What Size Wire for 20 Amp 200 Feet Away
Table-based wire size estimate for 20 amps at 200 feet on a 120V single-phase circuit. Immediate answer below.
Updated November 12, 2026
Recommended Wire Size
Required ampacity: 20 A × 1 = 20 A. Drop uses 20 A. Ampacity: NEC Table 310.16, 60°C column (NEC 110.14(C) default for circuits of 100 A or less; equipment marked for 75°C terminals can allow the 75°C column), single-phase, 120V, 3% max voltage drop, one-way distance 200 ft.
Voltage drop uses AC resistance and reactance from NEC Chapter 9 Table 9 (NEC 2017 Table 9 values) for conductors in steel conduit at 0.85 lagging power factor, effective Z = R × PF + XL × sin(acos PF), single-phase, one set, VD = 2 × I × Z × L / 1000. Ampacity uses NEC 2023 Table 310.16 at 30°C ambient with no more than three current-carrying conductors. These are the same engine and defaults as the wire size calculator (steel conduit, PF 0.85).
Wire Comparison Table
| Wire Size | Ampacity | V-Drop (V) | V-Drop (%) | V at Load | Status |
|---|---|---|---|---|---|
| 8 AWG | 40A | 5.578V | 4.65% | 114.42V | |
| 6 AWG | 55A | 3.602V | 3% | 116.4V | |
| 4 AWGREC | 70A | 2.361V | 1.97% | 117.64V | |
| 3 AWG | 85A | 1.949V | 1.62% | 118.05V | |
| 2 AWG | 95A | 1.6V | 1.33% | 118.4V |
Table shows nearby candidate sizes for 20A at 200 ft on 120V (copper). Green check = meets both ampacity and 3% voltage drop (Table 9, steel conduit, PF 0.85). REC = smallest size meeting these two model checks. See the full conductor tables for other sizes.
Remote outlets and extension leads
A long fixed branch to an outdoor work area may be followed by another flexible cord. Record the cord gauge and actual length as a separate segment, and check its permitted use and condition. Upsizing the fixed run does not remove voltage loss from an undersized extension or a poor plug connection.
Operating boundaries: 20 A, 200 ft, 120 V, copper
Voltage drop controls: the ampacity floor is 12 AWG, but its 3% route limit at 20 A is only 51.849 ft. The 200 ft route therefore needs 4 AWG. One set meets both checks; parallel conductors are not required by this model.
6 AWG has enough ampacity, but the route must shrink from 200 ft to at most 199.905 ft (shorten by 0.095 ft) to meet 3% at 20 A. Alternatively, keep the route and reduce current to at most 19.990 A, down 0.010 A. Either change makes the smaller size eligible; reducing both inputs further may permit another size.
For the selected 4 AWG, increasing load beyond 30.497 A changes the choice: voltage drop reaches its limit first. That leaves 10.497 A above the present load. With current fixed, route growth above 304.974 ft also requires reselection, a margin of 104.974 ft.
A 2% budget is 2.400 V instead of 3.600 V. At 20 A, the existing conductor’s length ceiling falls to 203.316 ft; at 200 ft, its combined current ceiling becomes 20.332 A. The unchanged inputs still select 4 AWG, giving 2.361 V (1.967%).
- Current −10%: 18.000 A / 200.000 ft → 6 AWG (2.701%).
- Current +10%: 22.000 A / 200.000 ft → 4 AWG (2.164%).
- Route −10%: 20.000 A / 180.000 ft → 6 AWG (2.701%).
- Route +10%: 20.000 A / 220.000 ft → 4 AWG (2.164%).
Basis: Z = 0.2951 Ω/kft (effective impedance, Table 9, steel conduit, PF 0.85; NEC 2017 Table 9 values); Imax = min(ampacity / 1, V × target × 1000 / (2 × L × Z)); Lmax = V × target × 1000 / (2 × I × Z). Boundaries are displayed to three decimals; selection uses unrounded values. These are load changes, not permission to change a breaker.
Which assumption changes this selection?
copper: 20 A · 200 ft · 120 V. Alternatives are hypothetical; all results use the same Table 9 model (Table 9, steel conduit, PF 0.85).
| Assumption | Load / route / supply | Required ampacity | Minimum size | Drop / end voltage |
|---|---|---|---|---|
| Present route, 3% target | 20 A / 200 ft / 120 V | 20 A | 4 AWG | 2.361 V (1.97%) / 117.639 V |
| Reserve more voltage: 2% target | 20 A / 200 ft / 120 V | 20 A | 4 AWG | 2.361 V (1.97%) / 117.639 V |
| General branch circuit: Same assumed watts at twice the supply voltage | 10 A / 200 ft / 240 V | 10 A | 12 AWG | 6.943 V (2.89%) / 233.057 V |
Key Considerations
Use actual load current; check continuous duty separately. The site retains small-conductor protection limits. Verify cable and terminal temperature, equipment voltage range, upstream loss and connections.
Reference: NFPA 70 (NEC), including Articles 215, 240, 310, 430, 440, 547, 625 and 680 as applicable. Verify the adopted edition and equipment instructions. These are calculated examples, not installation approvals.
Frequently Asked Questions
What size wire do I need for a 20 amp circuit at 200 feet?▾
Can I use aluminum wire for a 20 amp circuit?▾
What happens if the voltage drop exceeds 3%?▾
Related Wire Size Calculations
Need a Custom Calculation?
Different voltage, three-phase, or custom max drop percentage? Use our interactive calculator.
Wire Size Calculator