Wire Sizing

What Size Wire for 125 Amp 100 Feet Away

Pre-calculated NEC-compliant wire size for 125 amps at 100 feet on a 240V single-phase circuit. Immediate answer below.

Recommended Wire Size

Copper
1 AWG
Voltage drop: 1.6% (3.85V)
Voltage at load: 236.2V
Controlling factor: Ampacity (NEC 310.16)
Aluminum
2/0 AWG
Voltage drop: 1.66% (3.98V)
Voltage at load: 236V
Controlling factor: Ampacity (NEC 310.16)

Based on NEC Table 310.16 (75°C column), single-phase, 240V, 3% max voltage drop, one-way distance 100 ft.

Wire Comparison Table

Wire SizeAmpacityV-Drop (V)V-Drop (%)V at LoadStatus
14 AWG15A78.5V32.71%161.5V
12 AWG20A49.5V20.63%190.5V
10 AWG30A31V12.92%209V
8 AWG50A19.45V8.1%220.6V
6 AWG65A12.28V5.11%227.7V
4 AWG85A7.7V3.21%232.3V
3 AWG100A6.13V2.55%233.9V
2 AWG115A4.85V2.02%235.2V
1 AWGREC130A3.85V1.6%236.2V
1/0 AWG150A3.05V1.27%237V
2/0 AWG175A2.42V1.01%237.6V
3/0 AWG200A1.91V0.8%238.1V
4/0 AWG230A1.52V0.63%238.5V
250 kcmil255A1.29V0.54%238.7V
300 kcmil285A1.07V0.45%238.9V
350 kcmil310A0.92V0.38%239.1V
400 kcmil335A0.8V0.33%239.2V
500 kcmil380A0.65V0.27%239.4V

Table shows all standard AWG/kcmil sizes for 125A at 100 ft on 240V (copper). Green check = meets both ampacity and 3% voltage drop. REC = smallest compliant size.

Key Considerations

For a 125A circuit at 100 feet on 240V, both ampacity and voltage drop must be satisfied. NEC recommends keeping the total voltage drop (feeder + branch) under 5%, with no more than 3% on either segment alone.

Copper conductors at 75°C column (THHN/THWN-2) are assumed. If using 60°C terminations, derate the ampacity to the 60°C column values. Verify the temperature rating of your terminals.

Frequently Asked Questions

What size wire do I need for a 125 amp service at 100 feet?
For a 125A/240V circuit at 100 feet, use 1 AWG copper (1.6% drop) or 2/0 AWG aluminum. This keeps voltage drop within the NEC-recommended 3% limit.
Can I use aluminum wire for a 125 amp circuit?
Yes. Aluminum wire is a cost-effective alternative for larger circuits. For 125A at 100 feet, use 2/0 AWG aluminum (1.66% voltage drop). Aluminum requires AL-rated connectors and anti-oxidant compound at all terminations.
What happens if the voltage drop exceeds 3%?
Voltage drop above 3% reduces equipment efficiency, can cause motors to overheat, and may violate NEC 210.19(A) Informational Note No. 4. For a 125A circuit at 100 feet on 240V, exceeding 3% means the load receives less than 232.8V, which can damage sensitive electronics and shorten appliance lifespan.

Need a Custom Calculation?

Different voltage, three-phase, or custom max drop percentage? Use our interactive calculator.

Wire Size Calculator