What Size Wire for 125 Amp 100 Feet Away
Table-based wire size estimate for 125 amps at 100 feet on a 240V single-phase circuit. Immediate answer below.
Updated November 12, 2026
Recommended Wire Size
Required ampacity: 125 A × 1 = 125 A. Drop uses 125 A. Ampacity: NEC Table 310.16, 75°C column (NEC 110.14(C) for circuits above 100 A), single-phase, 240V, 3% max voltage drop, one-way distance 100 ft.
Voltage drop uses AC resistance and reactance from NEC Chapter 9 Table 9 (NEC 2017 Table 9 values) for conductors in steel conduit at 0.85 lagging power factor, effective Z = R × PF + XL × sin(acos PF), single-phase, one set, VD = 2 × I × Z × L / 1000. Ampacity uses NEC 2023 Table 310.16 at 30°C ambient with no more than three current-carrying conductors. These are the same engine and defaults as the wire size calculator (steel conduit, PF 0.85).
Wire Comparison Table
| Wire Size | Ampacity | V-Drop (V) | V-Drop (%) | V at Load | Status |
|---|---|---|---|---|---|
| 3 AWG | 100A | 6.09V | 2.54% | 233.91V | |
| 2 AWG | 115A | 5.001V | 2.08% | 235V | |
| 1 AWGREC | 130A | 4.151V | 1.73% | 235.85V | |
| 1/0 AWG | 150A | 3.274V | 1.36% | 236.73V | |
| 2/0 AWG | 175A | 2.836V | 1.18% | 237.16V |
Table shows nearby candidate sizes for 125A at 100 ft on 240V (copper). Green check = meets both ampacity and 3% voltage drop (Table 9, steel conduit, PF 0.85). REC = smallest size meeting these two model checks. See the full conductor tables for other sizes.
Load calculation and terminal column
At this feeder rating, confirm the equipment’s marked terminal temperature and the chosen conductor insulation before using a particular ampacity column. Also determine whether the entered current is calculated demand or merely a protective-device rating. The recommendation does not apply dwelling-specific allowances or correction for grouped current-carrying conductors.
Operating boundaries: 125 A, 100 ft, 240 V, copper
Ampacity sets the minimum: 1 AWG supports 130 A (75°C column) against the 125.000 A requirement. At 125 A it can reach 173.466 ft before the 3% drop target takes over. Shortening this 100 ft route alone cannot reduce the ampacity floor. One set suffices in this model.
2 AWG cannot carry this assumed load: its current ceiling after the ×1 allowance is 115.000 A. At the present 100 ft, its drop ceiling is 179.976 A. Both checks first allow that smaller conductor at or below 115.000 A, a reduction of 10.000 A. Distance alone cannot fix its ampacity shortfall.
For the selected 1 AWG, increasing load beyond 130.000 A changes the choice: ampacity reaches its limit first. That leaves 5.000 A above the present load. With current fixed, route growth above 173.466 ft also requires reselection, a margin of 73.466 ft.
A 2% budget is 4.800 V instead of 7.200 V. At 125 A, the existing conductor’s length ceiling falls to 115.644 ft; at 100 ft, its combined current ceiling becomes 130.000 A. The unchanged inputs still select 1 AWG, giving 4.151 V (1.729%).
- Current −10%: 112.500 A / 100.000 ft → 2 AWG (1.875%).
- Current +10%: 137.500 A / 100.000 ft → 1/0 AWG (1.501%).
- Route −10%: 125.000 A / 90.000 ft → 1 AWG (1.556%).
- Route +10%: 125.000 A / 110.000 ft → 1 AWG (1.902%).
Basis: Z = 0.1660 Ω/kft (effective impedance, Table 9, steel conduit, PF 0.85; NEC 2017 Table 9 values); Imax = min(ampacity / 1, V × target × 1000 / (2 × L × Z)); Lmax = V × target × 1000 / (2 × I × Z). Boundaries are displayed to three decimals; selection uses unrounded values. These are load changes, not permission to change a breaker.
Which assumption changes this selection?
copper: 125 A · 100 ft · 240 V. Alternatives are hypothetical; all results use the same Table 9 model (Table 9, steel conduit, PF 0.85).
| Assumption | Load / route / supply | Required ampacity | Minimum size | Drop / end voltage |
|---|---|---|---|---|
| Present route, 3% target | 125 A / 100 ft / 240 V | 125 A | 1 AWG | 4.151 V (1.73%) / 235.849 V |
| Reserve more voltage: 2% target | 125 A / 100 ft / 240 V | 125 A | 1 AWG | 4.151 V (1.73%) / 235.849 V |
| Sub-panel feeder: Feeder allocated 1% of supply voltage | 125 A / 100 ft / 240 V | 125 A | 3/0 AWG | 2.364 V (0.98%) / 237.636 V |
Key Considerations
Calculate feeder demand, separating continuous loads; panel rating is not demand. Add downstream loss at the same operating condition. Review neutral isolation, equipment grounding and detached-building electrodes; this balanced model does not size an unbalanced neutral.
Reference: NFPA 70 (NEC), including Articles 215, 240, 310, 430, 440, 547, 625 and 680 as applicable. Verify the adopted edition and equipment instructions. These are calculated examples, not installation approvals.
Frequently Asked Questions
What size wire do I need for a 125 amp feeder at 100 feet?▾
Can I use aluminum wire for a 125 amp circuit?▾
What happens if the voltage drop exceeds 3%?▾
Related Wire Size Calculations
Need a Custom Calculation?
Different voltage, three-phase, or custom max drop percentage? Use our interactive calculator.
Wire Size Calculator