What Size Wire for 100 Amp 100 Feet Away
Table-based wire size estimate for 100 amps at 100 feet on a 240V single-phase circuit. Immediate answer below.
Updated November 12, 2026
Recommended Wire Size
Required ampacity: 100 A × 1 = 100 A. Drop uses 100 A. Ampacity: NEC Table 310.16, 60°C column (NEC 110.14(C) default for circuits of 100 A or less; equipment marked for 75°C terminals can allow the 75°C column), single-phase, 240V, 3% max voltage drop, one-way distance 100 ft.
Voltage drop uses AC resistance and reactance from NEC Chapter 9 Table 9 (NEC 2017 Table 9 values) for conductors in steel conduit at 0.85 lagging power factor, effective Z = R × PF + XL × sin(acos PF), single-phase, one set, VD = 2 × I × Z × L / 1000. Ampacity uses NEC 2023 Table 310.16 at 30°C ambient with no more than three current-carrying conductors. These are the same engine and defaults as the wire size calculator (steel conduit, PF 0.85).
Wire Comparison Table
| Wire Size | Ampacity | V-Drop (V) | V-Drop (%) | V at Load | Status |
|---|---|---|---|---|---|
| 3 AWG | 85A | 4.872V | 2.03% | 235.13V | |
| 2 AWG | 95A | 4.001V | 1.67% | 236V | |
| 1 AWGREC | 110A | 3.321V | 1.38% | 236.68V | |
| 1/0 AWG | 125A | 2.619V | 1.09% | 237.38V | |
| 2/0 AWG | 145A | 2.269V | 0.95% | 237.73V |
Table shows nearby candidate sizes for 100A at 100 ft on 240V (copper). Green check = meets both ampacity and 3% voltage drop (Table 9, steel conduit, PF 0.85). REC = smallest size meeting these two model checks. See the full conductor tables for other sizes.
Panel rating versus demand
Before pricing a feeder, distinguish a panel marked 100 A from a calculated load of 100 A. This page assumes the latter. A panel supplying intermittent tools may draw less, while a panel supplying heating needs a separate continuous-load calculation. Changing that current changes both the ampacity decision and the loss calculation.
Operating boundaries: 100 A, 100 ft, 240 V, copper
Ampacity sets the minimum: 1 AWG supports 110 A (60°C column) against the 100.000 A requirement. At 100 A it can reach 216.833 ft before the 3% drop target takes over. Shortening this 100 ft route alone cannot reduce the ampacity floor. One set suffices in this model.
2 AWG cannot carry this assumed load: its current ceiling after the ×1 allowance is 95.000 A. At the present 100 ft, its drop ceiling is 179.976 A. Both checks first allow that smaller conductor at or below 95.000 A, a reduction of 5.000 A. Distance alone cannot fix its ampacity shortfall.
For the selected 1 AWG, increasing load beyond 130.000 A changes the choice: ampacity reaches its limit first. That leaves 30.000 A above the present load. With current fixed, route growth above 216.833 ft also requires reselection, a margin of 116.833 ft.
A 2% budget is 4.800 V instead of 7.200 V. At 100 A, the existing conductor’s length ceiling falls to 144.555 ft; at 100 ft, its combined current ceiling becomes 130.000 A. The unchanged inputs still select 1 AWG, giving 3.321 V (1.384%).
- Current −10%: 90.000 A / 100.000 ft → 2 AWG (1.500%).
- Current +10%: 110.000 A / 100.000 ft → 2 AWG (1.834%).
- Route −10%: 100.000 A / 90.000 ft → 1 AWG (1.245%).
- Route +10%: 100.000 A / 110.000 ft → 1 AWG (1.522%).
Basis: Z = 0.1660 Ω/kft (effective impedance, Table 9, steel conduit, PF 0.85; NEC 2017 Table 9 values); Imax = min(ampacity / 1, V × target × 1000 / (2 × L × Z)); Lmax = V × target × 1000 / (2 × I × Z). Boundaries are displayed to three decimals; selection uses unrounded values. These are load changes, not permission to change a breaker.
Which assumption changes this selection?
copper: 100 A · 100 ft · 240 V. Alternatives are hypothetical; all results use the same Table 9 model (Table 9, steel conduit, PF 0.85).
| Assumption | Load / route / supply | Required ampacity | Minimum size | Drop / end voltage |
|---|---|---|---|---|
| Present route, 3% target | 100 A / 100 ft / 240 V | 100 A | 1 AWG | 3.321 V (1.38%) / 236.679 V |
| Reserve more voltage: 2% target | 100 A / 100 ft / 240 V | 100 A | 1 AWG | 3.321 V (1.38%) / 236.679 V |
| Sub-panel feeder: Feeder allocated 1% of supply voltage | 100 A / 100 ft / 240 V | 100 A | 2/0 AWG | 2.269 V (0.95%) / 237.731 V |
Key Considerations
Calculate feeder demand, separating continuous loads; panel rating is not demand. Add downstream loss at the same operating condition. Review neutral isolation, equipment grounding and detached-building electrodes; this balanced model does not size an unbalanced neutral.
Reference: NFPA 70 (NEC), including Articles 215, 240, 310, 430, 440, 547, 625 and 680 as applicable. Verify the adopted edition and equipment instructions. These are calculated examples, not installation approvals.
Frequently Asked Questions
What size wire do I need for a 100 amp feeder at 100 feet?▾
Can I use aluminum wire for a 100 amp circuit?▾
What happens if the voltage drop exceeds 3%?▾
Related Wire Size Calculations
Need a Custom Calculation?
Different voltage, three-phase, or custom max drop percentage? Use our interactive calculator.
Wire Size Calculator