Wire Sizing

What Size Wire for 20 Amp 150 Feet Away

Pre-calculated NEC-compliant wire size for 20 amps at 150 feet on a 120V single-phase circuit. Immediate answer below.

Recommended Wire Size

Copper
6 AWG
Voltage drop: 2.46% (2.95V)
Voltage at load: 117.1V
Controlling factor: Voltage Drop (3% limit)
Aluminum
4 AWG
Voltage drop: 2.54% (3.05V)
Voltage at load: 117V
Controlling factor: Voltage Drop (3% limit)

Based on NEC Table 310.16 (75°C column), single-phase, 120V, 3% max voltage drop, one-way distance 150 ft.

Wire Comparison Table

Wire SizeAmpacityV-Drop (V)V-Drop (%)V at LoadStatus
14 AWG15A18.84V15.7%101.2V
12 AWG20A11.88V9.9%108.1V
10 AWG30A7.44V6.2%112.6V
8 AWG50A4.67V3.89%115.3V
6 AWGREC65A2.95V2.46%117.1V
4 AWG85A1.85V1.54%118.2V
3 AWG100A1.47V1.23%118.5V
2 AWG115A1.16V0.97%118.8V
1 AWG130A0.92V0.77%119.1V
1/0 AWG150A0.73V0.61%119.3V
2/0 AWG175A0.58V0.48%119.4V
3/0 AWG200A0.46V0.38%119.5V
4/0 AWG230A0.36V0.3%119.6V
250 kcmil255A0.31V0.26%119.7V
300 kcmil285A0.26V0.21%119.7V
350 kcmil310A0.22V0.18%119.8V
400 kcmil335A0.19V0.16%119.8V
500 kcmil380A0.15V0.13%119.8V

Table shows all standard AWG/kcmil sizes for 20A at 150 ft on 120V (copper). Green check = meets both ampacity and 3% voltage drop. REC = smallest compliant size.

Key Considerations

For a 20A circuit at 150 feet on 120V, both ampacity and voltage drop must be satisfied. NEC recommends keeping the total voltage drop (feeder + branch) under 5%, with no more than 3% on either segment alone.

Copper conductors at 75°C column (THHN/THWN-2) are assumed. If using 60°C terminations, derate the ampacity to the 60°C column values. Verify the temperature rating of your terminals.

Frequently Asked Questions

What size wire do I need for a 20 amp service at 150 feet?
For a 20A/120V circuit at 150 feet, use 6 AWG copper (2.46% drop) or 4 AWG aluminum. This keeps voltage drop within the NEC-recommended 3% limit.
Can I use aluminum wire for a 20 amp circuit?
Yes. Aluminum wire is a cost-effective alternative for larger circuits. For 20A at 150 feet, use 4 AWG aluminum (2.54% voltage drop). Aluminum requires AL-rated connectors and anti-oxidant compound at all terminations.
What happens if the voltage drop exceeds 3%?
Voltage drop above 3% reduces equipment efficiency, can cause motors to overheat, and may violate NEC 210.19(A) Informational Note No. 4. For a 20A circuit at 150 feet on 120V, exceeding 3% means the load receives less than 116.4V, which can damage sensitive electronics and shorten appliance lifespan.

Need a Custom Calculation?

Different voltage, three-phase, or custom max drop percentage? Use our interactive calculator.

Wire Size Calculator