Wire Sizing

What Size Wire for 50 Amp 240V 50 Feet

Pre-calculated NEC-compliant wire size for 50 amps at 50 feet on a 240V single-phase circuit. Immediate answer below.

Recommended Wire Size

Copper
8 AWG
Voltage drop: 1.62% (3.89V)
Voltage at load: 236.1V
Controlling factor: Ampacity (NEC 310.16)
Aluminum
6 AWG
Voltage drop: 1.68% (4.04V)
Voltage at load: 236V
Controlling factor: Ampacity (NEC 310.16)

Based on NEC Table 310.16 (75°C column), single-phase, 240V, 3% max voltage drop, one-way distance 50 ft.

Wire Comparison Table

Wire SizeAmpacityV-Drop (V)V-Drop (%)V at LoadStatus
14 AWG15A15.7V6.54%224.3V
12 AWG20A9.9V4.13%230.1V
10 AWG30A6.2V2.58%233.8V
8 AWGREC50A3.89V1.62%236.1V
6 AWG65A2.46V1.02%237.5V
4 AWG85A1.54V0.64%238.5V
3 AWG100A1.23V0.51%238.8V
2 AWG115A0.97V0.4%239V
1 AWG130A0.77V0.32%239.2V
1/0 AWG150A0.61V0.25%239.4V
2/0 AWG175A0.48V0.2%239.5V
3/0 AWG200A0.38V0.16%239.6V
4/0 AWG230A0.3V0.13%239.7V
250 kcmil255A0.26V0.11%239.7V
300 kcmil285A0.21V0.09%239.8V
350 kcmil310A0.18V0.08%239.8V
400 kcmil335A0.16V0.07%239.8V
500 kcmil380A0.13V0.05%239.9V

Table shows all standard AWG/kcmil sizes for 50A at 50 ft on 240V (copper). Green check = meets both ampacity and 3% voltage drop. REC = smallest compliant size.

Key Considerations

For a 50A circuit at 50 feet on 240V, both ampacity and voltage drop must be satisfied. NEC recommends keeping the total voltage drop (feeder + branch) under 5%, with no more than 3% on either segment alone.

Copper conductors at 75°C column (THHN/THWN-2) are assumed. If using 60°C terminations, derate the ampacity to the 60°C column values. Verify the temperature rating of your terminals.

Frequently Asked Questions

What size wire do I need for a 50 amp service at 50 feet?
For a 50A/240V circuit at 50 feet, use 8 AWG copper (1.62% drop) or 6 AWG aluminum. This keeps voltage drop within the NEC-recommended 3% limit.
Can I use aluminum wire for a 50 amp circuit?
Yes. Aluminum wire is a cost-effective alternative for larger circuits. For 50A at 50 feet, use 6 AWG aluminum (1.68% voltage drop). Aluminum requires AL-rated connectors and anti-oxidant compound at all terminations.
What happens if the voltage drop exceeds 3%?
Voltage drop above 3% reduces equipment efficiency, can cause motors to overheat, and may violate NEC 210.19(A) Informational Note No. 4. For a 50A circuit at 50 feet on 240V, exceeding 3% means the load receives less than 232.8V, which can damage sensitive electronics and shorten appliance lifespan.

Need a Custom Calculation?

Different voltage, three-phase, or custom max drop percentage? Use our interactive calculator.

Wire Size Calculator