What Size Wire for 200 Amp 200 Feet Away
Table-based wire size estimate for 200 amps at 200 feet on a 240V single-phase circuit. Immediate answer below.
Updated November 12, 2026
Recommended Wire Size
Required ampacity: 200 A × 1 = 200 A. Drop uses 200 A. Ampacity: NEC Table 310.16, 75°C column (NEC 110.14(C) for circuits above 100 A), single-phase, 240V, 3% max voltage drop, one-way distance 200 ft.
Voltage drop uses AC resistance and reactance from NEC Chapter 9 Table 9 (NEC 2017 Table 9 values) for conductors in steel conduit at 0.85 lagging power factor, effective Z = R × PF + XL × sin(acos PF), single-phase, one set, VD = 2 × I × Z × L / 1000. Ampacity uses NEC 2023 Table 310.16 at 30°C ambient with no more than three current-carrying conductors. These are the same engine and defaults as the wire size calculator (steel conduit, PF 0.85).
Wire Comparison Table
| Wire Size | Ampacity | V-Drop (V) | V-Drop (%) | V at Load | Status |
|---|---|---|---|---|---|
| 2/0 AWG | 175A | 9.076V | 3.78% | 230.92V | |
| 3/0 AWG | 200A | 7.563V | 3.15% | 232.44V | |
| 4/0 AWGREC | 230A | 6.433V | 2.68% | 233.57V | |
| 250 kcmil | 255A | 5.863V | 2.44% | 234.14V | |
| 300 kcmil | 285A | 5.209V | 2.17% | 234.79V |
Table shows nearby candidate sizes for 200A at 200 ft on 240V (copper). Green check = meets both ampacity and 3% voltage drop (Table 9, steel conduit, PF 0.85). REC = smallest size meeting these two model checks. See the full conductor tables for other sizes.
Distribution beyond the feeder
This estimate also applies to a sub-panel feeder. A main distribution panel can feed several long outgoing circuits, so identify the worst complete path from source to appliance. Do not add two independent percentage targets and assume the total is acceptable. Use simultaneous currents and the voltage at the feeder origin for that complete-path check.
Operating boundaries: 200 A, 200 ft, 240 V, copper
Voltage drop controls: the ampacity floor is 3/0 AWG, but its 3% route limit at 200 A is only 190.390 ft. The 200 ft route therefore needs 4/0 AWG. One set meets both checks; parallel conductors are not required by this model.
3/0 AWG has enough ampacity, but the route must shrink from 200 ft to at most 190.390 ft (shorten by 9.610 ft) to meet 3% at 200 A. Alternatively, keep the route and reduce current to at most 190.390 A, down 9.610 A. Either change makes the smaller size eligible; reducing both inputs further may permit another size.
For the selected 4/0 AWG, increasing load beyond 223.836 A changes the choice: voltage drop reaches its limit first. That leaves 23.836 A above the present load. With current fixed, route growth above 223.836 ft also requires reselection, a margin of 23.836 ft.
A 2% budget is 4.800 V instead of 7.200 V. At 200 A, the existing conductor’s length ceiling falls to 149.224 ft; at 200 ft, its combined current ceiling becomes 149.224 A. The unchanged inputs now select 350 kcmil, giving 4.759 V (1.983%).
- Current −10%: 180.000 A / 200.000 ft → 3/0 AWG (2.836%).
- Current +10%: 220.000 A / 200.000 ft → 4/0 AWG (2.949%).
- Route −10%: 200.000 A / 180.000 ft → 3/0 AWG (2.836%).
- Route +10%: 200.000 A / 220.000 ft → 4/0 AWG (2.949%).
Basis: Z = 0.0804 Ω/kft (effective impedance, Table 9, steel conduit, PF 0.85; NEC 2017 Table 9 values); Imax = min(ampacity / 1, V × target × 1000 / (2 × L × Z)); Lmax = V × target × 1000 / (2 × I × Z). Boundaries are displayed to three decimals; selection uses unrounded values. These are load changes, not permission to change a breaker.
Which assumption changes this selection?
copper: 200 A · 200 ft · 240 V. Alternatives are hypothetical; all results use the same Table 9 model (Table 9, steel conduit, PF 0.85).
| Assumption | Load / route / supply | Required ampacity | Minimum size | Drop / end voltage |
|---|---|---|---|---|
| Present route, 3% target | 200 A / 200 ft / 240 V | 200 A | 4/0 AWG | 6.433 V (2.68%) / 233.567 V |
| Reserve more voltage: 2% target | 200 A / 200 ft / 240 V | 200 A | 350 kcmil | 4.759 V (1.98%) / 235.241 V |
| Sub-panel feeder: Feeder allocated 1% of supply voltage | 200 A / 200 ft / 240 V | 200 A | No single conductor in the table meets both ampacity and voltage-drop limits for this input. Use parallel sets or a larger conductor, and have the design reviewed. | No supported single conductor |
Key Considerations
Calculate feeder demand, separating continuous loads; panel rating is not demand. Add downstream loss at the same operating condition. Review neutral isolation, equipment grounding and detached-building electrodes; this balanced model does not size an unbalanced neutral.
Reference: NFPA 70 (NEC), including Articles 215, 240, 310, 430, 440, 547, 625 and 680 as applicable. Verify the adopted edition and equipment instructions. These are calculated examples, not installation approvals.
Frequently Asked Questions
What size wire do I need for a 200 amp feeder at 200 feet?▾
Can I use aluminum wire for a 200 amp circuit?▾
What happens if the voltage drop exceeds 3%?▾
Related Wire Size Calculations
Need a Custom Calculation?
Different voltage, three-phase, or custom max drop percentage? Use our interactive calculator.
Wire Size Calculator