the actual voltage, current, one-way distance, conductor and parallel sets. Check voltage drop together with ampacity, correction factors, protection and equipment requirements.

Open Calculator