Wire Sizing

What Size Wire for 50 Amp 240V 75 Feet

Table-based wire size estimate for 50 amps at 75 feet on a 240V single-phase circuit. Immediate answer below.

Updated November 12, 2026

Recommended Wire Size

Copper
6 AWG
Voltage drop: 1.41% (3.377V)
Voltage at load: 236.62V
Ampacity used: 55 A (60°C column). Controlling factor: Ampacity (NEC 310.16)
Aluminum
4 AWG
Voltage drop: 1.45% (3.488V)
Voltage at load: 236.51V
Ampacity used: 55 A (60°C column). Controlling factor: Ampacity (NEC 310.16)

Required ampacity: 50 A × 1 = 50 A. Drop uses 50 A. Ampacity: NEC Table 310.16, 60°C column (NEC 110.14(C) default for circuits of 100 A or less; equipment marked for 75°C terminals can allow the 75°C column), single-phase, 240V, 3% max voltage drop, one-way distance 75 ft.

Voltage drop uses AC resistance and reactance from NEC Chapter 9 Table 9 (NEC 2017 Table 9 values) for conductors in steel conduit at 0.85 lagging power factor, effective Z = R × PF + XL × sin(acos PF), single-phase, one set, VD = 2 × I × Z × L / 1000. Ampacity uses NEC 2023 Table 310.16 at 30°C ambient with no more than three current-carrying conductors. These are the same engine and defaults as the wire size calculator (steel conduit, PF 0.85).

Wire Comparison Table

Wire SizeAmpacityV-Drop (V)V-Drop (%)V at LoadStatus
10 AWG30A7.899V3.29%232.1V
8 AWG40A5.229V2.18%234.77V
6 AWGREC55A3.377V1.41%236.62V
4 AWG70A2.213V0.92%237.79V
3 AWG85A1.827V0.76%238.17V

Table shows nearby candidate sizes for 50A at 75 ft on 240V (copper). Green check = meets both ampacity and 3% voltage drop (Table 9, steel conduit, PF 0.85). REC = smallest size meeting these two model checks. See the full conductor tables for other sizes.

Spa heater and pump combinations

This estimate also applies to a hot tub. Check the spa’s marked supply requirements and permitted heater/pump operating combinations instead of adding guessed appliance currents. The output covers conductor impedance along the supply route; it cannot establish the required ground-fault protection, bonding connections or disconnect location around the spa.

Operating boundaries: 50 A, 75 ft, 240 V, copper

Ampacity sets the minimum: 6 AWG supports 55 A (60°C column) against the 50.000 A requirement. At 50 A it can reach 159.924 ft before the 3% drop target takes over. Shortening this 75 ft route alone cannot reduce the ampacity floor. One set suffices in this model.

8 AWG cannot carry this assumed load: its current ceiling after the ×1 allowance is 40.000 A. At the present 75 ft, its drop ceiling is 68.843 A. Both checks first allow that smaller conductor at or below 40.000 A, a reduction of 10.000 A. Distance alone cannot fix its ampacity shortfall.

For the selected 6 AWG, increasing load beyond 55.000 A changes the choice: ampacity reaches its limit first. That leaves 5.000 A above the present load. With current fixed, route growth above 159.924 ft also requires reselection, a margin of 84.924 ft.

A 2% budget is 4.800 V instead of 7.200 V. At 50 A, the existing conductor’s length ceiling falls to 106.616 ft; at 75 ft, its combined current ceiling becomes 55.000 A. The unchanged inputs still select 6 AWG, giving 3.377 V (1.407%).

  • Current −10%: 45.000 A / 75.000 ft → 6 AWG (1.266%).
  • Current +10%: 55.000 A / 75.000 ft → 4 AWG (1.014%).
  • Route −10%: 50.000 A / 67.500 ft → 6 AWG (1.266%).
  • Route +10%: 50.000 A / 82.500 ft → 6 AWG (1.548%).

Basis: Z = 0.4502 Ω/kft (effective impedance, Table 9, steel conduit, PF 0.85; NEC 2017 Table 9 values); Imax = min(ampacity / 1, V × target × 1000 / (2 × L × Z)); Lmax = V × target × 1000 / (2 × I × Z). Boundaries are displayed to three decimals; selection uses unrounded values. These are load changes, not permission to change a breaker.

Which assumption changes this selection?

copper: 50 A · 75 ft · 240 V. Alternatives are hypothetical; all results use the same Table 9 model (Table 9, steel conduit, PF 0.85).

AssumptionLoad / route / supplyRequired ampacityMinimum sizeDrop / end voltage
Present route, 3% target50 A / 75 ft / 240 V50 A6 AWG3.377 V (1.41%) / 236.623 V
Reserve more voltage: 2% target50 A / 75 ft / 240 V50 A6 AWG3.377 V (1.41%) / 236.623 V
Hot tub or spa: Hypothetical simultaneous load increases 25%62.5 A / 75 ft / 240 V62.5 A4 AWG2.767 V (1.15%) / 237.233 V

Also covers: hot tub 50 amp 75 feet

The same amps, distance and voltage above also describe this equipment, so the result applies to it too. Apply the Key Considerations below; extra equipment conditions are listed here.

  • Confirm simultaneous heater/pump demand, neutral needs and permitted conductor material from the spa instructions. Review ground-fault protection, bonding, disconnect position and wet-location wiring under the applicable pool/spa rules.

Key Considerations

Use actual load current; check continuous duty separately. The site retains small-conductor protection limits. Verify cable and terminal temperature, equipment voltage range, upstream loss and connections.

Reference: NFPA 70 (NEC), including Articles 215, 240, 310, 430, 440, 547, 625 and 680 as applicable. Verify the adopted edition and equipment instructions. These are calculated examples, not installation approvals.

Frequently Asked Questions

What size wire do I need for a 50 amp circuit at 75 feet?▾
For a 50A/240V circuit at 75 feet, use 6 AWG copper (1.41% drop) or 4 AWG aluminum. The ampacity check uses 50A; voltage drop uses the actual 50A (NEC Chapter 9 Table 9 impedance, Table 9, steel conduit, PF 0.85). Installation adjustments and equipment ratings must be checked separately.
Can I use aluminum wire for a 50 amp circuit?▾
At 50A over 75 ft, use 4 AWG aluminum (1.45% voltage drop). Use only equipment and connectors listed for this aluminum gauge; follow their preparation instructions.
What happens if the voltage drop exceeds 3%?▾
3% is a planning target, not installation approval. Here it means 232.8V at the load before upstream loss. Compare the combined path with the equipment’s operating range.

Need a Custom Calculation?

Different voltage, three-phase, or custom max drop percentage? Use our interactive calculator.

Wire Size Calculator