Wire Size for Barn — 60 Amp 200 Feet
Table-based wire size estimate for 60 amps at 200 feet on a 240V single-phase circuit. Immediate answer below.
Updated November 12, 2026
Recommended Wire Size
Required ampacity: 60 A × 1 = 60 A. Drop uses 60 A. Ampacity: NEC Table 310.16, 60°C column (NEC 110.14(C) default for circuits of 100 A or less; equipment marked for 75°C terminals can allow the 75°C column), single-phase, 240V, 3% max voltage drop, one-way distance 200 ft.
Voltage drop uses AC resistance and reactance from NEC Chapter 9 Table 9 (NEC 2017 Table 9 values) for conductors in steel conduit at 0.85 lagging power factor, effective Z = R × PF + XL × sin(acos PF), single-phase, one set, VD = 2 × I × Z × L / 1000. Ampacity uses NEC 2023 Table 310.16 at 30°C ambient with no more than three current-carrying conductors. These are the same engine and defaults as the wire size calculator (steel conduit, PF 0.85).
Wire Comparison Table
| Wire Size | Ampacity | V-Drop (V) | V-Drop (%) | V at Load | Status |
|---|---|---|---|---|---|
| 8 AWG | 40A | 16.734V | 6.97% | 223.27V | |
| 6 AWG | 55A | 10.805V | 4.5% | 229.19V | |
| 4 AWGREC | 70A | 7.083V | 2.95% | 232.92V | |
| 3 AWG | 85A | 5.846V | 2.44% | 234.15V | |
| 2 AWG | 95A | 4.801V | 2% | 235.2V |
Table shows nearby candidate sizes for 60A at 200 ft on 240V (copper). Green check = meets both ampacity and 3% voltage drop (Table 9, steel conduit, PF 0.85). REC = smallest size meeting these two model checks. See the full conductor tables for other sizes.
Moisture and livestock exposure
A remote barn supply needs more than a trench-length calculation. Establish which areas are wet, corrosive or accessible to livestock and whether an equipotential plane is required. Electrical resistance depends on the conductor route, but the installation method and bonding design depend on the actual agricultural activity.
Why this copper conductor?
4 AWG has a site ampacity of 70 A against a required 60 A. Table 9 lists R = 0.31 and XL = 0.06 Ω/kft (steel conduit), so at PF 0.85 its effective Z is 0.2951 Ω/kft. Substituting the actual load into 2 × 60 × 200 × 0.2951 / 1000 gives 7.083 V (2.95%).
The next smaller size, 6 AWG, has 55 A of site ampacity and 4.50% drop on this route. It fails both checks.
3% route-length limit: 203.3 ft one way; remaining margin: 3.3 ft. This margin excludes upstream loss and does not authorize extra load.
Which assumption changes this selection?
copper: 60 A · 200 ft · 240 V. Alternatives are hypothetical; all results use the same Table 9 model (Table 9, steel conduit, PF 0.85).
| Assumption | Load / route / supply | Required ampacity | Minimum size | Drop / end voltage |
|---|---|---|---|---|
| Present route, 3% target | 60 A / 200 ft / 240 V | 60 A | 4 AWG | 7.083 V (2.95%) / 232.917 V |
| Reserve more voltage: 2% target | 60 A / 200 ft / 240 V | 60 A | 1 AWG | 3.985 V (1.66%) / 236.015 V |
| Barn or detached agricultural building: Hypothetical trench detour adds 50% to route | 60 A / 300 ft / 240 V | 60 A | 1 AWG | 5.977 V (2.49%) / 234.023 V |
The detour represents a longer trench around an obstacle, not a measured property of this site. Recalculate using the surveyed electrical path; a straight-line building separation can miss the threshold at which another conductor size is needed.
3% → 2% changes 4 AWG → 1 AWG. Load-voltage gain: 3.098 V. Original conductor’s 2% length limit: 135.5 ft one way.
Also covers: 60 amp 200 feet
The same amps, distance and voltage above also describe this equipment, so the result applies to it too. Apply the Key Considerations below; extra equipment conditions are listed here.
- The entered current is a load assumption, not a breaker selection. If the load is continuous, determine its required ampacity separately; the generic calculation uses a factor of 1.
- For small copper and aluminum conductors, the recommendation retains the site’s NEC 240.4(D) overcurrent limits. A higher insulation temperature rating does not by itself allow a larger breaker.
- Verify cable type and terminal temperature before using the 75°C column. For example, a cable or termination limited to 60°C can require a different conductor even when the voltage-drop calculation passes.
- Check the appliance’s supply range and any upstream loss. The calculation assumes the stated voltage at the beginning of this run and does not model receptacle contacts or loose connections.
Key Considerations
List ventilation, water pumping, lighting and receptacle loads by duty and starting behavior before treating the service or panel rating as demand. Seasonal equipment can change the combination of loads operating together.
A detached building needs review of its disconnect, equipment grounding path and grounding electrodes. A long trench does not remove those requirements, and grounding electrodes do not replace the feeder grounding conductor.
Agricultural locations may expose wiring to moisture, dust, corrosion or livestock contact. Determine whether Article 547 and equipotential-plane provisions apply to the actual use of the building.
Check burial method, wet-location conductor rating, physical protection and accessible terminations. Aluminum can be considered only with compatible listed connections and the manufacturer’s preparation instructions.
Reference: NFPA 70 (NEC), including Articles 215, 240, 310, 430, 440, 547, 625 and 680 as applicable. Verify the adopted edition and equipment instructions. These are calculated examples, not installation approvals.
Frequently Asked Questions
What size wire do I need for a barn feeder at 200 feet?▾
Can I use aluminum wire for a 60 amp circuit?▾
What happens if the voltage drop exceeds 3%?▾