Wire Sizing

Wire Size for HVAC Unit — 20 Amp 50 Feet

Table-based wire size estimate for 20 amps at 50 feet on a 240V single-phase circuit. Immediate answer below.

Updated November 12, 2026

Recommended Wire Size

Copper
12 AWG
Voltage drop: 1.45% (3.472V)
Voltage at load: 236.53V
Ampacity used: 20 A (60°C column). Controlling factor: Ampacity (NEC 310.16)
Aluminum
10 AWG
Voltage drop: 1.44% (3.466V)
Voltage at load: 236.53V
Ampacity used: 25 A (60°C column). Controlling factor: Ampacity (NEC 310.16)

Required ampacity: 20 A × 1 = 20 A. Drop uses 20 A. Ampacity: NEC Table 310.16, 60°C column (NEC 110.14(C) default for circuits of 100 A or less; equipment marked for 75°C terminals can allow the 75°C column), single-phase, 240V, 3% max voltage drop, one-way distance 50 ft.

Voltage drop uses AC resistance and reactance from NEC Chapter 9 Table 9 (NEC 2017 Table 9 values) for conductors in steel conduit at 0.85 lagging power factor, effective Z = R × PF + XL × sin(acos PF), single-phase, one set, VD = 2 × I × Z × L / 1000. Ampacity uses NEC 2023 Table 310.16 at 30°C ambient with no more than three current-carrying conductors. These are the same engine and defaults as the wire size calculator (steel conduit, PF 0.85).

Wire Comparison Table

Wire SizeAmpacityV-Drop (V)V-Drop (%)V at LoadStatus
14 AWG15A5.347V2.23%234.65V
12 AWGREC20A3.472V1.45%236.53V
10 AWG30A2.106V0.88%237.89V
8 AWG40A1.394V0.58%238.61V
6 AWG55A0.9V0.38%239.1V

Table shows nearby candidate sizes for 20A at 50 ft on 240V (copper). Green check = meets both ampacity and 3% voltage drop (Table 9, steel conduit, PF 0.85). REC = smallest size meeting these two model checks. See the full conductor tables for other sizes.

Keep MCA separate from the breaker label

For a small condenser or packaged unit, photograph or transcribe the electrical nameplate before selecting the circuit. Running amperes, MCA and MOCP serve different purposes. This short-route estimate does not automatically convert between them, and it cannot override equipment instructions that specify a particular conductor or protective device.

Why this copper conductor?

12 AWG has a site ampacity of 20 A against a required 20 A. Table 9 lists R = 2 and XL = 0.068 Ω/kft (steel conduit), so at PF 0.85 its effective Z is 1.7358 Ω/kft. Substituting the actual load into 2 × 20 × 50 × 1.7358 / 1000 gives 3.472 V (1.45%).

The next smaller size, 14 AWG, has 15 A of site ampacity and 2.23% drop on this route. It fails the ampacity requirement.

3% route-length limit: 103.7 ft one way; remaining margin: 53.7 ft. This margin excludes upstream loss and does not authorize extra load.

Which assumption changes this selection?

copper: 20 A · 50 ft · 240 V. Alternatives are hypothetical; all results use the same Table 9 model (Table 9, steel conduit, PF 0.85).

AssumptionLoad / route / supplyRequired ampacityMinimum sizeDrop / end voltage
Present route, 3% target20 A / 50 ft / 240 V20 A12 AWG3.472 V (1.45%) / 236.528 V
Reserve more voltage: 2% target20 A / 50 ft / 240 V20 A12 AWG3.472 V (1.45%) / 236.528 V
HVAC equipment: Hypothetical nameplate MCA = 1.25 × running A20 A / 50 ft / 240 V25 A10 AWG2.106 V (0.88%) / 237.894 V

The alternative MCA is a hypothetical terminal/nameplate constraint, not a calculated equipment MCA. Running current stays fixed, so a change of conductor here comes from the ampacity screen. Replace this assumption with the marked MCA; do not multiply an existing MCA again.

3% → 2% retains 12 AWG → 12 AWG. Load-voltage gain: 0.000 V. Original conductor’s 2% length limit: 69.1 ft one way.

Key Considerations

Read the equipment nameplate MCA (minimum circuit ampacity) and MOCP (maximum overcurrent protection) separately. MOCP is a protection ceiling, not the operating current and not the conductor ampacity to copy into this model.

These estimates use the stated amperes as running current with an ampacity factor of 1. They do not calculate MCA. Compare the recommendation with the marked MCA; do not add a second blanket 125% factor to a marked MCA that already includes equipment allowances.

A steady running-current result does not predict compressor starting voltage. Check locked-rotor data, starting method and source impedance, especially where the contactor or compressor has a restricted operating-voltage range.

Roof temperature, grouped conductors and disconnect terminal ratings can reduce usable ampacity. Equipment-specific Article 440 protection rules require a separate review; this tool retains its conservative small-conductor limits.

Reference: NFPA 70 (NEC), including Articles 215, 240, 310, 430, 440, 547, 625 and 680 as applicable. Verify the adopted edition and equipment instructions. These are calculated examples, not installation approvals.

Frequently Asked Questions

What size wire do I need for a HVAC running-load estimate at 50 feet?▾
For a 20A/240V circuit at 50 feet, use 12 AWG copper (1.45% drop) or 10 AWG aluminum. The ampacity check uses 20A; voltage drop uses the actual 20A (NEC Chapter 9 Table 9 impedance, Table 9, steel conduit, PF 0.85). Installation adjustments and equipment ratings must be checked separately.
Can I use aluminum wire for a 20 amp circuit?▾
At 20A over 50 ft, use 10 AWG aluminum (1.44% voltage drop). Use only equipment and connectors listed for this aluminum gauge; follow their preparation instructions.
What happens if the voltage drop exceeds 3%?▾
3% is a planning target, not installation approval. Here it means 232.8V at the load before upstream loss. Compare the combined path with the equipment’s operating range.

Need a Custom Calculation?

Different voltage, three-phase, or custom max drop percentage? Use our interactive calculator.

Wire Size Calculator