What Size Wire for 50 Amp 240V 100 Feet
Table-based wire size estimate for 50 amps at 100 feet on a 240V single-phase circuit. Immediate answer below.
Updated October 24, 2026
Recommended Wire Size
Required ampacity: 50 A × 1 = 50 A. Drop uses 50 A. Based on NEC Table 310.16 (75°C column), single-phase, 240V, 3% max voltage drop, one-way distance 100 ft.
Wire Comparison Table
| Wire Size | Ampacity | V-Drop (V) | V-Drop (%) | V at Load | Status |
|---|---|---|---|---|---|
| 10 AWG | 30A | 12.4V | 5.17% | 227.6V | |
| 8 AWG | 50A | 7.78V | 3.24% | 232.2V | |
| 6 AWGREC | 65A | 4.91V | 2.05% | 235.1V | |
| 4 AWG | 85A | 3.08V | 1.28% | 236.9V | |
| 3 AWG | 100A | 2.45V | 1.02% | 237.6V |
Table shows nearby candidate sizes for 50A at 100 ft on 240V (copper). Green check = meets both ampacity and 3% voltage drop. REC = smallest size meeting these two model checks. See the full conductor tables for other sizes.
Hot-tub supply versus charging supply
The former hot-tub scenario is covered here, but a spa and a vehicle charger do not share all circuit requirements. Use the spa installation manual for its circuit arrangement. For vehicle charging at this current and distance, use the dedicated EV scenario, whose ampacity check includes the continuous charging allowance.
Operating boundaries: 50 A, 100 ft, 240 V, copper
Voltage drop controls: the ampacity floor is 8 AWG, but its 3% route limit at 50 A is only 92.545 ft. The 100 ft route therefore needs 6 AWG. One set meets both checks; parallel conductors are not required by this model.
8 AWG has enough ampacity, but the route must shrink from 100 ft to at most 92.545 ft (shorten by 7.455 ft) to meet 3% at 50 A. Alternatively, keep the route and reduce current to at most 46.272 A, down 3.728 A. Either change makes the smaller size eligible; reducing both inputs further may permit another size.
For the selected 6 AWG, increasing load beyond 65.000 A changes the choice: ampacity reaches its limit first. That leaves 15.000 A above the present load. With current fixed, route growth above 146.640 ft also requires reselection, a margin of 46.640 ft.
A 2% budget is 4.800 V instead of 7.200 V. At 50 A, the existing conductor’s length ceiling falls to 97.760 ft; at 100 ft, its combined current ceiling becomes 48.880 A. The unchanged inputs now select 4 AWG, giving 3.080 V (1.283%).
- Current −10%: 45.000 A / 100.000 ft → 8 AWG (2.917%).
- Current +10%: 55.000 A / 100.000 ft → 6 AWG (2.250%).
- Route −10%: 50.000 A / 90.000 ft → 8 AWG (2.917%).
- Route +10%: 50.000 A / 110.000 ft → 6 AWG (2.250%).
Basis: R = 0.491 Ω/kft at 75°C; Imax = min(ampacity / 1, V × target × 1000 / (2 × L × R)); Lmax = V × target × 1000 / (2 × I × R). Boundaries are displayed to three decimals; selection uses unrounded values. These are load changes, not permission to change a breaker.
Which assumption changes this selection?
copper: 50 A · 100 ft · 240 V. Alternatives are hypothetical; all results use the site resistance table.
| Assumption | Load / route / supply | Required ampacity | Minimum size | Drop / end voltage |
|---|---|---|---|---|
| Present route, 3% target | 50 A / 100 ft / 240 V | 50 A | 6 AWG | 4.910 V (2.05%) / 235.090 V |
| Reserve more voltage: 2% target | 50 A / 100 ft / 240 V | 50 A | 4 AWG | 3.080 V (1.28%) / 236.920 V |
| Hot tub or spa: Hypothetical simultaneous load increases 25% | 62.5 A / 100 ft / 240 V | 62.5 A | 6 AWG | 6.138 V (2.56%) / 233.863 V |
Also covers: hot tub 50 amp 100 feet
This merged scenario shares the route inputs above. Apply the Key Considerations below; any additional equipment conditions are listed here.
- Confirm simultaneous heater/pump demand, neutral needs and permitted conductor material from the spa instructions. Review ground-fault protection, bonding, disconnect position and wet-location wiring under the applicable pool/spa rules.
Key Considerations
Use actual load current; check continuous duty separately. The site retains small-conductor protection limits. Verify cable and terminal temperature, equipment voltage range, upstream loss and connections.
Reference: NFPA 70 (NEC), including Articles 215, 240, 310, 430, 440, 547, 625 and 680 as applicable. Verify the adopted edition and equipment instructions. These are calculated examples, not installation approvals.
Frequently Asked Questions
What size wire do I need for a 50 amp circuit at 100 feet?▾
Can I use aluminum wire for a 50 amp circuit?▾
What happens if the voltage drop exceeds 3%?▾
Related Wire Size Calculations
Need a Custom Calculation?
Different voltage, three-phase, or custom max drop percentage? Use our interactive calculator.
Wire Size Calculator