What Size Wire for 60 Amp 75 Feet Away
Table-based wire size estimate for 60 amps at 75 feet on a 240V single-phase circuit. Immediate answer below.
Updated November 12, 2026
Recommended Wire Size
Required ampacity: 60 A × 1 = 60 A. Drop uses 60 A. Ampacity: NEC Table 310.16, 60°C column (NEC 110.14(C) default for circuits of 100 A or less; equipment marked for 75°C terminals can allow the 75°C column), single-phase, 240V, 3% max voltage drop, one-way distance 75 ft.
Voltage drop uses AC resistance and reactance from NEC Chapter 9 Table 9 (NEC 2017 Table 9 values) for conductors in steel conduit at 0.85 lagging power factor, effective Z = R × PF + XL × sin(acos PF), single-phase, one set, VD = 2 × I × Z × L / 1000. Ampacity uses NEC 2023 Table 310.16 at 30°C ambient with no more than three current-carrying conductors. These are the same engine and defaults as the wire size calculator (steel conduit, PF 0.85).
Wire Comparison Table
| Wire Size | Ampacity | V-Drop (V) | V-Drop (%) | V at Load | Status |
|---|---|---|---|---|---|
| 8 AWG | 40A | 6.275V | 2.61% | 233.72V | |
| 6 AWG | 55A | 4.052V | 1.69% | 235.95V | |
| 4 AWGREC | 70A | 2.656V | 1.11% | 237.34V | |
| 3 AWG | 85A | 2.192V | 0.91% | 237.81V | |
| 2 AWG | 95A | 1.8V | 0.75% | 238.2V |
Table shows nearby candidate sizes for 60A at 75 ft on 240V (copper). Green check = meets both ampacity and 3% voltage drop (Table 9, steel conduit, PF 0.85). REC = smallest size meeting these two model checks. See the full conductor tables for other sizes.
Balanced model and neutral loading
This estimate assumes the stated load uses the line-to-line supply. A feeder serving many line-to-neutral circuits can have uneven leg currents and neutral loss that this model omits. Review the load allocation and neutral sizing separately, particularly where the feeder supports both heating equipment and general receptacles.
Operating boundaries: 60 A, 75 ft, 240 V, copper
Ampacity sets the minimum: 4 AWG supports 70 A (60°C column) against the 60.000 A requirement. At 60 A it can reach 203.316 ft before the 3% drop target takes over. Shortening this 75 ft route alone cannot reduce the ampacity floor. One set suffices in this model.
6 AWG cannot carry this assumed load: its current ceiling after the ×1 allowance is 55.000 A. At the present 75 ft, its drop ceiling is 106.616 A. Both checks first allow that smaller conductor at or below 55.000 A, a reduction of 5.000 A. Distance alone cannot fix its ampacity shortfall.
For the selected 4 AWG, increasing load beyond 70.000 A changes the choice: ampacity reaches its limit first. That leaves 10.000 A above the present load. With current fixed, route growth above 203.316 ft also requires reselection, a margin of 128.316 ft.
A 2% budget is 4.800 V instead of 7.200 V. At 60 A, the existing conductor’s length ceiling falls to 135.544 ft; at 75 ft, its combined current ceiling becomes 70.000 A. The unchanged inputs still select 4 AWG, giving 2.656 V (1.107%).
- Current −10%: 54.000 A / 75.000 ft → 6 AWG (1.519%).
- Current +10%: 66.000 A / 75.000 ft → 4 AWG (1.217%).
- Route −10%: 60.000 A / 67.500 ft → 4 AWG (0.996%).
- Route +10%: 60.000 A / 82.500 ft → 4 AWG (1.217%).
Basis: Z = 0.2951 Ω/kft (effective impedance, Table 9, steel conduit, PF 0.85; NEC 2017 Table 9 values); Imax = min(ampacity / 1, V × target × 1000 / (2 × L × Z)); Lmax = V × target × 1000 / (2 × I × Z). Boundaries are displayed to three decimals; selection uses unrounded values. These are load changes, not permission to change a breaker.
Which assumption changes this selection?
copper: 60 A · 75 ft · 240 V. Alternatives are hypothetical; all results use the same Table 9 model (Table 9, steel conduit, PF 0.85).
| Assumption | Load / route / supply | Required ampacity | Minimum size | Drop / end voltage |
|---|---|---|---|---|
| Present route, 3% target | 60 A / 75 ft / 240 V | 60 A | 4 AWG | 2.656 V (1.11%) / 237.344 V |
| Reserve more voltage: 2% target | 60 A / 75 ft / 240 V | 60 A | 4 AWG | 2.656 V (1.11%) / 237.344 V |
| Sub-panel feeder: Feeder allocated 1% of supply voltage | 60 A / 75 ft / 240 V | 60 A | 3 AWG | 2.192 V (0.91%) / 237.808 V |
Key Considerations
Calculate feeder demand, separating continuous loads; panel rating is not demand. Add downstream loss at the same operating condition. Review neutral isolation, equipment grounding and detached-building electrodes; this balanced model does not size an unbalanced neutral.
Reference: NFPA 70 (NEC), including Articles 215, 240, 310, 430, 440, 547, 625 and 680 as applicable. Verify the adopted edition and equipment instructions. These are calculated examples, not installation approvals.
Frequently Asked Questions
What size wire do I need for a 60 amp feeder at 75 feet?▾
Can I use aluminum wire for a 60 amp circuit?▾
What happens if the voltage drop exceeds 3%?▾