Wire Sizing

What Size Wire for 40 Amp 150 Feet Away

Table-based wire size estimate for 40 amps at 150 feet on a 240V single-phase circuit. Immediate answer below.

Updated November 12, 2026

Recommended Wire Size

Copper
6 AWG
Voltage drop: 2.25% (5.403V)
Voltage at load: 234.60V
Ampacity used: 55 A (60°C column). Controlling factor: Voltage Drop (3% limit)
Aluminum
4 AWG
Voltage drop: 2.33% (5.581V)
Voltage at load: 234.42V
Ampacity used: 55 A (60°C column). Controlling factor: Voltage Drop (3% limit)

Required ampacity: 40 A × 1 = 40 A. Drop uses 40 A. Ampacity: NEC Table 310.16, 60°C column (NEC 110.14(C) default for circuits of 100 A or less; equipment marked for 75°C terminals can allow the 75°C column), single-phase, 240V, 3% max voltage drop, one-way distance 150 ft.

Voltage drop uses AC resistance and reactance from NEC Chapter 9 Table 9 (NEC 2017 Table 9 values) for conductors in steel conduit at 0.85 lagging power factor, effective Z = R × PF + XL × sin(acos PF), single-phase, one set, VD = 2 × I × Z × L / 1000. Ampacity uses NEC 2023 Table 310.16 at 30°C ambient with no more than three current-carrying conductors. These are the same engine and defaults as the wire size calculator (steel conduit, PF 0.85).

Wire Comparison Table

Wire SizeAmpacityV-Drop (V)V-Drop (%)V at LoadStatus
10 AWG30A12.638V5.27%227.36V
8 AWG40A8.367V3.49%231.63V
6 AWGREC55A5.403V2.25%234.6V
4 AWG70A3.541V1.48%236.46V
3 AWG85A2.923V1.22%237.08V

Table shows nearby candidate sizes for 40A at 150 ft on 240V (copper). Green check = meets both ampacity and 3% voltage drop (Table 9, steel conduit, PF 0.85). REC = smallest size meeting these two model checks. See the full conductor tables for other sizes.

Compressor demand on a longer branch

This estimate also applies to HVAC equipment. Compare the steady-state load voltage against the unit’s allowed range, then evaluate starting with the actual compressor and source data. Increasing conductor size reduces cable loss but does not correct an undersized transformer or generator whose own voltage falls during acceleration.

Operating boundaries: 40 A, 150 ft, 240 V, copper

Voltage drop controls: the ampacity floor is 8 AWG, but its 3% route limit at 40 A is only 129.080 ft. The 150 ft route therefore needs 6 AWG. One set meets both checks; parallel conductors are not required by this model.

8 AWG has enough ampacity, but the route must shrink from 150 ft to at most 129.080 ft (shorten by 20.920 ft) to meet 3% at 40 A. Alternatively, keep the route and reduce current to at most 34.421 A, down 5.579 A. Either change makes the smaller size eligible; reducing both inputs further may permit another size.

For the selected 6 AWG, increasing load beyond 53.308 A changes the choice: voltage drop reaches its limit first. That leaves 13.308 A above the present load. With current fixed, route growth above 199.905 ft also requires reselection, a margin of 49.905 ft.

A 2% budget is 4.800 V instead of 7.200 V. At 40 A, the existing conductor’s length ceiling falls to 133.270 ft; at 150 ft, its combined current ceiling becomes 35.539 A. The unchanged inputs now select 4 AWG, giving 3.541 V (1.476%).

  • Current −10%: 36.000 A / 150.000 ft → 6 AWG (2.026%).
  • Current +10%: 44.000 A / 150.000 ft → 6 AWG (2.476%).
  • Route −10%: 40.000 A / 135.000 ft → 6 AWG (2.026%).
  • Route +10%: 40.000 A / 165.000 ft → 6 AWG (2.476%).

Basis: Z = 0.4502 Ω/kft (effective impedance, Table 9, steel conduit, PF 0.85; NEC 2017 Table 9 values); Imax = min(ampacity / 1, V × target × 1000 / (2 × L × Z)); Lmax = V × target × 1000 / (2 × I × Z). Boundaries are displayed to three decimals; selection uses unrounded values. These are load changes, not permission to change a breaker.

Which assumption changes this selection?

copper: 40 A · 150 ft · 240 V. Alternatives are hypothetical; all results use the same Table 9 model (Table 9, steel conduit, PF 0.85).

AssumptionLoad / route / supplyRequired ampacityMinimum sizeDrop / end voltage
Present route, 3% target40 A / 150 ft / 240 V40 A6 AWG5.403 V (2.25%) / 234.597 V
Reserve more voltage: 2% target40 A / 150 ft / 240 V40 A4 AWG3.541 V (1.48%) / 236.459 V
HVAC equipment: Hypothetical nameplate MCA = 1.25 × running A40 A / 150 ft / 240 V50 A6 AWG5.403 V (2.25%) / 234.597 V

Also covers: hvac 40 amp 150 feet

The same amps, distance and voltage above also describe this equipment, so the result applies to it too. Apply the Key Considerations below; extra equipment conditions are listed here.

  • Use nameplate MCA for conductors and MOCP for protection; neither is running current. Do not multiply an already marked MCA again. Check starting voltage, roof temperature, grouping, disconnect terminals and equipment protection rules separately.

Key Considerations

Use actual load current; check continuous duty separately. The site retains small-conductor protection limits. Verify cable and terminal temperature, equipment voltage range, upstream loss and connections.

Reference: NFPA 70 (NEC), including Articles 215, 240, 310, 430, 440, 547, 625 and 680 as applicable. Verify the adopted edition and equipment instructions. These are calculated examples, not installation approvals.

Frequently Asked Questions

What size wire do I need for a 40 amp circuit at 150 feet?▾
For a 40A/240V circuit at 150 feet, use 6 AWG copper (2.25% drop) or 4 AWG aluminum. The ampacity check uses 40A; voltage drop uses the actual 40A (NEC Chapter 9 Table 9 impedance, Table 9, steel conduit, PF 0.85). Installation adjustments and equipment ratings must be checked separately.
Can I use aluminum wire for a 40 amp circuit?▾
At 40A over 150 ft, use 4 AWG aluminum (2.33% voltage drop). Use only equipment and connectors listed for this aluminum gauge; follow their preparation instructions.
What happens if the voltage drop exceeds 3%?▾
3% is a planning target, not installation approval. Here it means 232.8V at the load before upstream loss. Compare the combined path with the equipment’s operating range.

Need a Custom Calculation?

Different voltage, three-phase, or custom max drop percentage? Use our interactive calculator.

Wire Size Calculator