Wire Sizing

Wire Size for 100 Amp Sub-Panel 200 Feet

Table-based wire size estimate for 100 amps at 200 feet on a 240V single-phase circuit. Immediate answer below.

Updated November 12, 2026

Recommended Wire Size

Copper
1 AWG
Voltage drop: 2.77% (6.641V)
Voltage at load: 233.36V
Ampacity used: 110 A (60°C column). Controlling factor: Ampacity (NEC 310.16)
Aluminum
2/0 AWG
Voltage drop: 2.74% (6.578V)
Voltage at load: 233.42V
Ampacity used: 115 A (60°C column). Controlling factor: Voltage Drop (3% limit)

Required ampacity: 100 A × 1 = 100 A. Drop uses 100 A. Ampacity: NEC Table 310.16, 60°C column (NEC 110.14(C) default for circuits of 100 A or less; equipment marked for 75°C terminals can allow the 75°C column), single-phase, 240V, 3% max voltage drop, one-way distance 200 ft.

Voltage drop uses AC resistance and reactance from NEC Chapter 9 Table 9 (NEC 2017 Table 9 values) for conductors in steel conduit at 0.85 lagging power factor, effective Z = R × PF + XL × sin(acos PF), single-phase, one set, VD = 2 × I × Z × L / 1000. Ampacity uses NEC 2023 Table 310.16 at 30°C ambient with no more than three current-carrying conductors. These are the same engine and defaults as the wire size calculator (steel conduit, PF 0.85).

Wire Comparison Table

Wire SizeAmpacityV-Drop (V)V-Drop (%)V at LoadStatus
3 AWG85A9.743V4.06%230.26V
2 AWG95A8.001V3.33%232V
1 AWGREC110A6.641V2.77%233.36V
1/0 AWG125A5.239V2.18%234.76V
2/0 AWG145A4.538V1.89%235.46V

Table shows nearby candidate sizes for 100A at 200 ft on 240V (copper). Green check = meets both ampacity and 3% voltage drop (Table 9, steel conduit, PF 0.85). REC = smallest size meeting these two model checks. See the full conductor tables for other sizes.

Detached building neutral and grounding

This estimate also applies to a barn. Identify any line-to-neutral loads and the feeder grounding arrangement before choosing a cable assembly. The numerical result assumes a balanced line-to-line load; neutral imbalance, building disconnect provisions and agricultural bonding requirements need their own design review.

Operating boundaries: 100 A, 200 ft, 240 V, copper

Ampacity sets the minimum: 1 AWG supports 110 A (60°C column) against the 100.000 A requirement. At 100 A it can reach 216.833 ft before the 3% drop target takes over. Shortening this 200 ft route alone cannot reduce the ampacity floor. One set suffices in this model.

2 AWG cannot carry this assumed load: its current ceiling after the ×1 allowance is 95.000 A. At the present 200 ft, its drop ceiling is 89.988 A. Both checks first allow that smaller conductor at or below 89.988 A, a reduction of 10.012 A. Distance alone cannot fix its ampacity shortfall.

For the selected 1 AWG, increasing load beyond 108.416 A changes the choice: voltage drop reaches its limit first. That leaves 8.416 A above the present load. With current fixed, route growth above 216.833 ft also requires reselection, a margin of 16.833 ft.

A 2% budget is 4.800 V instead of 7.200 V. At 100 A, the existing conductor’s length ceiling falls to 144.555 ft; at 200 ft, its combined current ceiling becomes 72.278 A. The unchanged inputs now select 2/0 AWG, giving 4.538 V (1.891%).

  • Current −10%: 90.000 A / 200.000 ft → 1 AWG (2.490%).
  • Current +10%: 110.000 A / 200.000 ft → 1/0 AWG (2.401%).
  • Route −10%: 100.000 A / 180.000 ft → 1 AWG (2.490%).
  • Route +10%: 100.000 A / 220.000 ft → 1/0 AWG (2.401%).

Basis: Z = 0.1660 Ω/kft (effective impedance, Table 9, steel conduit, PF 0.85; NEC 2017 Table 9 values); Imax = min(ampacity / 1, V × target × 1000 / (2 × L × Z)); Lmax = V × target × 1000 / (2 × I × Z). Boundaries are displayed to three decimals; selection uses unrounded values. These are load changes, not permission to change a breaker.

Which assumption changes this selection?

copper: 100 A · 200 ft · 240 V. Alternatives are hypothetical; all results use the same Table 9 model (Table 9, steel conduit, PF 0.85).

AssumptionLoad / route / supplyRequired ampacityMinimum sizeDrop / end voltage
Present route, 3% target100 A / 200 ft / 240 V100 A1 AWG6.641 V (2.77%) / 233.359 V
Reserve more voltage: 2% target100 A / 200 ft / 240 V100 A2/0 AWG4.538 V (1.89%) / 235.462 V
Sub-panel feeder: Feeder allocated 1% of supply voltage100 A / 200 ft / 240 V100 A350 kcmil2.380 V (0.99%) / 237.620 V
Barn or detached agricultural building: Hypothetical trench detour adds 50% to route100 A / 300 ft / 240 V100 A2/0 AWG6.807 V (2.84%) / 233.193 V

Also covers: barn 100 amp 200 feet

The same amps, distance and voltage above also describe this equipment, so the result applies to it too. Apply the Key Considerations below; extra equipment conditions are listed here.

  • List ventilation, water pumping, lighting and receptacle loads by duty and starting behavior before treating the service or panel rating as demand. Seasonal equipment can change the combination of loads operating together.
  • A detached building needs review of its disconnect, equipment grounding path and grounding electrodes. A long trench does not remove those requirements, and grounding electrodes do not replace the feeder grounding conductor.
  • Agricultural locations may expose wiring to moisture, dust, corrosion or livestock contact. Determine whether Article 547 and equipotential-plane provisions apply to the actual use of the building.
  • Check burial method, wet-location conductor rating, physical protection and accessible terminations. Aluminum can be considered only with compatible listed connections and the manufacturer’s preparation instructions.

Also covers: 100 amp 200 feet

The same amps, distance and voltage above also describe this equipment, so the result applies to it too. Apply the Key Considerations below; extra equipment conditions are listed here.

  • Use actual load current; check continuous duty separately. The site retains small-conductor protection limits. Verify cable and terminal temperature, equipment voltage range, upstream loss and connections.

Key Considerations

Calculate feeder demand, separating continuous loads; panel rating is not demand. Add downstream loss at the same operating condition. Review neutral isolation, equipment grounding and detached-building electrodes; this balanced model does not size an unbalanced neutral.

Reference: NFPA 70 (NEC), including Articles 215, 240, 310, 430, 440, 547, 625 and 680 as applicable. Verify the adopted edition and equipment instructions. These are calculated examples, not installation approvals.

Frequently Asked Questions

What size wire do I need for a sub-panel feeder at 200 feet?▾
For a 100A/240V circuit at 200 feet, use 1 AWG copper (2.77% drop) or 2/0 AWG aluminum. The ampacity check uses 100A; voltage drop uses the actual 100A (NEC Chapter 9 Table 9 impedance, Table 9, steel conduit, PF 0.85). Installation adjustments and equipment ratings must be checked separately.
Can I use aluminum wire for a 100 amp circuit?▾
At 100A over 200 ft, use 2/0 AWG aluminum (2.74% voltage drop). Use only equipment and connectors listed for this aluminum gauge; follow their preparation instructions.
What happens if the voltage drop exceeds 3%?▾
3% is a planning target, not installation approval. Here it means 232.8V at the load before upstream loss. Compare the combined path with the equipment’s operating range.

Need a Custom Calculation?

Different voltage, three-phase, or custom max drop percentage? Use our interactive calculator.

Wire Size Calculator