Wire Sizing

What Size Wire for 150 Amp 150 Feet Away

Pre-calculated NEC-compliant wire size for 150 amps at 150 feet on a 240V single-phase circuit. Immediate answer below.

Recommended Wire Size

Copper
1/0 AWG
Voltage drop: 2.29% (5.49V)
Voltage at load: 234.5V
Controlling factor: Ampacity (NEC 310.16)
Aluminum
3/0 AWG
Voltage drop: 2.36% (5.67V)
Voltage at load: 234.3V
Controlling factor: Ampacity (NEC 310.16)

Based on NEC Table 310.16 (75°C column), single-phase, 240V, 3% max voltage drop, one-way distance 150 ft.

Wire Comparison Table

Wire SizeAmpacityV-Drop (V)V-Drop (%)V at LoadStatus
14 AWG15A141.3V58.88%98.7V
12 AWG20A89.1V37.12%150.9V
10 AWG30A55.8V23.25%184.2V
8 AWG50A35.01V14.59%205V
6 AWG65A22.1V9.21%217.9V
4 AWG85A13.86V5.78%226.1V
3 AWG100A11.03V4.59%229V
2 AWG115A8.73V3.64%231.3V
1 AWG130A6.93V2.89%233.1V
1/0 AWGREC150A5.49V2.29%234.5V
2/0 AWG175A4.35V1.81%235.6V
3/0 AWG200A3.45V1.44%236.6V
4/0 AWG230A2.74V1.14%237.3V
250 kcmil255A2.32V0.97%237.7V
300 kcmil285A1.93V0.8%238.1V
350 kcmil310A1.65V0.69%238.3V
400 kcmil335A1.44V0.6%238.6V
500 kcmil380A1.16V0.48%238.8V

Table shows all standard AWG/kcmil sizes for 150A at 150 ft on 240V (copper). Green check = meets both ampacity and 3% voltage drop. REC = smallest compliant size.

Key Considerations

For a 150A circuit at 150 feet on 240V, both ampacity and voltage drop must be satisfied. NEC recommends keeping the total voltage drop (feeder + branch) under 5%, with no more than 3% on either segment alone.

Copper conductors at 75°C column (THHN/THWN-2) are assumed. If using 60°C terminations, derate the ampacity to the 60°C column values. Verify the temperature rating of your terminals.

Frequently Asked Questions

What size wire do I need for a 150 amp service at 150 feet?
For a 150A/240V circuit at 150 feet, use 1/0 AWG copper (2.29% drop) or 3/0 AWG aluminum. This keeps voltage drop within the NEC-recommended 3% limit.
Can I use aluminum wire for a 150 amp circuit?
Yes. Aluminum wire is a cost-effective alternative for larger circuits. For 150A at 150 feet, use 3/0 AWG aluminum (2.36% voltage drop). Aluminum requires AL-rated connectors and anti-oxidant compound at all terminations.
What happens if the voltage drop exceeds 3%?
Voltage drop above 3% reduces equipment efficiency, can cause motors to overheat, and may violate NEC 210.19(A) Informational Note No. 4. For a 150A circuit at 150 feet on 240V, exceeding 3% means the load receives less than 232.8V, which can damage sensitive electronics and shorten appliance lifespan.

Need a Custom Calculation?

Different voltage, three-phase, or custom max drop percentage? Use our interactive calculator.

Wire Size Calculator