Wire Sizing

What Size Wire for 100 Amp 150 Feet Away

Table-based wire size estimate for 100 amps at 150 feet on a 240V single-phase circuit. Immediate answer below.

Updated November 12, 2026

Recommended Wire Size

Copper
1 AWG
Voltage drop: 2.08% (4.981V)
Voltage at load: 235.02V
Ampacity used: 110 A (60°C column). Controlling factor: Ampacity (NEC 310.16)
Aluminum
1/0 AWG
Voltage drop: 2.49% (5.969V)
Voltage at load: 234.03V
Ampacity used: 100 A (60°C column). Controlling factor: Ampacity (NEC 310.16)

Required ampacity: 100 A × 1 = 100 A. Drop uses 100 A. Ampacity: NEC Table 310.16, 60°C column (NEC 110.14(C) default for circuits of 100 A or less; equipment marked for 75°C terminals can allow the 75°C column), single-phase, 240V, 3% max voltage drop, one-way distance 150 ft.

Voltage drop uses AC resistance and reactance from NEC Chapter 9 Table 9 (NEC 2017 Table 9 values) for conductors in steel conduit at 0.85 lagging power factor, effective Z = R × PF + XL × sin(acos PF), single-phase, one set, VD = 2 × I × Z × L / 1000. Ampacity uses NEC 2023 Table 310.16 at 30°C ambient with no more than three current-carrying conductors. These are the same engine and defaults as the wire size calculator (steel conduit, PF 0.85).

Wire Comparison Table

Wire SizeAmpacityV-Drop (V)V-Drop (%)V at LoadStatus
3 AWG85A7.307V3.04%232.69V
2 AWG95A6.001V2.5%234V
1 AWGREC110A4.981V2.08%235.02V
1/0 AWG125A3.929V1.64%236.07V
2/0 AWG145A3.403V1.42%236.6V

Table shows nearby candidate sizes for 100A at 150 ft on 240V (copper). Green check = meets both ampacity and 3% voltage drop (Table 9, steel conduit, PF 0.85). REC = smallest size meeting these two model checks. See the full conductor tables for other sizes.

Feeder and downstream branch allocation

This estimate also applies to a sub-panel feeder. Measure to the downstream panel, then evaluate its longest loaded branch separately. The voltage shown here is at the panel terminals, not at a distant receptacle. A workshop with long internal circuits can need a tighter feeder target even when this run alone meets the displayed limit.

Operating boundaries: 100 A, 150 ft, 240 V, copper

Ampacity sets the minimum: 1 AWG supports 110 A (60°C column) against the 100.000 A requirement. At 100 A it can reach 216.833 ft before the 3% drop target takes over. Shortening this 150 ft route alone cannot reduce the ampacity floor. One set suffices in this model.

2 AWG cannot carry this assumed load: its current ceiling after the ×1 allowance is 95.000 A. At the present 150 ft, its drop ceiling is 119.984 A. Both checks first allow that smaller conductor at or below 95.000 A, a reduction of 5.000 A. Distance alone cannot fix its ampacity shortfall.

For the selected 1 AWG, increasing load beyond 130.000 A changes the choice: ampacity reaches its limit first. That leaves 30.000 A above the present load. With current fixed, route growth above 216.833 ft also requires reselection, a margin of 66.833 ft.

A 2% budget is 4.800 V instead of 7.200 V. At 100 A, the existing conductor’s length ceiling falls to 144.555 ft; at 150 ft, its combined current ceiling becomes 96.370 A. The unchanged inputs now select 1/0 AWG, giving 3.929 V (1.637%).

  • Current −10%: 90.000 A / 150.000 ft → 2 AWG (2.250%).
  • Current +10%: 110.000 A / 150.000 ft → 2 AWG (2.750%).
  • Route −10%: 100.000 A / 135.000 ft → 1 AWG (1.868%).
  • Route +10%: 100.000 A / 165.000 ft → 1 AWG (2.283%).

Basis: Z = 0.1660 Ω/kft (effective impedance, Table 9, steel conduit, PF 0.85; NEC 2017 Table 9 values); Imax = min(ampacity / 1, V × target × 1000 / (2 × L × Z)); Lmax = V × target × 1000 / (2 × I × Z). Boundaries are displayed to three decimals; selection uses unrounded values. These are load changes, not permission to change a breaker.

Which assumption changes this selection?

copper: 100 A · 150 ft · 240 V. Alternatives are hypothetical; all results use the same Table 9 model (Table 9, steel conduit, PF 0.85).

AssumptionLoad / route / supplyRequired ampacityMinimum sizeDrop / end voltage
Present route, 3% target100 A / 150 ft / 240 V100 A1 AWG4.981 V (2.08%) / 235.019 V
Reserve more voltage: 2% target100 A / 150 ft / 240 V100 A1/0 AWG3.929 V (1.64%) / 236.071 V
Sub-panel feeder: Feeder allocated 1% of supply voltage100 A / 150 ft / 240 V100 A250 kcmil2.199 V (0.92%) / 237.801 V

Key Considerations

Calculate feeder demand, separating continuous loads; panel rating is not demand. Add downstream loss at the same operating condition. Review neutral isolation, equipment grounding and detached-building electrodes; this balanced model does not size an unbalanced neutral.

Reference: NFPA 70 (NEC), including Articles 215, 240, 310, 430, 440, 547, 625 and 680 as applicable. Verify the adopted edition and equipment instructions. These are calculated examples, not installation approvals.

Frequently Asked Questions

What size wire do I need for a 100 amp feeder at 150 feet?▾
For a 100A/240V circuit at 150 feet, use 1 AWG copper (2.08% drop) or 1/0 AWG aluminum. The ampacity check uses 100A; voltage drop uses the actual 100A (NEC Chapter 9 Table 9 impedance, Table 9, steel conduit, PF 0.85). Installation adjustments and equipment ratings must be checked separately.
Can I use aluminum wire for a 100 amp circuit?▾
At 100A over 150 ft, use 1/0 AWG aluminum (2.49% voltage drop). Use only equipment and connectors listed for this aluminum gauge; follow their preparation instructions.
What happens if the voltage drop exceeds 3%?▾
3% is a planning target, not installation approval. Here it means 232.8V at the load before upstream loss. Compare the combined path with the equipment’s operating range.

Need a Custom Calculation?

Different voltage, three-phase, or custom max drop percentage? Use our interactive calculator.

Wire Size Calculator