Temperature Effects on Voltage Drop and Conductor Sizing
Understand how temperature affects conductor resistance and voltage drop. Learn about derating factors, ambient temperature considerations, and thermal calculations.
TL;DR
For the same current and cable route, higher conductor temperature increases resistance and therefore voltage drop. Ambient temperature also affects allowable ampacity, so check resistance correction and ampacity derating as separate parts of conductor selection.
Temperature and Conductor Performance
Temperature significantly affects conductor performance in two ways: it changes the resistance of the conductor material, and it affects the allowable ampacity based on insulation ratings and heat dissipation. Understanding these thermal effects is essential for accurate voltage drop calculations and safe electrical system design, particularly in extreme temperature environments or heavily loaded circuits.
Metal conductors exhibit a positive temperature coefficient of resistance—their resistance increases as temperature rises. This means a circuit operating at elevated temperature will have higher voltage drop than the same circuit at room temperature, a factor that must be considered in critical applications.
Resistance vs Temperature
The standard resistance values in NEC Chapter 9, Table 8 are given at 75°C. For other conductor temperatures, recalculate resistance with the temperature coefficient. The coefficients below are referenced to 20°C, so the formula starts from the 20°C resistance (or divides out the 75°C factor first).
Temperature Resistance Formula
Because α is referenced to 20°C, each 10°C above 75°C raises copper resistance by about 3.2%, not 3.93%. A copper conductor running at 90°C has (1 + 0.00393 × 70) / (1 + 0.00393 × 55) = 1.275 / 1.216 ≈ 1.048 times the Table 8 value, so resistance and voltage drop are about 4.8% higher than the table suggests.
Ambient Temperature Considerations
NEC ampacity tables are based on an ambient temperature of 30°C (86°F). When conductors are installed in environments with higher ambient temperatures, their ampacity must be reduced (derated) to prevent overheating. This derating affects both ampacity and, indirectly, the actual operating temperature and resistance.
| Ambient Temp | 60°C Wire | 75°C Wire | 90°C Wire |
|---|---|---|---|
| 21-25°C | 1.08 | 1.05 | 1.04 |
| 26-30°C | 1.00 | 1.00 | 1.00 |
| 31-35°C | 0.91 | 0.94 | 0.96 |
| 36-40°C | 0.82 | 0.88 | 0.91 |
| 41-45°C | 0.71 | 0.82 | 0.87 |
Practical Applications
Hot Environments
- • Rooftop installations in summer
- • Industrial boiler rooms
- • Attic wiring in hot climates
- • Solar PV conduit runs
Cold Environments
- • Refrigerated warehouses
- • Arctic installations
- • Underground in cold climates
- • Actually improves voltage drop
Calculate with Temperature Factors
The main voltage drop calculator uses the fixed 75°C Table 8 resistance. To see the effect of conductor temperature, use the wire resistance calculator; for ambient temperature correction of ampacity, use the ampacity derating calculator.
Wire Resistance by TemperatureFrequently Asked Questions
How does conductor temperature affect voltage drop?
Copper and aluminum resistance rises as conductor temperature rises. With current and length held constant, the higher resistance increases the voltage lost along the conductor.
Does a hotter conductor mean more voltage reaches the load?
At a fixed source voltage and current, a hotter conductor has higher resistance and a larger voltage drop, so less voltage remains at the load. This is a conductor-loss relationship, not a statement that the source voltage itself changes.
What effect does ambient temperature have on wire sizing?
The page’s ampacity reference uses a 30°C ambient basis. At higher ambient temperatures, apply the correction factor for the insulation temperature rating and check the resulting ampacity against the load.
Is ambient temperature the same as conductor operating temperature?
They are different inputs to the design checks: ambient conditions affect heat dissipation and ampacity, while the conductor’s operating temperature is used for its resistance correction. Check both for the installation.
Sources and references
- NFPA 70 — National Electrical Code
The ampacity and ambient-temperature correction reference discussed on this page.
- NIST / NBS Circular 31 — Copper Wire Tables
Background for copper resistance and its temperature coefficient, including the need to state the reference temperature.
Hommer Zhao
Founder & General Manager
LinkedIn