Illustrative example · Residential

This is an illustrative engineering example built from stated assumptions, not a record of a specific installed project.

Residential EV Charger Installation: 200ft Garage Run

Hypothetical setting: San Diego, CA

Assume a detached garage supplied by a 240V single-phase circuit, with a 48A EV charging load and a 200ft one-way cable route. San Diego is an illustrative setting only.

Initial conductor

9.43 V · 3.93%

Larger conductor

5.91 V · 2.46%

Conditions: 48A continuous load sized at 125%; resistive drop only. Termination temperature rating, wiring method and installation corrections are checked separately, so a lower drop is not an installation approval.

Challenge

Compare conductor sizes for a long, continuous charging load.

Comparison approach

Compare 6 AWG and 4 AWG copper at the same current and distance; verify ampacity separately.

Stated inputs and calculation method

All lengths below are one-way feet. Resistance R is in Ω per 1000ft from the site’s 75°C resistance table. N is the number of identical parallel sets. The AC examples use a resistive estimate at unity power factor, without reactance or source impedance.

DC / single-phase: Vd = 2 × I × L × R / (1000 × N). Three-phase: Vd = √3 × I × L × R / (1000 × N).

Vd% = Vd / V × 100; load voltage = V − Vd.

Results are calculated before rounding; displayed voltages and percentages use two decimal places. These are conductor-drop estimates, not field measurements or full installation approvals.

Site wire tables

Worked voltage-drop comparisons

Initial conductor

240 V · I = 48 A · L = 200 ft · 6 AWG · copper · N = 1

Table resistance: R = 0.491 Ω/1000ft; R/N = 0.491 Ω/1000ft.

Vd = 2 × 48 × 200 × 0.491 / (1000 × 1) = 9.43 V

Vd% = 9.43 / 240 × 100 ≈ 3.93%

Calculated load voltage: 240 − 9.43 = 230.57 V

Larger conductor

240 V · I = 48 A · L = 200 ft · 4 AWG · copper · N = 1

Table resistance: R = 0.308 Ω/1000ft; R/N = 0.308 Ω/1000ft.

Vd = 2 × 48 × 200 × 0.308 / (1000 × 1) = 5.91 V

Vd% = 5.91 / 240 × 100 ≈ 2.46%

Calculated load voltage: 240 − 5.91 = 234.09 V

Engineering interpretation and limits

The continuous-load sizing assumption is 48A × 1.25 = 60A. The site table lists 65A for 6 AWG copper and 85A for 4 AWG copper in the 75°C column; termination ratings and installation corrections still apply.

Upsizing reduces the calculated drop, but this does not establish a charging speed, vehicle range, customer satisfaction score, or a completed code-compliant installation.

Economic evaluation requires real inputs

Any savings estimate needs actual electricity prices, operating hours and the load profile. Installed cost, maintenance and equipment life need project evidence. No savings amount, payback period or customer outcome is claimed for this example.

Apply the method to your inputs

Enter the actual voltage, current, one-way distance, conductor and parallel sets. Check voltage drop together with ampacity, correction factors, protection and equipment requirements.

Open Calculator

Related illustrative examples