What Size Wire for 60 Amp 300 Feet Away
Table-based wire size estimate for 60 amps at 300 feet on a 240V single-phase circuit. Immediate answer below.
Updated November 12, 2026
Recommended Wire Size
Required ampacity: 60 A × 1 = 60 A. Drop uses 60 A. Ampacity: NEC Table 310.16, 60°C column (NEC 110.14(C) default for circuits of 100 A or less; equipment marked for 75°C terminals can allow the 75°C column), single-phase, 240V, 3% max voltage drop, one-way distance 300 ft.
Voltage drop uses AC resistance and reactance from NEC Chapter 9 Table 9 (NEC 2017 Table 9 values) for conductors in steel conduit at 0.85 lagging power factor, effective Z = R × PF + XL × sin(acos PF), single-phase, one set, VD = 2 × I × Z × L / 1000. Ampacity uses NEC 2023 Table 310.16 at 30°C ambient with no more than three current-carrying conductors. These are the same engine and defaults as the wire size calculator (steel conduit, PF 0.85).
Wire Comparison Table
| Wire Size | Ampacity | V-Drop (V) | V-Drop (%) | V at Load | Status |
|---|---|---|---|---|---|
| 3 AWG | 85A | 8.769V | 3.65% | 231.23V | |
| 2 AWG | 95A | 7.201V | 3% | 232.8V | |
| 1 AWGREC | 110A | 5.977V | 2.49% | 234.02V | |
| 1/0 AWG | 125A | 4.715V | 1.96% | 235.28V | |
| 2/0 AWG | 145A | 4.084V | 1.7% | 235.92V |
Table shows nearby candidate sizes for 60A at 300 ft on 240V (copper). Green check = meets both ampacity and 3% voltage drop (Table 9, steel conduit, PF 0.85). REC = smallest size meeting these two model checks. See the full conductor tables for other sizes.
Route reduction versus conductor increase
Before committing to a large conductor for a remote outbuilding, compare feasible routing and panel-location options. Loss is proportional to electrical path length in this model, so eliminating an unnecessary detour can preserve voltage without changing material. Access, burial protection and disconnect requirements still constrain which routes are feasible.
Why this copper conductor?
1 AWG has a site ampacity of 110 A against a required 60 A. Table 9 lists R = 0.16 and XL = 0.057 Ω/kft (steel conduit), so at PF 0.85 its effective Z is 0.1660 Ω/kft. Substituting the actual load into 2 × 60 × 300 × 0.1660 / 1000 gives 5.977 V (2.49%).
The next smaller size, 2 AWG, has 95 A of site ampacity and 3.00% drop on this route. It fails the voltage-drop target.
3% route-length limit: 361.4 ft one way; remaining margin: 61.4 ft. This margin excludes upstream loss and does not authorize extra load.
Which assumption changes this selection?
copper: 60 A · 300 ft · 240 V. Alternatives are hypothetical; all results use the same Table 9 model (Table 9, steel conduit, PF 0.85).
| Assumption | Load / route / supply | Required ampacity | Minimum size | Drop / end voltage |
|---|---|---|---|---|
| Present route, 3% target | 60 A / 300 ft / 240 V | 60 A | 1 AWG | 5.977 V (2.49%) / 234.023 V |
| Reserve more voltage: 2% target | 60 A / 300 ft / 240 V | 60 A | 1/0 AWG | 4.715 V (1.96%) / 235.285 V |
| Sub-panel feeder: Feeder allocated 1% of supply voltage | 60 A / 300 ft / 240 V | 60 A | 300 kcmil | 2.344 V (0.98%) / 237.656 V |
The 1% allocation leaves 4 percentage points of a hypothetical 5% whole-path target for downstream wiring. The 2% allocation leaves 3 points, and 3% leaves 2. These are budgets referenced to the same supply voltage; add actual drops at the same load before comparing the final outlet voltage.
3% → 2% changes 1 AWG → 1/0 AWG. Load-voltage gain: 1.262 V. Original conductor’s 2% length limit: 240.9 ft one way.
Key Considerations
Use the calculated feeder demand, separating continuous and noncontinuous loads. The panel bus rating is a maximum equipment rating, not proof that the panel draws that current; no diversity or continuous-load factor is applied here.
A feeder drop uses part of the budget available at the final outlet. Add the downstream branch drop at the same operating condition rather than treating a feeder target and a branch target as independent full allowances.
For a typical downstream panel, keep the neutral isolated from the enclosure and equipment grounding bar. A detached structure also needs a grounding review; earth is not a substitute for the equipment grounding conductor.
This balanced line-to-line estimate does not size the neutral or predict unbalanced line-to-neutral voltage. List the actual loads on each leg and verify neutral current, protection and terminal ratings separately.
Reference: NFPA 70 (NEC), including Articles 215, 240, 310, 430, 440, 547, 625 and 680 as applicable. Verify the adopted edition and equipment instructions. These are calculated examples, not installation approvals.
Frequently Asked Questions
What size wire do I need for a 60 amp feeder at 300 feet?▾
Can I use aluminum wire for a 60 amp circuit?▾
What happens if the voltage drop exceeds 3%?▾
Related Wire Size Calculations
Need a Custom Calculation?
Different voltage, three-phase, or custom max drop percentage? Use our interactive calculator.
Wire Size Calculator