Wire Size for HVAC Unit — 40 Amp 100 Feet
Table-based wire size estimate for 40 amps at 100 feet on a 240V single-phase circuit. Immediate answer below.
Updated October 24, 2026
Recommended Wire Size
Required ampacity: 40 A × 1 = 40 A. Drop uses 40 A. Based on NEC Table 310.16 (75°C column), single-phase, 240V, 3% max voltage drop, one-way distance 100 ft.
Wire Comparison Table
| Wire Size | Ampacity | V-Drop (V) | V-Drop (%) | V at Load | Status |
|---|---|---|---|---|---|
| 12 AWG | 20A | 15.84V | 6.6% | 224.2V | |
| 10 AWG | 30A | 9.92V | 4.13% | 230.1V | |
| 8 AWGREC | 50A | 6.22V | 2.59% | 233.8V | |
| 6 AWG | 65A | 3.93V | 1.64% | 236.1V | |
| 4 AWG | 85A | 2.46V | 1.03% | 237.5V |
Table shows nearby candidate sizes for 40A at 100 ft on 240V (copper). Green check = meets both ampacity and 3% voltage drop. REC = smallest size meeting these two model checks. See the full conductor tables for other sizes.
Operating voltage through compressor start
The former generic route is included here. Verify whether the circuit supplies a single compressor or a packaged assembly with fans and controls; that distinction affects the applicable nameplate information. Use running current to evaluate normal terminal voltage and manufacturer starting data to assess the separate compressor acceleration event.
Operating boundaries: 40 A, 100 ft, 240 V, copper
Ampacity sets the minimum: 8 AWG supports 50 A against the 40.000 A requirement. At 40 A it can reach 115.681 ft before the 3% drop target takes over. Shortening this 100 ft route alone cannot reduce the ampacity floor. One set suffices in this model.
10 AWG cannot carry this assumed load: its current ceiling after the ×1 allowance is 30.000 A. At the present 100 ft, its drop ceiling is 29.032 A. Both checks first allow that smaller conductor at or below 29.032 A, a reduction of 10.968 A. Distance alone cannot fix its ampacity shortfall.
For the selected 8 AWG, increasing load beyond 46.272 A changes the choice: voltage drop reaches its limit first. That leaves 6.272 A above the present load. With current fixed, route growth above 115.681 ft also requires reselection, a margin of 15.681 ft.
A 2% budget is 4.800 V instead of 7.200 V. At 40 A, the existing conductor’s length ceiling falls to 77.121 ft; at 100 ft, its combined current ceiling becomes 30.848 A. The unchanged inputs now select 6 AWG, giving 3.928 V (1.637%).
- Current −10%: 36.000 A / 100.000 ft → 8 AWG (2.334%).
- Current +10%: 44.000 A / 100.000 ft → 8 AWG (2.853%).
- Route −10%: 40.000 A / 90.000 ft → 8 AWG (2.334%).
- Route +10%: 40.000 A / 110.000 ft → 8 AWG (2.853%).
Basis: R = 0.778 Ω/kft at 75°C; Imax = min(ampacity / 1, V × target × 1000 / (2 × L × R)); Lmax = V × target × 1000 / (2 × I × R). Boundaries are displayed to three decimals; selection uses unrounded values. These are load changes, not permission to change a breaker.
Which assumption changes this selection?
copper: 40 A · 100 ft · 240 V. Alternatives are hypothetical; all results use the site resistance table.
| Assumption | Load / route / supply | Required ampacity | Minimum size | Drop / end voltage |
|---|---|---|---|---|
| Present route, 3% target | 40 A / 100 ft / 240 V | 40 A | 8 AWG | 6.224 V (2.59%) / 233.776 V |
| Reserve more voltage: 2% target | 40 A / 100 ft / 240 V | 40 A | 6 AWG | 3.928 V (1.64%) / 236.072 V |
| HVAC equipment: Hypothetical nameplate MCA = 1.25 × running A | 40 A / 100 ft / 240 V | 50 A | 8 AWG | 6.224 V (2.59%) / 233.776 V |
Also covers: 40 amp 100 feet
This merged scenario shares the route inputs above. Apply the Key Considerations below; any additional equipment conditions are listed here.
- Use actual load current; check continuous duty separately. The site retains small-conductor protection limits. Verify cable and terminal temperature, equipment voltage range, upstream loss and connections.
Key Considerations
Use nameplate MCA for conductors and MOCP for protection; neither is running current. Do not multiply an already marked MCA again. Check starting voltage, roof temperature, grouping, disconnect terminals and equipment protection rules separately.
Reference: NFPA 70 (NEC), including Articles 215, 240, 310, 430, 440, 547, 625 and 680 as applicable. Verify the adopted edition and equipment instructions. These are calculated examples, not installation approvals.
Frequently Asked Questions
What size wire do I need for a HVAC running-load estimate at 100 feet?▾
Can I use aluminum wire for a 40 amp circuit?▾
What happens if the voltage drop exceeds 3%?▾