What Size Wire for 60 Amp 150 Feet Away
Table-based wire size estimate for 60 amps at 150 feet on a 240V single-phase circuit. Immediate answer below.
Updated November 12, 2026
Recommended Wire Size
Required ampacity: 60 A × 1 = 60 A. Drop uses 60 A. Ampacity: NEC Table 310.16, 60°C column (NEC 110.14(C) default for circuits of 100 A or less; equipment marked for 75°C terminals can allow the 75°C column), single-phase, 240V, 3% max voltage drop, one-way distance 150 ft.
Voltage drop uses AC resistance and reactance from NEC Chapter 9 Table 9 (NEC 2017 Table 9 values) for conductors in steel conduit at 0.85 lagging power factor, effective Z = R × PF + XL × sin(acos PF), single-phase, one set, VD = 2 × I × Z × L / 1000. Ampacity uses NEC 2023 Table 310.16 at 30°C ambient with no more than three current-carrying conductors. These are the same engine and defaults as the wire size calculator (steel conduit, PF 0.85).
Wire Comparison Table
| Wire Size | Ampacity | V-Drop (V) | V-Drop (%) | V at Load | Status |
|---|---|---|---|---|---|
| 8 AWG | 40A | 12.55V | 5.23% | 227.45V | |
| 6 AWG | 55A | 8.104V | 3.38% | 231.9V | |
| 4 AWGREC | 70A | 5.312V | 2.21% | 234.69V | |
| 3 AWG | 85A | 4.384V | 1.83% | 235.62V | |
| 2 AWG | 95A | 3.6V | 1.5% | 236.4V |
Table shows nearby candidate sizes for 60A at 150 ft on 240V (copper). Green check = meets both ampacity and 3% voltage drop (Table 9, steel conduit, PF 0.85). REC = smallest size meeting these two model checks. See the full conductor tables for other sizes.
A barn feeder with mixed uses
This estimate also applies to a barn on the same run. Distinguish general storage from livestock housing, wet processing areas or dusty workspaces before specifying the wiring method. The same electrical current and distance can require different physical protection and bonding provisions depending on how the building is used.
Why this copper conductor?
4 AWG has a site ampacity of 70 A against a required 60 A. Table 9 lists R = 0.31 and XL = 0.06 Ω/kft (steel conduit), so at PF 0.85 its effective Z is 0.2951 Ω/kft. Substituting the actual load into 2 × 60 × 150 × 0.2951 / 1000 gives 5.312 V (2.21%).
The next smaller size, 6 AWG, has 55 A of site ampacity and 3.38% drop on this route. It fails both checks.
3% route-length limit: 203.3 ft one way; remaining margin: 53.3 ft. This margin excludes upstream loss and does not authorize extra load.
Which assumption changes this selection?
copper: 60 A · 150 ft · 240 V. Alternatives are hypothetical; all results use the same Table 9 model (Table 9, steel conduit, PF 0.85).
| Assumption | Load / route / supply | Required ampacity | Minimum size | Drop / end voltage |
|---|---|---|---|---|
| Present route, 3% target | 60 A / 150 ft / 240 V | 60 A | 4 AWG | 5.312 V (2.21%) / 234.688 V |
| Reserve more voltage: 2% target | 60 A / 150 ft / 240 V | 60 A | 3 AWG | 4.384 V (1.83%) / 235.616 V |
| Barn or detached agricultural building: Hypothetical trench detour adds 50% to route | 60 A / 225 ft / 240 V | 60 A | 3 AWG | 6.577 V (2.74%) / 233.423 V |
The detour represents a longer trench around an obstacle, not a measured property of this site. Recalculate using the surveyed electrical path; a straight-line building separation can miss the threshold at which another conductor size is needed.
3% → 2% changes 4 AWG → 3 AWG. Load-voltage gain: 0.927 V. Original conductor’s 2% length limit: 135.5 ft one way.
Also covers: barn 60 amp 150 feet
The same amps, distance and voltage above also describe this equipment, so the result applies to it too. Apply the Key Considerations below; extra equipment conditions are listed here.
- List ventilation, water pumping, lighting and receptacle loads by duty and starting behavior before treating the service or panel rating as demand. Seasonal equipment can change the combination of loads operating together.
- A detached building needs review of its disconnect, equipment grounding path and grounding electrodes. A long trench does not remove those requirements, and grounding electrodes do not replace the feeder grounding conductor.
- Agricultural locations may expose wiring to moisture, dust, corrosion or livestock contact. Determine whether Article 547 and equipotential-plane provisions apply to the actual use of the building.
- Check burial method, wet-location conductor rating, physical protection and accessible terminations. Aluminum can be considered only with compatible listed connections and the manufacturer’s preparation instructions.
Key Considerations
Use the calculated feeder demand, separating continuous and noncontinuous loads. The panel bus rating is a maximum equipment rating, not proof that the panel draws that current; no diversity or continuous-load factor is applied here.
A feeder drop uses part of the budget available at the final outlet. Add the downstream branch drop at the same operating condition rather than treating a feeder target and a branch target as independent full allowances.
For a typical downstream panel, keep the neutral isolated from the enclosure and equipment grounding bar. A detached structure also needs a grounding review; earth is not a substitute for the equipment grounding conductor.
This balanced line-to-line estimate does not size the neutral or predict unbalanced line-to-neutral voltage. List the actual loads on each leg and verify neutral current, protection and terminal ratings separately.
Reference: NFPA 70 (NEC), including Articles 215, 240, 310, 430, 440, 547, 625 and 680 as applicable. Verify the adopted edition and equipment instructions. These are calculated examples, not installation approvals.
Frequently Asked Questions
What size wire do I need for a 60 amp feeder at 150 feet?▾
Can I use aluminum wire for a 60 amp circuit?▾
What happens if the voltage drop exceeds 3%?▾