Wire Sizing

Wire Size for 60 Amp Sub-Panel 100 Feet

Table-based wire size estimate for 60 amps at 100 feet on a 240V single-phase circuit. Immediate answer below.

Updated November 12, 2026

Recommended Wire Size

Copper
4 AWG
Voltage drop: 1.48% (3.541V)
Voltage at load: 236.46V
Ampacity used: 70 A (60°C column). Controlling factor: Ampacity (NEC 310.16)
Aluminum
3 AWG
Voltage drop: 1.86% (4.453V)
Voltage at load: 235.55V
Ampacity used: 65 A (60°C column). Controlling factor: Ampacity (NEC 310.16)

Required ampacity: 60 A × 1 = 60 A. Drop uses 60 A. Ampacity: NEC Table 310.16, 60°C column (NEC 110.14(C) default for circuits of 100 A or less; equipment marked for 75°C terminals can allow the 75°C column), single-phase, 240V, 3% max voltage drop, one-way distance 100 ft.

Voltage drop uses AC resistance and reactance from NEC Chapter 9 Table 9 (NEC 2017 Table 9 values) for conductors in steel conduit at 0.85 lagging power factor, effective Z = R × PF + XL × sin(acos PF), single-phase, one set, VD = 2 × I × Z × L / 1000. Ampacity uses NEC 2023 Table 310.16 at 30°C ambient with no more than three current-carrying conductors. These are the same engine and defaults as the wire size calculator (steel conduit, PF 0.85).

Wire Comparison Table

Wire SizeAmpacityV-Drop (V)V-Drop (%)V at LoadStatus
8 AWG40A8.367V3.49%231.63V
6 AWG55A5.403V2.25%234.6V
4 AWGREC70A3.541V1.48%236.46V
3 AWG85A2.923V1.22%237.08V
2 AWG95A2.4V1%237.6V

Table shows nearby candidate sizes for 60A at 100 ft on 240V (copper). Green check = meets both ampacity and 3% voltage drop (Table 9, steel conduit, PF 0.85). REC = smallest size meeting these two model checks. See the full conductor tables for other sizes.

Workshop load schedule

List the tools and appliances likely to operate together, including dust collection or ventilation that runs whenever a machine is used. Keep motor starting separate from the steady feeder demand. The panel label alone does not describe this combination, and a conductor that passes this balanced load estimate does not validate the longest outgoing workshop branch.

Operating boundaries: 60 A, 100 ft, 240 V, copper

Ampacity sets the minimum: 4 AWG supports 70 A (60°C column) against the 60.000 A requirement. At 60 A it can reach 203.316 ft before the 3% drop target takes over. Shortening this 100 ft route alone cannot reduce the ampacity floor. One set suffices in this model.

6 AWG cannot carry this assumed load: its current ceiling after the ×1 allowance is 55.000 A. At the present 100 ft, its drop ceiling is 79.962 A. Both checks first allow that smaller conductor at or below 55.000 A, a reduction of 5.000 A. Distance alone cannot fix its ampacity shortfall.

For the selected 4 AWG, increasing load beyond 70.000 A changes the choice: ampacity reaches its limit first. That leaves 10.000 A above the present load. With current fixed, route growth above 203.316 ft also requires reselection, a margin of 103.316 ft.

A 2% budget is 4.800 V instead of 7.200 V. At 60 A, the existing conductor’s length ceiling falls to 135.544 ft; at 100 ft, its combined current ceiling becomes 70.000 A. The unchanged inputs still select 4 AWG, giving 3.541 V (1.476%).

  • Current −10%: 54.000 A / 100.000 ft → 6 AWG (2.026%).
  • Current +10%: 66.000 A / 100.000 ft → 4 AWG (1.623%).
  • Route −10%: 60.000 A / 90.000 ft → 4 AWG (1.328%).
  • Route +10%: 60.000 A / 110.000 ft → 4 AWG (1.623%).

Basis: Z = 0.2951 Ω/kft (effective impedance, Table 9, steel conduit, PF 0.85; NEC 2017 Table 9 values); Imax = min(ampacity / 1, V × target × 1000 / (2 × L × Z)); Lmax = V × target × 1000 / (2 × I × Z). Boundaries are displayed to three decimals; selection uses unrounded values. These are load changes, not permission to change a breaker.

Which assumption changes this selection?

copper: 60 A · 100 ft · 240 V. Alternatives are hypothetical; all results use the same Table 9 model (Table 9, steel conduit, PF 0.85).

AssumptionLoad / route / supplyRequired ampacityMinimum sizeDrop / end voltage
Present route, 3% target60 A / 100 ft / 240 V60 A4 AWG3.541 V (1.48%) / 236.459 V
Reserve more voltage: 2% target60 A / 100 ft / 240 V60 A4 AWG3.541 V (1.48%) / 236.459 V
Sub-panel feeder: Feeder allocated 1% of supply voltage60 A / 100 ft / 240 V60 A1 AWG1.992 V (0.83%) / 238.008 V

Also covers: 60 amp 100 feet

The same amps, distance and voltage above also describe this equipment, so the result applies to it too. Apply the Key Considerations below; extra equipment conditions are listed here.

  • Use actual load current; check continuous duty separately. The site retains small-conductor protection limits. Verify cable and terminal temperature, equipment voltage range, upstream loss and connections.

Key Considerations

Calculate feeder demand, separating continuous loads; panel rating is not demand. Add downstream loss at the same operating condition. Review neutral isolation, equipment grounding and detached-building electrodes; this balanced model does not size an unbalanced neutral.

Reference: NFPA 70 (NEC), including Articles 215, 240, 310, 430, 440, 547, 625 and 680 as applicable. Verify the adopted edition and equipment instructions. These are calculated examples, not installation approvals.

Frequently Asked Questions

What size wire do I need for a sub-panel feeder at 100 feet?▾
For a 60A/240V circuit at 100 feet, use 4 AWG copper (1.48% drop) or 3 AWG aluminum. The ampacity check uses 60A; voltage drop uses the actual 60A (NEC Chapter 9 Table 9 impedance, Table 9, steel conduit, PF 0.85). Installation adjustments and equipment ratings must be checked separately.
Can I use aluminum wire for a 60 amp circuit?▾
At 60A over 100 ft, use 3 AWG aluminum (1.86% voltage drop). Use only equipment and connectors listed for this aluminum gauge; follow their preparation instructions.
What happens if the voltage drop exceeds 3%?▾
3% is a planning target, not installation approval. Here it means 232.8V at the load before upstream loss. Compare the combined path with the equipment’s operating range.

Need a Custom Calculation?

Different voltage, three-phase, or custom max drop percentage? Use our interactive calculator.

Wire Size Calculator