Wire Sizing

What Size Wire for 40 Amp 100 Feet Away

Pre-calculated NEC-compliant wire size for 40 amps at 100 feet on a 240V single-phase circuit. Immediate answer below.

Recommended Wire Size

Copper
8 AWG
Voltage drop: 2.59% (6.22V)
Voltage at load: 233.8V
Controlling factor: Ampacity (NEC 310.16)
Aluminum
6 AWG
Voltage drop: 2.69% (6.46V)
Voltage at load: 233.5V
Controlling factor: Voltage Drop (3% limit)

Based on NEC Table 310.16 (75°C column), single-phase, 240V, 3% max voltage drop, one-way distance 100 ft.

Wire Comparison Table

Wire SizeAmpacityV-Drop (V)V-Drop (%)V at LoadStatus
14 AWG15A25.12V10.47%214.9V
12 AWG20A15.84V6.6%224.2V
10 AWG30A9.92V4.13%230.1V
8 AWGREC50A6.22V2.59%233.8V
6 AWG65A3.93V1.64%236.1V
4 AWG85A2.46V1.03%237.5V
3 AWG100A1.96V0.82%238V
2 AWG115A1.55V0.65%238.4V
1 AWG130A1.23V0.51%238.8V
1/0 AWG150A0.98V0.41%239V
2/0 AWG175A0.77V0.32%239.2V
3/0 AWG200A0.61V0.26%239.4V
4/0 AWG230A0.49V0.2%239.5V
250 kcmil255A0.41V0.17%239.6V
300 kcmil285A0.34V0.14%239.7V
350 kcmil310A0.29V0.12%239.7V
400 kcmil335A0.26V0.11%239.7V
500 kcmil380A0.21V0.09%239.8V

Table shows all standard AWG/kcmil sizes for 40A at 100 ft on 240V (copper). Green check = meets both ampacity and 3% voltage drop. REC = smallest compliant size.

Key Considerations

For a 40A circuit at 100 feet on 240V, both ampacity and voltage drop must be satisfied. NEC recommends keeping the total voltage drop (feeder + branch) under 5%, with no more than 3% on either segment alone.

Copper conductors at 75°C column (THHN/THWN-2) are assumed. If using 60°C terminations, derate the ampacity to the 60°C column values. Verify the temperature rating of your terminals.

Frequently Asked Questions

What size wire do I need for a 40 amp service at 100 feet?
For a 40A/240V circuit at 100 feet, use 8 AWG copper (2.59% drop) or 6 AWG aluminum. This keeps voltage drop within the NEC-recommended 3% limit.
Can I use aluminum wire for a 40 amp circuit?
Yes. Aluminum wire is a cost-effective alternative for larger circuits. For 40A at 100 feet, use 6 AWG aluminum (2.69% voltage drop). Aluminum requires AL-rated connectors and anti-oxidant compound at all terminations.
What happens if the voltage drop exceeds 3%?
Voltage drop above 3% reduces equipment efficiency, can cause motors to overheat, and may violate NEC 210.19(A) Informational Note No. 4. For a 40A circuit at 100 feet on 240V, exceeding 3% means the load receives less than 232.8V, which can damage sensitive electronics and shorten appliance lifespan.

Need a Custom Calculation?

Different voltage, three-phase, or custom max drop percentage? Use our interactive calculator.

Wire Size Calculator