Wire Sizing

What Size Wire for 100 Amp 300 Feet Away

Table-based wire size estimate for 100 amps at 300 feet on a 240V single-phase circuit. Immediate answer below.

Updated November 12, 2026

Recommended Wire Size

Copper
2/0 AWG
Voltage drop: 2.84% (6.807V)
Voltage at load: 233.19V
Ampacity used: 145 A (60°C column). Controlling factor: Voltage Drop (3% limit)
Aluminum
4/0 AWG
Voltage drop: 2.80% (6.712V)
Voltage at load: 233.29V
Ampacity used: 150 A (60°C column). Controlling factor: Voltage Drop (3% limit)

Required ampacity: 100 A × 1 = 100 A. Drop uses 100 A. Ampacity: NEC Table 310.16, 60°C column (NEC 110.14(C) default for circuits of 100 A or less; equipment marked for 75°C terminals can allow the 75°C column), single-phase, 240V, 3% max voltage drop, one-way distance 300 ft.

Voltage drop uses AC resistance and reactance from NEC Chapter 9 Table 9 (NEC 2017 Table 9 values) for conductors in steel conduit at 0.85 lagging power factor, effective Z = R × PF + XL × sin(acos PF), single-phase, one set, VD = 2 × I × Z × L / 1000. Ampacity uses NEC 2023 Table 310.16 at 30°C ambient with no more than three current-carrying conductors. These are the same engine and defaults as the wire size calculator (steel conduit, PF 0.85).

Wire Comparison Table

Wire SizeAmpacityV-Drop (V)V-Drop (%)V at LoadStatus
1 AWG110A9.962V4.15%230.04V
1/0 AWG125A7.858V3.27%232.14V
2/0 AWGREC145A6.807V2.84%233.19V
3/0 AWG165A5.673V2.36%234.33V
4/0 AWG195A4.825V2.01%235.18V

Table shows nearby candidate sizes for 100A at 300 ft on 240V (copper). Green check = meets both ampacity and 3% voltage drop (Table 9, steel conduit, PF 0.85). REC = smallest size meeting these two model checks. See the full conductor tables for other sizes.

Farm loads at the remote building

This estimate also applies to a barn. Water pumping and ventilation may operate together when lighting demand is low, so the largest simultaneous operating combination is more useful than an average monthly energy figure. Verify whether agricultural-location rules apply to the building, especially where livestock can touch conductive equipment.

Operating boundaries: 100 A, 300 ft, 240 V, copper

Voltage drop controls: the ampacity floor is 1 AWG, but its 3% route limit at 100 A is only 216.833 ft. The 300 ft route therefore needs 2/0 AWG. One set meets both checks; parallel conductors are not required by this model.

1/0 AWG has enough ampacity, but the route must shrink from 300 ft to at most 274.866 ft (shorten by 25.134 ft) to meet 3% at 100 A. Alternatively, keep the route and reduce current to at most 91.622 A, down 8.378 A. Either change makes the smaller size eligible; reducing both inputs further may permit another size.

For the selected 2/0 AWG, increasing load beyond 105.777 A changes the choice: voltage drop reaches its limit first. That leaves 5.777 A above the present load. With current fixed, route growth above 317.331 ft also requires reselection, a margin of 17.331 ft.

A 2% budget is 4.800 V instead of 7.200 V. At 100 A, the existing conductor’s length ceiling falls to 211.554 ft; at 300 ft, its combined current ceiling becomes 70.518 A. The unchanged inputs now select 250 kcmil, giving 4.398 V (1.832%).

  • Current −10%: 90.000 A / 300.000 ft → 1/0 AWG (2.947%).
  • Current +10%: 110.000 A / 300.000 ft → 3/0 AWG (2.600%).
  • Route −10%: 100.000 A / 270.000 ft → 1/0 AWG (2.947%).
  • Route +10%: 100.000 A / 330.000 ft → 3/0 AWG (2.600%).

Basis: Z = 0.1134 Ω/kft (effective impedance, Table 9, steel conduit, PF 0.85; NEC 2017 Table 9 values); Imax = min(ampacity / 1, V × target × 1000 / (2 × L × Z)); Lmax = V × target × 1000 / (2 × I × Z). Boundaries are displayed to three decimals; selection uses unrounded values. These are load changes, not permission to change a breaker.

Which assumption changes this selection?

copper: 100 A · 300 ft · 240 V. Alternatives are hypothetical; all results use the same Table 9 model (Table 9, steel conduit, PF 0.85).

AssumptionLoad / route / supplyRequired ampacityMinimum sizeDrop / end voltage
Present route, 3% target100 A / 300 ft / 240 V100 A2/0 AWG6.807 V (2.84%) / 233.193 V
Reserve more voltage: 2% target100 A / 300 ft / 240 V100 A250 kcmil4.398 V (1.83%) / 235.602 V
Barn or detached agricultural building: Hypothetical trench detour adds 50% to route100 A / 450 ft / 240 V100 A250 kcmil6.596 V (2.75%) / 233.404 V

Also covers: barn 100 amp 300 feet

The same amps, distance and voltage above also describe this equipment, so the result applies to it too. Apply the Key Considerations below; extra equipment conditions are listed here.

  • List ventilation, water pumping, lighting and receptacle loads by duty and starting behavior before treating the service or panel rating as demand. Seasonal equipment can change the combination of loads operating together.
  • A detached building needs review of its disconnect, equipment grounding path and grounding electrodes. A long trench does not remove those requirements, and grounding electrodes do not replace the feeder grounding conductor.
  • Agricultural locations may expose wiring to moisture, dust, corrosion or livestock contact. Determine whether Article 547 and equipotential-plane provisions apply to the actual use of the building.
  • Check burial method, wet-location conductor rating, physical protection and accessible terminations. Aluminum can be considered only with compatible listed connections and the manufacturer’s preparation instructions.

Key Considerations

Calculate feeder demand, separating continuous loads; panel rating is not demand. Add downstream loss at the same operating condition. Review neutral isolation, equipment grounding and detached-building electrodes; this balanced model does not size an unbalanced neutral.

Reference: NFPA 70 (NEC), including Articles 215, 240, 310, 430, 440, 547, 625 and 680 as applicable. Verify the adopted edition and equipment instructions. These are calculated examples, not installation approvals.

Frequently Asked Questions

What size wire do I need for a 100 amp feeder at 300 feet?▾
For a 100A/240V circuit at 300 feet, use 2/0 AWG copper (2.84% drop) or 4/0 AWG aluminum. The ampacity check uses 100A; voltage drop uses the actual 100A (NEC Chapter 9 Table 9 impedance, Table 9, steel conduit, PF 0.85). Installation adjustments and equipment ratings must be checked separately.
Can I use aluminum wire for a 100 amp circuit?▾
At 100A over 300 ft, use 4/0 AWG aluminum (2.80% voltage drop). Use only equipment and connectors listed for this aluminum gauge; follow their preparation instructions.
What happens if the voltage drop exceeds 3%?▾
3% is a planning target, not installation approval. Here it means 232.8V at the load before upstream loss. Compare the combined path with the equipment’s operating range.

Need a Custom Calculation?

Different voltage, three-phase, or custom max drop percentage? Use our interactive calculator.

Wire Size Calculator