Wire Sizing

Wire Size for 50 Amp EV Charger 75 Feet

Pre-calculated NEC-compliant wire size for 50 amps at 75 feet on a 240V single-phase circuit. Immediate answer below.

Recommended Wire Size

Copper
8 AWG
Voltage drop: 2.43% (5.84V)
Voltage at load: 234.2V
Controlling factor: Ampacity (NEC 310.16)
Aluminum
6 AWG
Voltage drop: 2.53% (6.06V)
Voltage at load: 233.9V
Controlling factor: Ampacity (NEC 310.16)

Based on NEC Table 310.16 (75°C column), single-phase, 240V, 3% max voltage drop, one-way distance 75 ft.

Wire Comparison Table

Wire SizeAmpacityV-Drop (V)V-Drop (%)V at LoadStatus
14 AWG15A23.55V9.81%216.5V
12 AWG20A14.85V6.19%225.2V
10 AWG30A9.3V3.88%230.7V
8 AWGREC50A5.84V2.43%234.2V
6 AWG65A3.68V1.53%236.3V
4 AWG85A2.31V0.96%237.7V
3 AWG100A1.84V0.77%238.2V
2 AWG115A1.46V0.61%238.5V
1 AWG130A1.16V0.48%238.8V
1/0 AWG150A0.92V0.38%239.1V
2/0 AWG175A0.73V0.3%239.3V
3/0 AWG200A0.57V0.24%239.4V
4/0 AWG230A0.46V0.19%239.5V
250 kcmil255A0.39V0.16%239.6V
300 kcmil285A0.32V0.13%239.7V
350 kcmil310A0.28V0.11%239.7V
400 kcmil335A0.24V0.1%239.8V
500 kcmil380A0.19V0.08%239.8V

Table shows all standard AWG/kcmil sizes for 50A at 75 ft on 240V (copper). Green check = meets both ampacity and 3% voltage drop. REC = smallest compliant size.

Key Considerations

EV chargers are continuous loads under NEC Article 625. The conductor must be sized for 125% of the rated current (50A x 1.25 = 62.5A) when selecting breaker size. The voltage drop calculation above uses the actual draw of 50A.

Install a dedicated circuit with no other loads. Use THHN/THWN-2 conductors rated for 75°C or higher. All connections at the panel and EVSE must be torqued to manufacturer specifications.

Frequently Asked Questions

What size wire do I need for a EV charger at 75 feet?
For a 50A/240V circuit at 75 feet, use 8 AWG copper (2.43% drop) or 6 AWG aluminum. This keeps voltage drop within the NEC-recommended 3% limit.
Can I use aluminum wire for a 50 amp circuit?
Yes. Aluminum wire is a cost-effective alternative for larger circuits. For 50A at 75 feet, use 6 AWG aluminum (2.53% voltage drop). Aluminum requires AL-rated connectors and anti-oxidant compound at all terminations.
What happens if the voltage drop exceeds 3%?
Voltage drop above 3% reduces equipment efficiency, can cause motors to overheat, and may violate NEC 210.19(A) Informational Note No. 4. For a 50A circuit at 75 feet on 240V, exceeding 3% means the load receives less than 232.8V, which can damage sensitive electronics and shorten appliance lifespan.

Need a Custom Calculation?

Different voltage, three-phase, or custom max drop percentage? Use our interactive calculator.

Wire Size Calculator