Wire Sizing

What Size Wire for 20 Amp 50 Feet Away

Table-based wire size estimate for 20 amps at 50 feet on a 120V single-phase circuit. Immediate answer below.

Updated November 12, 2026

Recommended Wire Size

Copper
12 AWG
Voltage drop: 2.89% (3.472V)
Voltage at load: 116.53V
Ampacity used: 20 A (60°C column). Controlling factor: Ampacity (NEC 310.16)
Aluminum
10 AWG
Voltage drop: 2.89% (3.466V)
Voltage at load: 116.53V
Ampacity used: 25 A (60°C column). Controlling factor: Ampacity (NEC 310.16)

Required ampacity: 20 A × 1 = 20 A. Drop uses 20 A. Ampacity: NEC Table 310.16, 60°C column (NEC 110.14(C) default for circuits of 100 A or less; equipment marked for 75°C terminals can allow the 75°C column), single-phase, 120V, 3% max voltage drop, one-way distance 50 ft.

Voltage drop uses AC resistance and reactance from NEC Chapter 9 Table 9 (NEC 2017 Table 9 values) for conductors in steel conduit at 0.85 lagging power factor, effective Z = R × PF + XL × sin(acos PF), single-phase, one set, VD = 2 × I × Z × L / 1000. Ampacity uses NEC 2023 Table 310.16 at 30°C ambient with no more than three current-carrying conductors. These are the same engine and defaults as the wire size calculator (steel conduit, PF 0.85).

Wire Comparison Table

Wire SizeAmpacityV-Drop (V)V-Drop (%)V at LoadStatus
14 AWG15A5.347V4.46%114.65V
12 AWGREC20A3.472V2.89%116.53V
10 AWG30A2.106V1.76%117.89V
8 AWG40A1.394V1.16%118.61V
6 AWG55A0.9V0.75%119.1V

Table shows nearby candidate sizes for 20A at 50 ft on 120V (copper). Green check = meets both ampacity and 3% voltage drop (Table 9, steel conduit, PF 0.85). REC = smallest size meeting these two model checks. See the full conductor tables for other sizes.

Wiring method before insulation rating

Check whether the proposed installation uses a cable assembly or individual conductors in raceway. Cable-specific ampacity restrictions and terminal ratings can differ from the 75°C reference column used here. A marking on conductor insulation alone is not enough to justify the table ampacity for the completed branch circuit.

Operating boundaries: 20 A, 50 ft, 120 V, copper

Ampacity sets the minimum: 12 AWG supports 20 A (60°C column) against the 20.000 A requirement. At 20 A it can reach 51.849 ft before the 3% drop target takes over. Shortening this 50 ft route alone cannot reduce the ampacity floor. One set suffices in this model.

14 AWG cannot carry this assumed load: its current ceiling after the ×1 allowance is 15.000 A. At the present 50 ft, its drop ceiling is 13.466 A. Both checks first allow that smaller conductor at or below 13.466 A, a reduction of 6.534 A. Distance alone cannot fix its ampacity shortfall.

For the selected 12 AWG, increasing load beyond 20.000 A changes the choice: ampacity reaches its limit first. That leaves 0.000 A above the present load. With current fixed, route growth above 51.849 ft also requires reselection, a margin of 1.849 ft.

A 2% budget is 2.400 V instead of 3.600 V. At 20 A, the existing conductor’s length ceiling falls to 34.566 ft; at 50 ft, its combined current ceiling becomes 13.826 A. The unchanged inputs now select 10 AWG, giving 2.106 V (1.755%).

  • Current −10%: 18.000 A / 50.000 ft → 12 AWG (2.604%).
  • Current +10%: 22.000 A / 50.000 ft → 10 AWG (1.931%).
  • Route −10%: 20.000 A / 45.000 ft → 12 AWG (2.604%).
  • Route +10%: 20.000 A / 55.000 ft → 10 AWG (1.931%).

Basis: Z = 1.7358 Ω/kft (effective impedance, Table 9, steel conduit, PF 0.85; NEC 2017 Table 9 values); Imax = min(ampacity / 1, V × target × 1000 / (2 × L × Z)); Lmax = V × target × 1000 / (2 × I × Z). Boundaries are displayed to three decimals; selection uses unrounded values. These are load changes, not permission to change a breaker.

Which assumption changes this selection?

copper: 20 A · 50 ft · 120 V. Alternatives are hypothetical; all results use the same Table 9 model (Table 9, steel conduit, PF 0.85).

AssumptionLoad / route / supplyRequired ampacityMinimum sizeDrop / end voltage
Present route, 3% target20 A / 50 ft / 120 V20 A12 AWG3.472 V (2.89%) / 116.528 V
Reserve more voltage: 2% target20 A / 50 ft / 120 V20 A10 AWG2.106 V (1.76%) / 117.894 V
General branch circuit: Same assumed watts at twice the supply voltage10 A / 50 ft / 240 V10 A14 AWG2.673 V (1.11%) / 237.327 V

Key Considerations

Use actual load current; check continuous duty separately. The site retains small-conductor protection limits. Verify cable and terminal temperature, equipment voltage range, upstream loss and connections.

Reference: NFPA 70 (NEC), including Articles 215, 240, 310, 430, 440, 547, 625 and 680 as applicable. Verify the adopted edition and equipment instructions. These are calculated examples, not installation approvals.

Frequently Asked Questions

What size wire do I need for a 20 amp circuit at 50 feet?▾
For a 20A/120V circuit at 50 feet, use 12 AWG copper (2.89% drop) or 10 AWG aluminum. The ampacity check uses 20A; voltage drop uses the actual 20A (NEC Chapter 9 Table 9 impedance, Table 9, steel conduit, PF 0.85). Installation adjustments and equipment ratings must be checked separately.
Can I use aluminum wire for a 20 amp circuit?▾
At 20A over 50 ft, use 10 AWG aluminum (2.89% voltage drop). Use only equipment and connectors listed for this aluminum gauge; follow their preparation instructions.
What happens if the voltage drop exceeds 3%?▾
3% is a planning target, not installation approval. Here it means 116.4V at the load before upstream loss. Compare the combined path with the equipment’s operating range.

Need a Custom Calculation?

Different voltage, three-phase, or custom max drop percentage? Use our interactive calculator.

Wire Size Calculator