Wire Sizing

What Size Wire for 125 Amp 150 Feet Away

Table-based wire size estimate for 125 amps at 150 feet on a 240V single-phase circuit. Immediate answer below.

Updated October 24, 2026

Recommended Wire Size

Copper
1 AWG
Voltage drop: 2.41% (5.775V)
Voltage at load: 234.22V
Controlling factor: Ampacity (NEC 310.16)
Aluminum
2/0 AWG
Voltage drop: 2.48% (5.963V)
Voltage at load: 234.04V
Controlling factor: Ampacity (NEC 310.16)

Required ampacity: 125 A × 1 = 125 A. Drop uses 125 A. Based on NEC Table 310.16 (75°C column), single-phase, 240V, 3% max voltage drop, one-way distance 150 ft.

Wire Comparison Table

Wire SizeAmpacityV-Drop (V)V-Drop (%)V at LoadStatus
3 AWG100A9.19V3.83%230.8V
2 AWG115A7.28V3.03%232.7V
1 AWGREC130A5.78V2.41%234.2V
1/0 AWG150A4.58V1.91%235.4V
2/0 AWG175A3.63V1.51%236.4V

Table shows nearby candidate sizes for 125A at 150 ft on 240V (copper). Green check = meets both ampacity and 3% voltage drop. REC = smallest size meeting these two model checks. See the full conductor tables for other sizes.

Existing conduit reuse

If this feeder must fit an existing raceway, check fill, pulling conditions and bending space using the selected conductor’s actual dimensions. An electrical recommendation does not prove physical fit. Do not reduce conductor size solely to reuse the conduit without recalculating ampacity and delivered voltage for the proposed alternative.

Operating boundaries: 125 A, 150 ft, 240 V, copper

Ampacity sets the minimum: 1 AWG supports 130 A against the 125.000 A requirement. At 125 A it can reach 187.013 ft before the 3% drop target takes over. Shortening this 150 ft route alone cannot reduce the ampacity floor. One set suffices in this model.

2 AWG cannot carry this assumed load: its current ceiling after the ×1 allowance is 115.000 A. At the present 150 ft, its drop ceiling is 123.711 A. Both checks first allow that smaller conductor at or below 115.000 A, a reduction of 10.000 A. Distance alone cannot fix its ampacity shortfall.

For the selected 1 AWG, increasing load beyond 130.000 A changes the choice: ampacity reaches its limit first. That leaves 5.000 A above the present load. With current fixed, route growth above 187.013 ft also requires reselection, a margin of 37.013 ft.

A 2% budget is 4.800 V instead of 7.200 V. At 125 A, the existing conductor’s length ceiling falls to 124.675 ft; at 150 ft, its combined current ceiling becomes 103.896 A. The unchanged inputs now select 1/0 AWG, giving 4.575 V (1.906%).

  • Current −10%: 112.500 A / 150.000 ft → 2 AWG (2.728%).
  • Current +10%: 137.500 A / 150.000 ft → 1/0 AWG (2.097%).
  • Route −10%: 125.000 A / 135.000 ft → 1 AWG (2.166%).
  • Route +10%: 125.000 A / 165.000 ft → 1 AWG (2.647%).

Basis: R = 0.154 Ω/kft at 75°C; Imax = min(ampacity / 1, V × target × 1000 / (2 × L × R)); Lmax = V × target × 1000 / (2 × I × R). Boundaries are displayed to three decimals; selection uses unrounded values. These are load changes, not permission to change a breaker.

Which assumption changes this selection?

copper: 125 A · 150 ft · 240 V. Alternatives are hypothetical; all results use the site resistance table.

AssumptionLoad / route / supplyRequired ampacityMinimum sizeDrop / end voltage
Present route, 3% target125 A / 150 ft / 240 V125 A1 AWG5.775 V (2.41%) / 234.225 V
Reserve more voltage: 2% target125 A / 150 ft / 240 V125 A1/0 AWG4.575 V (1.91%) / 235.425 V
Sub-panel feeder: Feeder allocated 1% of supply voltage125 A / 150 ft / 240 V125 A4/0 AWG2.280 V (0.95%) / 237.720 V

Key Considerations

Calculate feeder demand, separating continuous loads; panel rating is not demand. Add downstream loss at the same operating condition. Review neutral isolation, equipment grounding and detached-building electrodes; this balanced model does not size an unbalanced neutral.

Reference: NFPA 70 (NEC), including Articles 215, 240, 310, 430, 440, 547, 625 and 680 as applicable. Verify the adopted edition and equipment instructions. These are calculated examples, not installation approvals.

Frequently Asked Questions

What size wire do I need for a 125 amp feeder at 150 feet?▾
For a 125A/240V circuit at 150 feet, use 1 AWG copper (2.41% drop) or 2/0 AWG aluminum. The ampacity check uses 125A; voltage drop uses the actual 125A. Installation adjustments and equipment ratings must be checked separately.
Can I use aluminum wire for a 125 amp circuit?▾
At 125A over 150 ft, use 2/0 AWG aluminum (2.48% voltage drop). Use only equipment and connectors listed for this aluminum gauge; follow their preparation instructions.
What happens if the voltage drop exceeds 3%?▾
3% is a planning target, not installation approval. Here it means 232.8V at the load before upstream loss. Compare the combined path with the equipment’s operating range.

Need a Custom Calculation?

Different voltage, three-phase, or custom max drop percentage? Use our interactive calculator.

Wire Size Calculator