What Size Wire for 50 Amp 240V 150 Feet
Table-based wire size estimate for 50 amps at 150 feet on a 240V single-phase circuit. Immediate answer below.
Updated November 12, 2026
Recommended Wire Size
Required ampacity: 50 A × 1 = 50 A. Drop uses 50 A. Ampacity: NEC Table 310.16, 60°C column (NEC 110.14(C) default for circuits of 100 A or less; equipment marked for 75°C terminals can allow the 75°C column), single-phase, 240V, 3% max voltage drop, one-way distance 150 ft.
Voltage drop uses AC resistance and reactance from NEC Chapter 9 Table 9 (NEC 2017 Table 9 values) for conductors in steel conduit at 0.85 lagging power factor, effective Z = R × PF + XL × sin(acos PF), single-phase, one set, VD = 2 × I × Z × L / 1000. Ampacity uses NEC 2023 Table 310.16 at 30°C ambient with no more than three current-carrying conductors. These are the same engine and defaults as the wire size calculator (steel conduit, PF 0.85).
Wire Comparison Table
| Wire Size | Ampacity | V-Drop (V) | V-Drop (%) | V at Load | Status |
|---|---|---|---|---|---|
| 10 AWG | 30A | 15.798V | 6.58% | 224.2V | |
| 8 AWG | 40A | 10.459V | 4.36% | 229.54V | |
| 6 AWGREC | 55A | 6.753V | 2.81% | 233.25V | |
| 4 AWG | 70A | 4.427V | 1.84% | 235.57V | |
| 3 AWG | 85A | 3.654V | 1.52% | 236.35V |
Table shows nearby candidate sizes for 50A at 150 ft on 240V (copper). Green check = meets both ampacity and 3% voltage drop (Table 9, steel conduit, PF 0.85). REC = smallest size meeting these two model checks. See the full conductor tables for other sizes.
HVAC nameplate review
This estimate also applies to HVAC equipment on the same circuit. A breaker marked 50 A does not establish a compressor’s running current or the nameplate MCA. Read those values at the equipment, compare conductor ampacity against MCA, and check protection against MOCP. Use running current for the operating voltage calculation, then assess compressor starting separately.
Why this copper conductor?
6 AWG has a site ampacity of 55 A against a required 50 A. Table 9 lists R = 0.49 and XL = 0.064 Ω/kft (steel conduit), so at PF 0.85 its effective Z is 0.4502 Ω/kft. Substituting the actual load into 2 × 50 × 150 × 0.4502 / 1000 gives 6.753 V (2.81%).
The next smaller size, 8 AWG, has 40 A of site ampacity and 4.36% drop on this route. It fails both checks.
3% route-length limit: 159.9 ft one way; remaining margin: 9.9 ft. This margin excludes upstream loss and does not authorize extra load.
Which assumption changes this selection?
copper: 50 A · 150 ft · 240 V. Alternatives are hypothetical; all results use the same Table 9 model (Table 9, steel conduit, PF 0.85).
| Assumption | Load / route / supply | Required ampacity | Minimum size | Drop / end voltage |
|---|---|---|---|---|
| Present route, 3% target | 50 A / 150 ft / 240 V | 50 A | 6 AWG | 6.753 V (2.81%) / 233.247 V |
| Reserve more voltage: 2% target | 50 A / 150 ft / 240 V | 50 A | 4 AWG | 4.427 V (1.84%) / 235.573 V |
| HVAC equipment: Hypothetical nameplate MCA = 1.25 × running A | 50 A / 150 ft / 240 V | 62.5 A | 4 AWG | 4.427 V (1.84%) / 235.573 V |
The alternative MCA is a hypothetical terminal/nameplate constraint, not a calculated equipment MCA. Running current stays fixed, so a change of conductor here comes from the ampacity screen. Replace this assumption with the marked MCA; do not multiply an existing MCA again.
3% → 2% changes 6 AWG → 4 AWG. Load-voltage gain: 2.327 V. Original conductor’s 2% length limit: 106.6 ft one way.
Also covers: hvac 50 amp 150 feet
The same amps, distance and voltage above also describe this equipment, so the result applies to it too. Apply the Key Considerations below; extra equipment conditions are listed here.
- Read the equipment nameplate MCA (minimum circuit ampacity) and MOCP (maximum overcurrent protection) separately. MOCP is a protection ceiling, not the operating current and not the conductor ampacity to copy into this model.
- These estimates use the stated amperes as running current with an ampacity factor of 1. They do not calculate MCA. Compare the recommendation with the marked MCA; do not add a second blanket 125% factor to a marked MCA that already includes equipment allowances.
- A steady running-current result does not predict compressor starting voltage. Check locked-rotor data, starting method and source impedance, especially where the contactor or compressor has a restricted operating-voltage range.
- Roof temperature, grouped conductors and disconnect terminal ratings can reduce usable ampacity. Equipment-specific Article 440 protection rules require a separate review; this tool retains its conservative small-conductor limits.
Key Considerations
The entered current is a load assumption, not a breaker selection. If the load is continuous, determine its required ampacity separately; the generic calculation uses a factor of 1.
For small copper and aluminum conductors, the recommendation retains the site’s NEC 240.4(D) overcurrent limits. A higher insulation temperature rating does not by itself allow a larger breaker.
Verify cable type and terminal temperature before using the 75°C column. For example, a cable or termination limited to 60°C can require a different conductor even when the voltage-drop calculation passes.
Check the appliance’s supply range and any upstream loss. The calculation assumes the stated voltage at the beginning of this run and does not model receptacle contacts or loose connections.
Reference: NFPA 70 (NEC), including Articles 215, 240, 310, 430, 440, 547, 625 and 680 as applicable. Verify the adopted edition and equipment instructions. These are calculated examples, not installation approvals.
Frequently Asked Questions
What size wire do I need for a 50 amp circuit at 150 feet?▾
Can I use aluminum wire for a 50 amp circuit?▾
What happens if the voltage drop exceeds 3%?▾
Related Wire Size Calculations
Need a Custom Calculation?
Different voltage, three-phase, or custom max drop percentage? Use our interactive calculator.
Wire Size Calculator