Wire Sizing

Wire Size for HVAC Unit — 20 Amp 50 Feet

Pre-calculated NEC-compliant wire size for 20 amps at 50 feet on a 240V single-phase circuit. Immediate answer below.

Recommended Wire Size

Copper
12 AWG
Voltage drop: 1.65% (3.96V)
Voltage at load: 236V
Controlling factor: Ampacity (NEC 310.16)
Aluminum
10 AWG
Voltage drop: 1.7% (4.08V)
Voltage at load: 235.9V
Controlling factor: Ampacity (NEC 310.16)

Based on NEC Table 310.16 (75°C column), single-phase, 240V, 3% max voltage drop, one-way distance 50 ft.

Wire Comparison Table

Wire SizeAmpacityV-Drop (V)V-Drop (%)V at LoadStatus
14 AWG15A6.28V2.62%233.7V
12 AWGREC20A3.96V1.65%236V
10 AWG30A2.48V1.03%237.5V
8 AWG50A1.56V0.65%238.4V
6 AWG65A0.98V0.41%239V
4 AWG85A0.62V0.26%239.4V
3 AWG100A0.49V0.2%239.5V
2 AWG115A0.39V0.16%239.6V
1 AWG130A0.31V0.13%239.7V
1/0 AWG150A0.24V0.1%239.8V
2/0 AWG175A0.19V0.08%239.8V
3/0 AWG200A0.15V0.06%239.8V
4/0 AWG230A0.12V0.05%239.9V
250 kcmil255A0.1V0.04%239.9V
300 kcmil285A0.09V0.04%239.9V
350 kcmil310A0.07V0.03%239.9V
400 kcmil335A0.06V0.03%239.9V
500 kcmil380A0.05V0.02%239.9V

Table shows all standard AWG/kcmil sizes for 20A at 50 ft on 240V (copper). Green check = meets both ampacity and 3% voltage drop. REC = smallest compliant size.

Key Considerations

For a 20A circuit at 50 feet on 240V, both ampacity and voltage drop must be satisfied. NEC recommends keeping the total voltage drop (feeder + branch) under 5%, with no more than 3% on either segment alone.

Copper conductors at 75°C column (THHN/THWN-2) are assumed. If using 60°C terminations, derate the ampacity to the 60°C column values. Verify the temperature rating of your terminals.

Frequently Asked Questions

What size wire do I need for a 20 amp service at 50 feet?
For a 20A/240V circuit at 50 feet, use 12 AWG copper (1.65% drop) or 10 AWG aluminum. This keeps voltage drop within the NEC-recommended 3% limit.
Can I use aluminum wire for a 20 amp circuit?
Yes. Aluminum wire is a cost-effective alternative for larger circuits. For 20A at 50 feet, use 10 AWG aluminum (1.7% voltage drop). Aluminum requires AL-rated connectors and anti-oxidant compound at all terminations.
What happens if the voltage drop exceeds 3%?
Voltage drop above 3% reduces equipment efficiency, can cause motors to overheat, and may violate NEC 210.19(A) Informational Note No. 4. For a 20A circuit at 50 feet on 240V, exceeding 3% means the load receives less than 232.8V, which can damage sensitive electronics and shorten appliance lifespan.

Need a Custom Calculation?

Different voltage, three-phase, or custom max drop percentage? Use our interactive calculator.

Wire Size Calculator