Wire Size for 60 Amp EV Charger 100 Feet
Table-based wire size estimate for 60 amps at 100 feet on a 240V single-phase circuit. Immediate answer below.
Updated November 12, 2026
Recommended Wire Size
Required ampacity: 60 A × 1.25 = 75 A. Drop uses 60 A. Ampacity: NEC Table 310.16, 60°C column (NEC 110.14(C) default for circuits of 100 A or less; equipment marked for 75°C terminals can allow the 75°C column), single-phase, 240V, 3% max voltage drop, one-way distance 100 ft.
Voltage drop uses AC resistance and reactance from NEC Chapter 9 Table 9 (NEC 2017 Table 9 values) for conductors in steel conduit at 0.85 lagging power factor, effective Z = R × PF + XL × sin(acos PF), single-phase, one set, VD = 2 × I × Z × L / 1000. Ampacity uses NEC 2023 Table 310.16 at 30°C ambient with no more than three current-carrying conductors. These are the same engine and defaults as the wire size calculator (steel conduit, PF 0.85).
Wire Comparison Table
| Wire Size | Ampacity | V-Drop (V) | V-Drop (%) | V at Load | Status |
|---|---|---|---|---|---|
| 6 AWG | 55A | 5.403V | 2.25% | 234.6V | |
| 4 AWG | 70A | 3.541V | 1.48% | 236.46V | |
| 3 AWGREC | 85A | 2.923V | 1.22% | 237.08V | |
| 2 AWG | 95A | 2.4V | 1% | 237.6V | |
| 1 AWG | 110A | 1.992V | 0.83% | 238.01V |
Table shows nearby candidate sizes for 60A at 100 ft on 240V (copper). Green check = meets both ampacity and 3% voltage drop (Table 9, steel conduit, PF 0.85). REC = smallest size meeting these two model checks. See the full conductor tables for other sizes.
EVSE terminal material compatibility
The aluminum recommendation describes a conductor-table result, not permission to terminate aluminum inside a charger. Read the EVSE terminal listing and conductor range. If the equipment accepts copper only, a suitable listed transition may be needed upstream, with its own enclosure and connection requirements; the transition must not become an unexamined weak point.
Why this copper conductor?
3 AWG has a site ampacity of 85 A against a required 75 A. Table 9 lists R = 0.25 and XL = 0.059 Ω/kft (steel conduit), so at PF 0.85 its effective Z is 0.2436 Ω/kft. Substituting the actual load into 2 × 60 × 100 × 0.2436 / 1000 gives 2.923 V (1.22%).
The next smaller size, 4 AWG, has 70 A of site ampacity and 1.48% drop on this route. It fails the ampacity requirement.
3% route-length limit: 246.3 ft one way; remaining margin: 146.3 ft. This margin excludes upstream loss and does not authorize extra load.
Which assumption changes this selection?
copper: 60 A · 100 ft · 240 V. Alternatives are hypothetical; all results use the same Table 9 model (Table 9, steel conduit, PF 0.85).
| Assumption | Load / route / supply | Required ampacity | Minimum size | Drop / end voltage |
|---|---|---|---|---|
| Present route, 3% target | 60 A / 100 ft / 240 V | 75 A | 3 AWG | 2.923 V (1.22%) / 237.077 V |
| Reserve more voltage: 2% target | 60 A / 100 ft / 240 V | 75 A | 3 AWG | 2.923 V (1.22%) / 237.077 V |
| EV charging: Hypothetical commissioned current at 80% | 48 A / 100 ft / 240 V | 60 A | 4 AWG | 2.833 V (1.18%) / 237.167 V |
The reduced-current row is an explicit alternative EVSE setting, not a claim about your charger. Its ampacity allowance stays at 125%; the voltage-drop current falls with the setting. Confirm that the equipment permits and retains that setting.
3% → 2% retains 3 AWG → 3 AWG. Load-voltage gain: 0.000 V. Original conductor’s 2% length limit: 164.2 ft one way.
Key Considerations
Charging is treated as a continuous load here: conductor ampacity is checked at 125% of the charging current, while voltage loss is calculated at the actual charging current. This is not the charger breaker rating.
Verify the EVSE installation instructions and its commissioned current setting. A software setting is not automatically an approved method of limiting the circuit load; adjustable equipment must meet the applicable listing and code conditions.
Check whether the EVSE terminals accept the selected conductor material and gauge. A conductor that passes the table may still require a listed transition or a different conductor because it will not fit the equipment terminals.
Hardwired and receptacle-connected charging have different connection and protection details. Confirm required ground-fault protection, disconnect provisions and terminal torque; the voltage-drop result does not check those features.
Reference: NFPA 70 (NEC), including Articles 215, 240, 310, 430, 440, 547, 625 and 680 as applicable. Verify the adopted edition and equipment instructions. These are calculated examples, not installation approvals.
Frequently Asked Questions
What size wire do I need for a EV charger at 100 feet?▾
Can I use aluminum wire for a 60 amp circuit?▾
What happens if the voltage drop exceeds 3%?▾
Related Wire Size Calculations
Need a Custom Calculation?
Different voltage, three-phase, or custom max drop percentage? Use our interactive calculator.
The general tool sizes for actual current unless its continuous-load option is selected. For EV charging, check conductor ampacity at 1.25 × 60 A = 75 A separately; calculate voltage drop at the actual 60 A charging current.
Wire Size Calculator