Wire Sizing

What Size Wire for 150 Amp 100 Feet Away

Table-based wire size estimate for 150 amps at 100 feet on a 240V single-phase circuit. Immediate answer below.

Updated November 12, 2026

Recommended Wire Size

Copper
1/0 AWG
Voltage drop: 1.64% (3.929V)
Voltage at load: 236.07V
Ampacity used: 150 A (75°C column). Controlling factor: Ampacity (NEC 310.16)
Aluminum
3/0 AWG
Voltage drop: 1.72% (4.137V)
Voltage at load: 235.86V
Ampacity used: 155 A (75°C column). Controlling factor: Ampacity (NEC 310.16)

Required ampacity: 150 A × 1 = 150 A. Drop uses 150 A. Ampacity: NEC Table 310.16, 75°C column (NEC 110.14(C) for circuits above 100 A), single-phase, 240V, 3% max voltage drop, one-way distance 100 ft.

Voltage drop uses AC resistance and reactance from NEC Chapter 9 Table 9 (NEC 2017 Table 9 values) for conductors in steel conduit at 0.85 lagging power factor, effective Z = R × PF + XL × sin(acos PF), single-phase, one set, VD = 2 × I × Z × L / 1000. Ampacity uses NEC 2023 Table 310.16 at 30°C ambient with no more than three current-carrying conductors. These are the same engine and defaults as the wire size calculator (steel conduit, PF 0.85).

Wire Comparison Table

Wire SizeAmpacityV-Drop (V)V-Drop (%)V at LoadStatus
2 AWG115A6.001V2.5%234V
1 AWG130A4.981V2.08%235.02V
1/0 AWGREC150A3.929V1.64%236.07V
2/0 AWG175A3.403V1.42%236.6V
3/0 AWG200A2.836V1.18%237.16V

Table shows nearby candidate sizes for 150A at 100 ft on 240V (copper). Green check = meets both ampacity and 3% voltage drop (Table 9, steel conduit, PF 0.85). REC = smallest size meeting these two model checks. See the full conductor tables for other sizes.

Panel rating and future equipment

Separate the rating of the installed panel from the load expected when future equipment is commissioned. This page evaluates the full stated operating current and does not apply demand diversity. Document the load schedule used for conductor selection; an empty breaker space does not demonstrate spare feeder capacity.

Why this copper conductor?

1/0 AWG has a site ampacity of 150 A against a required 150 A. Table 9 lists R = 0.12 and XL = 0.055 Ω/kft (steel conduit), so at PF 0.85 its effective Z is 0.1310 Ω/kft. Substituting the actual load into 2 × 150 × 100 × 0.1310 / 1000 gives 3.929 V (1.64%).

The next smaller size, 1 AWG, has 130 A of site ampacity and 2.08% drop on this route. It fails the ampacity requirement.

3% route-length limit: 183.2 ft one way; remaining margin: 83.2 ft. This margin excludes upstream loss and does not authorize extra load.

Which assumption changes this selection?

copper: 150 A · 100 ft · 240 V. Alternatives are hypothetical; all results use the same Table 9 model (Table 9, steel conduit, PF 0.85).

AssumptionLoad / route / supplyRequired ampacityMinimum sizeDrop / end voltage
Present route, 3% target150 A / 100 ft / 240 V150 A1/0 AWG3.929 V (1.64%) / 236.071 V
Reserve more voltage: 2% target150 A / 100 ft / 240 V150 A1/0 AWG3.929 V (1.64%) / 236.071 V
Sub-panel feeder: Feeder allocated 1% of supply voltage150 A / 100 ft / 240 V150 A250 kcmil2.199 V (0.92%) / 237.801 V

The 1% allocation leaves 4 percentage points of a hypothetical 5% whole-path target for downstream wiring. The 2% allocation leaves 3 points, and 3% leaves 2. These are budgets referenced to the same supply voltage; add actual drops at the same load before comparing the final outlet voltage.

3% → 2% retains 1/0 AWG → 1/0 AWG. Load-voltage gain: 0.000 V. Original conductor’s 2% length limit: 122.2 ft one way.

Key Considerations

Use the calculated feeder demand, separating continuous and noncontinuous loads. The panel bus rating is a maximum equipment rating, not proof that the panel draws that current; no diversity or continuous-load factor is applied here.

A feeder drop uses part of the budget available at the final outlet. Add the downstream branch drop at the same operating condition rather than treating a feeder target and a branch target as independent full allowances.

For a typical downstream panel, keep the neutral isolated from the enclosure and equipment grounding bar. A detached structure also needs a grounding review; earth is not a substitute for the equipment grounding conductor.

This balanced line-to-line estimate does not size the neutral or predict unbalanced line-to-neutral voltage. List the actual loads on each leg and verify neutral current, protection and terminal ratings separately.

Reference: NFPA 70 (NEC), including Articles 215, 240, 310, 430, 440, 547, 625 and 680 as applicable. Verify the adopted edition and equipment instructions. These are calculated examples, not installation approvals.

Frequently Asked Questions

What size wire do I need for a 150 amp feeder at 100 feet?▾
For a 150A/240V circuit at 100 feet, use 1/0 AWG copper (1.64% drop) or 3/0 AWG aluminum. The ampacity check uses 150A; voltage drop uses the actual 150A (NEC Chapter 9 Table 9 impedance, Table 9, steel conduit, PF 0.85). Installation adjustments and equipment ratings must be checked separately.
Can I use aluminum wire for a 150 amp circuit?▾
At 150A over 100 ft, use 3/0 AWG aluminum (1.72% voltage drop). Use only equipment and connectors listed for this aluminum gauge; follow their preparation instructions.
What happens if the voltage drop exceeds 3%?▾
3% is a planning target, not installation approval. Here it means 232.8V at the load before upstream loss. Compare the combined path with the equipment’s operating range.

Need a Custom Calculation?

Different voltage, three-phase, or custom max drop percentage? Use our interactive calculator.

Wire Size Calculator