Wire Sizing

Wire Size for Pool Pump — 20 Amp 100 Feet

Pre-calculated NEC-compliant wire size for 20 amps at 100 feet on a 240V single-phase circuit. Immediate answer below.

Recommended Wire Size

Copper
10 AWG
Voltage drop: 2.07% (4.96V)
Voltage at load: 235V
Controlling factor: Voltage Drop (3% limit)
Aluminum
8 AWG
Voltage drop: 2.13% (5.12V)
Voltage at load: 234.9V
Controlling factor: Voltage Drop (3% limit)

Based on NEC Table 310.16 (75°C column), single-phase, 240V, 3% max voltage drop, one-way distance 100 ft.

Wire Comparison Table

Wire SizeAmpacityV-Drop (V)V-Drop (%)V at LoadStatus
14 AWG15A12.56V5.23%227.4V
12 AWG20A7.92V3.3%232.1V
10 AWGREC30A4.96V2.07%235V
8 AWG50A3.11V1.3%236.9V
6 AWG65A1.96V0.82%238V
4 AWG85A1.23V0.51%238.8V
3 AWG100A0.98V0.41%239V
2 AWG115A0.78V0.32%239.2V
1 AWG130A0.62V0.26%239.4V
1/0 AWG150A0.49V0.2%239.5V
2/0 AWG175A0.39V0.16%239.6V
3/0 AWG200A0.31V0.13%239.7V
4/0 AWG230A0.24V0.1%239.8V
250 kcmil255A0.21V0.09%239.8V
300 kcmil285A0.17V0.07%239.8V
350 kcmil310A0.15V0.06%239.9V
400 kcmil335A0.13V0.05%239.9V
500 kcmil380A0.1V0.04%239.9V

Table shows all standard AWG/kcmil sizes for 20A at 100 ft on 240V (copper). Green check = meets both ampacity and 3% voltage drop. REC = smallest compliant size.

Key Considerations

For a 20A circuit at 100 feet on 240V, both ampacity and voltage drop must be satisfied. NEC recommends keeping the total voltage drop (feeder + branch) under 5%, with no more than 3% on either segment alone.

Copper conductors at 75°C column (THHN/THWN-2) are assumed. If using 60°C terminations, derate the ampacity to the 60°C column values. Verify the temperature rating of your terminals.

Frequently Asked Questions

What size wire do I need for a 20 amp service at 100 feet?
For a 20A/240V circuit at 100 feet, use 10 AWG copper (2.07% drop) or 8 AWG aluminum. This keeps voltage drop within the NEC-recommended 3% limit.
Can I use aluminum wire for a 20 amp circuit?
Yes. Aluminum wire is a cost-effective alternative for larger circuits. For 20A at 100 feet, use 8 AWG aluminum (2.13% voltage drop). Aluminum requires AL-rated connectors and anti-oxidant compound at all terminations.
What happens if the voltage drop exceeds 3%?
Voltage drop above 3% reduces equipment efficiency, can cause motors to overheat, and may violate NEC 210.19(A) Informational Note No. 4. For a 20A circuit at 100 feet on 240V, exceeding 3% means the load receives less than 232.8V, which can damage sensitive electronics and shorten appliance lifespan.

Need a Custom Calculation?

Different voltage, three-phase, or custom max drop percentage? Use our interactive calculator.

Wire Size Calculator