Wire Sizing

What Size Wire for 60 Amp 150 Feet Away

Table-based wire size estimate for 60 amps at 150 feet on a 240V single-phase circuit. Immediate answer below.

Updated October 23, 2026

Recommended Wire Size

Copper
4 AWG
Voltage drop: 2.31% (5.544V)
Voltage at load: 234.46V
Controlling factor: Voltage Drop (3% limit)
Aluminum
2 AWG
Voltage drop: 2.39% (5.742V)
Voltage at load: 234.26V
Controlling factor: Voltage Drop (3% limit)

Required ampacity: 60 A × 1 = 60 A. Drop uses 60 A. Based on NEC Table 310.16 (75°C column), single-phase, 240V, 3% max voltage drop, one-way distance 150 ft.

Wire Comparison Table

Wire SizeAmpacityV-Drop (V)V-Drop (%)V at LoadStatus
8 AWG50A14V5.84%226V
6 AWG65A8.84V3.68%231.2V
4 AWGREC85A5.54V2.31%234.5V
3 AWG100A4.41V1.84%235.6V
2 AWG115A3.49V1.46%236.5V

Table shows nearby candidate sizes for 60A at 150 ft on 240V (copper). Green check = meets both ampacity and 3% voltage drop. REC = smallest size meeting these two model checks. See the full conductor tables for other sizes.

A barn feeder with mixed uses

This route includes the retired barn scenario. Distinguish general storage from livestock housing, wet processing areas or dusty workspaces before specifying the wiring method. The same electrical current and distance can require different physical protection and bonding provisions depending on how the building is used.

Why this copper conductor?

4 AWG has a site ampacity of 85 A against a required 60 A. Its resistance is 0.308 Ω/kft. Substituting the actual load into 2 × 60 × 150 × 0.308 / 1000 gives 5.544 V (2.31%).

The next smaller size, 6 AWG, has 65 A of site ampacity and 3.68% drop on this route. It fails the voltage-drop target.

3% route-length limit: 194.8 ft one way; remaining margin: 44.8 ft. This margin excludes upstream loss and does not authorize extra load.

Which assumption changes this selection?

copper: 60 A · 150 ft · 240 V. Alternatives are hypothetical; all results use the site resistance table.

AssumptionLoad / route / supplyRequired ampacityMinimum sizeDrop / end voltage
Present route, 3% target60 A / 150 ft / 240 V60 A4 AWG5.544 V (2.31%) / 234.456 V
Reserve more voltage: 2% target60 A / 150 ft / 240 V60 A3 AWG4.410 V (1.84%) / 235.590 V
Barn or detached agricultural building: Hypothetical trench detour adds 50% to route60 A / 225 ft / 240 V60 A3 AWG6.615 V (2.76%) / 233.385 V

The detour represents a longer trench around an obstacle, not a measured property of this site. Recalculate using the surveyed electrical path; a straight-line building separation can miss the threshold at which another conductor size is needed.

3% → 2% changes 4 AWG → 3 AWG. Load-voltage gain: 1.134 V. Original conductor’s 2% length limit: 129.9 ft one way.

Also covers: barn 60 amp 150 feet

This merged scenario shares the route inputs above. Apply the Key Considerations below; any additional equipment conditions are listed here.

  • List ventilation, water pumping, lighting and receptacle loads by duty and starting behavior before treating the service or panel rating as demand. Seasonal equipment can change the combination of loads operating together.
  • A detached building needs review of its disconnect, equipment grounding path and grounding electrodes. A long trench does not remove those requirements, and grounding electrodes do not replace the feeder grounding conductor.
  • Agricultural locations may expose wiring to moisture, dust, corrosion or livestock contact. Determine whether Article 547 and equipotential-plane provisions apply to the actual use of the building.
  • Check burial method, wet-location conductor rating, physical protection and accessible terminations. Aluminum can be considered only with compatible listed connections and the manufacturer’s preparation instructions.

Key Considerations

Use the calculated feeder demand, separating continuous and noncontinuous loads. The panel bus rating is a maximum equipment rating, not proof that the panel draws that current; no diversity or continuous-load factor is applied here.

A feeder drop uses part of the budget available at the final outlet. Add the downstream branch drop at the same operating condition rather than treating a feeder target and a branch target as independent full allowances.

For a typical downstream panel, keep the neutral isolated from the enclosure and equipment grounding bar. A detached structure also needs a grounding review; earth is not a substitute for the equipment grounding conductor.

This balanced line-to-line estimate does not size the neutral or predict unbalanced line-to-neutral voltage. List the actual loads on each leg and verify neutral current, protection and terminal ratings separately.

Reference: NFPA 70 (NEC), including Articles 215, 240, 310, 430, 440, 547, 625 and 680 as applicable. Verify the adopted edition and equipment instructions. These are calculated examples, not installation approvals.

Frequently Asked Questions

What size wire do I need for a 60 amp feeder at 150 feet?▾
For a 60A/240V circuit at 150 feet, use 4 AWG copper (2.31% drop) or 2 AWG aluminum. The ampacity check uses 60A; voltage drop uses the actual 60A. Installation adjustments and equipment ratings must be checked separately.
Can I use aluminum wire for a 60 amp circuit?▾
At 60A over 150 ft, use 2 AWG aluminum (2.39% voltage drop). Use only equipment and connectors listed for this aluminum gauge; follow their preparation instructions.
What happens if the voltage drop exceeds 3%?▾
3% is a planning target, not installation approval. Here it means 232.8V at the load before upstream loss. Compare the combined path with the equipment’s operating range.

Need a Custom Calculation?

Different voltage, three-phase, or custom max drop percentage? Use our interactive calculator.

Wire Size Calculator