Wire Sizing

What Size Wire for 200 Amp 400 Feet Away

Table-based wire size estimate for 200 amps at 400 feet on a 240V single-phase circuit. Immediate answer below.

Updated November 12, 2026

Recommended Wire Size

Copper
750 kcmil
Voltage drop: 2.88% (6.902V)
Voltage at load: 233.10V
Ampacity used: 475 A (75°C column). Controlling factor: Voltage Drop (3% limit)
Aluminum
No single conductor in the table meets both ampacity and voltage-drop limits for this input. Use parallel sets or a larger conductor, and have the design reviewed.

Required ampacity: 200 A × 1 = 200 A. Drop uses 200 A. Ampacity: NEC Table 310.16, 75°C column (NEC 110.14(C) for circuits above 100 A), single-phase, 240V, 3% max voltage drop, one-way distance 400 ft.

Voltage drop uses AC resistance and reactance from NEC Chapter 9 Table 9 (NEC 2017 Table 9 values) for conductors in steel conduit at 0.85 lagging power factor, effective Z = R × PF + XL × sin(acos PF), single-phase, one set, VD = 2 × I × Z × L / 1000. Ampacity uses NEC 2023 Table 310.16 at 30°C ambient with no more than three current-carrying conductors. These are the same engine and defaults as the wire size calculator (steel conduit, PF 0.85).

Wire Comparison Table

Wire SizeAmpacityV-Drop (V)V-Drop (%)V at LoadStatus
500 kcmil380A7.99V3.33%232.01V
600 kcmil420A7.446V3.1%232.55V
750 kcmilREC475A6.902V2.88%233.1V
1000 kcmil545A6.325V2.64%233.67V

Table shows nearby candidate sizes for 200A at 400 ft on 240V (copper). Green check = meets both ampacity and 3% voltage drop (Table 9, steel conduit, PF 0.85). REC = smallest size meeting these two model checks. See the full conductor tables for other sizes.

Long agricultural supply planning

This estimate also applies to a long barn feeder. Separate steady operating loss from the voltage dip when water pumps or ventilation motors start. If the route demands conductors beyond the equipment connection range, compare engineered parallel arrangements or a revised distribution layout; neither option is automatically designed by this single-set table.

Why this copper conductor?

750 kcmil has a site ampacity of 475 A against a required 200 A. Table 9 lists R = 0.021 and XL = 0.048 Ω/kft (steel conduit), so at PF 0.85 its effective Z is 0.0431 Ω/kft. Substituting the actual load into 2 × 200 × 400 × 0.0431 / 1000 gives 6.902 V (2.88%).

The next smaller size, 600 kcmil, has 420 A of site ampacity and 3.10% drop on this route. It fails the voltage-drop target.

3% route-length limit: 417.3 ft one way; remaining margin: 17.3 ft. This margin excludes upstream loss and does not authorize extra load.

Which assumption changes this selection?

copper: 200 A · 400 ft · 240 V. Alternatives are hypothetical; all results use the same Table 9 model (Table 9, steel conduit, PF 0.85).

AssumptionLoad / route / supplyRequired ampacityMinimum sizeDrop / end voltage
Present route, 3% target200 A / 400 ft / 240 V200 A750 kcmil6.902 V (2.88%) / 233.098 V
Reserve more voltage: 2% target200 A / 400 ft / 240 V200 ANo single conductor in the table meets both ampacity and voltage-drop limits for this input. Use parallel sets or a larger conductor, and have the design reviewed.No supported single conductor
Barn or detached agricultural building: Hypothetical trench detour adds 50% to route200 A / 600 ft / 240 V200 ANo single conductor in the table meets both ampacity and voltage-drop limits for this input. Use parallel sets or a larger conductor, and have the design reviewed.No supported single conductor

The detour represents a longer trench around an obstacle, not a measured property of this site. Recalculate using the surveyed electrical path; a straight-line building separation can miss the threshold at which another conductor size is needed.

Also covers: barn 200 amp 400 feet

The same amps, distance and voltage above also describe this equipment, so the result applies to it too. Apply the Key Considerations below; extra equipment conditions are listed here.

  • List ventilation, water pumping, lighting and receptacle loads by duty and starting behavior before treating the service or panel rating as demand. Seasonal equipment can change the combination of loads operating together.
  • A detached building needs review of its disconnect, equipment grounding path and grounding electrodes. A long trench does not remove those requirements, and grounding electrodes do not replace the feeder grounding conductor.
  • Agricultural locations may expose wiring to moisture, dust, corrosion or livestock contact. Determine whether Article 547 and equipotential-plane provisions apply to the actual use of the building.
  • Check burial method, wet-location conductor rating, physical protection and accessible terminations. Aluminum can be considered only with compatible listed connections and the manufacturer’s preparation instructions.

Key Considerations

Use the calculated feeder demand, separating continuous and noncontinuous loads. The panel bus rating is a maximum equipment rating, not proof that the panel draws that current; no diversity or continuous-load factor is applied here.

A feeder drop uses part of the budget available at the final outlet. Add the downstream branch drop at the same operating condition rather than treating a feeder target and a branch target as independent full allowances.

For a typical downstream panel, keep the neutral isolated from the enclosure and equipment grounding bar. A detached structure also needs a grounding review; earth is not a substitute for the equipment grounding conductor.

This balanced line-to-line estimate does not size the neutral or predict unbalanced line-to-neutral voltage. List the actual loads on each leg and verify neutral current, protection and terminal ratings separately.

Reference: NFPA 70 (NEC), including Articles 215, 240, 310, 430, 440, 547, 625 and 680 as applicable. Verify the adopted edition and equipment instructions. These are calculated examples, not installation approvals.

Frequently Asked Questions

What size wire do I need for a 200 amp feeder at 400 feet?▾
For a 200A/240V circuit at 400 feet, use 750 kcmil copper (2.88% drop) or consult an engineer for aluminum. The ampacity check uses 200A; voltage drop uses the actual 200A (NEC Chapter 9 Table 9 impedance, Table 9, steel conduit, PF 0.85). Installation adjustments and equipment ratings must be checked separately.
Can I use aluminum wire for a 200 amp circuit?▾
At 200A over 400 ft, No single conductor in the table meets both ampacity and voltage-drop limits for this input. Use parallel sets or a larger conductor, and have the design reviewed.. Use only equipment and connectors listed for this aluminum gauge; follow their preparation instructions.
What happens if the voltage drop exceeds 3%?▾
3% is a planning target, not installation approval. Here it means 232.8V at the load before upstream loss. Compare the combined path with the equipment’s operating range.