Wire Sizing

What Size Wire for 80 Amp 100 Feet Away

Pre-calculated NEC-compliant wire size for 80 amps at 100 feet on a 240V single-phase circuit. Immediate answer below.

Recommended Wire Size

Copper
4 AWG
Voltage drop: 2.05% (4.93V)
Voltage at load: 235.1V
Controlling factor: Ampacity (NEC 310.16)
Aluminum
2 AWG
Voltage drop: 2.13% (5.1V)
Voltage at load: 234.9V
Controlling factor: Ampacity (NEC 310.16)

Based on NEC Table 310.16 (75°C column), single-phase, 240V, 3% max voltage drop, one-way distance 100 ft.

Wire Comparison Table

Wire SizeAmpacityV-Drop (V)V-Drop (%)V at LoadStatus
14 AWG15A50.24V20.93%189.8V
12 AWG20A31.68V13.2%208.3V
10 AWG30A19.84V8.27%220.2V
8 AWG50A12.45V5.19%227.6V
6 AWG65A7.86V3.27%232.1V
4 AWGREC85A4.93V2.05%235.1V
3 AWG100A3.92V1.63%236.1V
2 AWG115A3.1V1.29%236.9V
1 AWG130A2.46V1.03%237.5V
1/0 AWG150A1.95V0.81%238V
2/0 AWG175A1.55V0.64%238.5V
3/0 AWG200A1.23V0.51%238.8V
4/0 AWG230A0.97V0.41%239V
250 kcmil255A0.82V0.34%239.2V
300 kcmil285A0.69V0.29%239.3V
350 kcmil310A0.59V0.24%239.4V
400 kcmil335A0.51V0.21%239.5V
500 kcmil380A0.41V0.17%239.6V

Table shows all standard AWG/kcmil sizes for 80A at 100 ft on 240V (copper). Green check = meets both ampacity and 3% voltage drop. REC = smallest compliant size.

Key Considerations

For a 80A circuit at 100 feet on 240V, both ampacity and voltage drop must be satisfied. NEC recommends keeping the total voltage drop (feeder + branch) under 5%, with no more than 3% on either segment alone.

Copper conductors at 75°C column (THHN/THWN-2) are assumed. If using 60°C terminations, derate the ampacity to the 60°C column values. Verify the temperature rating of your terminals.

Frequently Asked Questions

What size wire do I need for a 80 amp service at 100 feet?
For a 80A/240V circuit at 100 feet, use 4 AWG copper (2.05% drop) or 2 AWG aluminum. This keeps voltage drop within the NEC-recommended 3% limit.
Can I use aluminum wire for a 80 amp circuit?
Yes. Aluminum wire is a cost-effective alternative for larger circuits. For 80A at 100 feet, use 2 AWG aluminum (2.13% voltage drop). Aluminum requires AL-rated connectors and anti-oxidant compound at all terminations.
What happens if the voltage drop exceeds 3%?
Voltage drop above 3% reduces equipment efficiency, can cause motors to overheat, and may violate NEC 210.19(A) Informational Note No. 4. For a 80A circuit at 100 feet on 240V, exceeding 3% means the load receives less than 232.8V, which can damage sensitive electronics and shorten appliance lifespan.

Need a Custom Calculation?

Different voltage, three-phase, or custom max drop percentage? Use our interactive calculator.

Wire Size Calculator