Wire Sizing

What Size Wire for 100 Amp 100 Feet Away

Pre-calculated NEC-compliant wire size for 100 amps at 100 feet on a 240V single-phase circuit. Immediate answer below.

Recommended Wire Size

Copper
3 AWG
Voltage drop: 2.04% (4.9V)
Voltage at load: 235.1V
Controlling factor: Ampacity (NEC 310.16)
Aluminum
1 AWG
Voltage drop: 2.11% (5.06V)
Voltage at load: 234.9V
Controlling factor: Ampacity (NEC 310.16)

Based on NEC Table 310.16 (75°C column), single-phase, 240V, 3% max voltage drop, one-way distance 100 ft.

Wire Comparison Table

Wire SizeAmpacityV-Drop (V)V-Drop (%)V at LoadStatus
14 AWG15A62.8V26.17%177.2V
12 AWG20A39.6V16.5%200.4V
10 AWG30A24.8V10.33%215.2V
8 AWG50A15.56V6.48%224.4V
6 AWG65A9.82V4.09%230.2V
4 AWG85A6.16V2.57%233.8V
3 AWGREC100A4.9V2.04%235.1V
2 AWG115A3.88V1.62%236.1V
1 AWG130A3.08V1.28%236.9V
1/0 AWG150A2.44V1.02%237.6V
2/0 AWG175A1.93V0.81%238.1V
3/0 AWG200A1.53V0.64%238.5V
4/0 AWG230A1.22V0.51%238.8V
250 kcmil255A1.03V0.43%239V
300 kcmil285A0.86V0.36%239.1V
350 kcmil310A0.73V0.31%239.3V
400 kcmil335A0.64V0.27%239.4V
500 kcmil380A0.52V0.22%239.5V

Table shows all standard AWG/kcmil sizes for 100A at 100 ft on 240V (copper). Green check = meets both ampacity and 3% voltage drop. REC = smallest compliant size.

Key Considerations

For a 100A circuit at 100 feet on 240V, both ampacity and voltage drop must be satisfied. NEC recommends keeping the total voltage drop (feeder + branch) under 5%, with no more than 3% on either segment alone.

Copper conductors at 75°C column (THHN/THWN-2) are assumed. If using 60°C terminations, derate the ampacity to the 60°C column values. Verify the temperature rating of your terminals.

Frequently Asked Questions

What size wire do I need for a 100 amp service at 100 feet?
For a 100A/240V circuit at 100 feet, use 3 AWG copper (2.04% drop) or 1 AWG aluminum. This keeps voltage drop within the NEC-recommended 3% limit.
Can I use aluminum wire for a 100 amp circuit?
Yes. Aluminum wire is a cost-effective alternative for larger circuits. For 100A at 100 feet, use 1 AWG aluminum (2.11% voltage drop). Aluminum requires AL-rated connectors and anti-oxidant compound at all terminations.
What happens if the voltage drop exceeds 3%?
Voltage drop above 3% reduces equipment efficiency, can cause motors to overheat, and may violate NEC 210.19(A) Informational Note No. 4. For a 100A circuit at 100 feet on 240V, exceeding 3% means the load receives less than 232.8V, which can damage sensitive electronics and shorten appliance lifespan.

Need a Custom Calculation?

Different voltage, three-phase, or custom max drop percentage? Use our interactive calculator.

Wire Size Calculator