Wire Size for Barn — 200 Amp 300 Feet
Table-based wire size estimate for 200 amps at 300 feet on a 240V single-phase circuit. Immediate answer below.
Updated November 12, 2026
Recommended Wire Size
Required ampacity: 200 A × 1 = 200 A. Drop uses 200 A. Ampacity: NEC Table 310.16, 75°C column (NEC 110.14(C) for circuits above 100 A), single-phase, 240V, 3% max voltage drop, one-way distance 300 ft.
Voltage drop uses AC resistance and reactance from NEC Chapter 9 Table 9 (NEC 2017 Table 9 values) for conductors in steel conduit at 0.85 lagging power factor, effective Z = R × PF + XL × sin(acos PF), single-phase, one set, VD = 2 × I × Z × L / 1000. Ampacity uses NEC 2023 Table 310.16 at 30°C ambient with no more than three current-carrying conductors. These are the same engine and defaults as the wire size calculator (steel conduit, PF 0.85).
Wire Comparison Table
| Wire Size | Ampacity | V-Drop (V) | V-Drop (%) | V at Load | Status |
|---|---|---|---|---|---|
| 250 kcmil | 255A | 8.795V | 3.66% | 231.2V | |
| 300 kcmil | 285A | 7.814V | 3.26% | 232.19V | |
| 350 kcmilREC | 310A | 7.139V | 2.97% | 232.86V | |
| 400 kcmil | 335A | 6.667V | 2.78% | 233.33V | |
| 500 kcmil | 380A | 5.992V | 2.5% | 234.01V |
Table shows nearby candidate sizes for 200A at 300 ft on 240V (copper). Green check = meets both ampacity and 3% voltage drop (Table 9, steel conduit, PF 0.85). REC = smallest size meeting these two model checks. See the full conductor tables for other sizes.
Distribution for multiple farm loads
Build a simultaneous demand schedule for pumps, fans, lighting and future equipment before treating the full panel rating as a permanent load. Check motor starts against source capacity and separate the utility service design from any downstream building feeder design.
Why this copper conductor?
350 kcmil has a site ampacity of 310 A against a required 200 A. Table 9 lists R = 0.039 and XL = 0.05 Ω/kft (steel conduit), so at PF 0.85 its effective Z is 0.0595 Ω/kft. Substituting the actual load into 2 × 200 × 300 × 0.0595 / 1000 gives 7.139 V (2.97%).
The next smaller size, 300 kcmil, has 285 A of site ampacity and 3.26% drop on this route. It fails the voltage-drop target.
3% route-length limit: 302.6 ft one way; remaining margin: 2.6 ft. This margin excludes upstream loss and does not authorize extra load.
Which assumption changes this selection?
copper: 200 A · 300 ft · 240 V. Alternatives are hypothetical; all results use the same Table 9 model (Table 9, steel conduit, PF 0.85).
| Assumption | Load / route / supply | Required ampacity | Minimum size | Drop / end voltage |
|---|---|---|---|---|
| Present route, 3% target | 200 A / 300 ft / 240 V | 200 A | 350 kcmil | 7.139 V (2.97%) / 232.861 V |
| Reserve more voltage: 2% target | 200 A / 300 ft / 240 V | 200 A | 1000 kcmil | 4.744 V (1.98%) / 235.256 V |
| Barn or detached agricultural building: Hypothetical trench detour adds 50% to route | 200 A / 450 ft / 240 V | 200 A | 1000 kcmil | 7.116 V (2.96%) / 232.884 V |
The detour represents a longer trench around an obstacle, not a measured property of this site. Recalculate using the surveyed electrical path; a straight-line building separation can miss the threshold at which another conductor size is needed.
3% → 2% changes 350 kcmil → 1000 kcmil. Load-voltage gain: 2.395 V. Original conductor’s 2% length limit: 201.7 ft one way.
Also covers: 200 amp 300 feet
The same amps, distance and voltage above also describe this equipment, so the result applies to it too. Apply the Key Considerations below; extra equipment conditions are listed here.
- The entered current is a load assumption, not a breaker selection. If the load is continuous, determine its required ampacity separately; the generic calculation uses a factor of 1.
- For small copper and aluminum conductors, the recommendation retains the site’s NEC 240.4(D) overcurrent limits. A higher insulation temperature rating does not by itself allow a larger breaker.
- Verify cable type and terminal temperature before using the 75°C column. For example, a cable or termination limited to 60°C can require a different conductor even when the voltage-drop calculation passes.
- Check the appliance’s supply range and any upstream loss. The calculation assumes the stated voltage at the beginning of this run and does not model receptacle contacts or loose connections.
Key Considerations
List ventilation, water pumping, lighting and receptacle loads by duty and starting behavior before treating the service or panel rating as demand. Seasonal equipment can change the combination of loads operating together.
A detached building needs review of its disconnect, equipment grounding path and grounding electrodes. A long trench does not remove those requirements, and grounding electrodes do not replace the feeder grounding conductor.
Agricultural locations may expose wiring to moisture, dust, corrosion or livestock contact. Determine whether Article 547 and equipotential-plane provisions apply to the actual use of the building.
Check burial method, wet-location conductor rating, physical protection and accessible terminations. Aluminum can be considered only with compatible listed connections and the manufacturer’s preparation instructions.
Reference: NFPA 70 (NEC), including Articles 215, 240, 310, 430, 440, 547, 625 and 680 as applicable. Verify the adopted edition and equipment instructions. These are calculated examples, not installation approvals.
Frequently Asked Questions
What size wire do I need for a barn feeder at 300 feet?▾
Can I use aluminum wire for a 200 amp circuit?▾
What happens if the voltage drop exceeds 3%?▾
Related Wire Size Calculations
Need a Custom Calculation?
Different voltage, three-phase, or custom max drop percentage? Use our interactive calculator.
Wire Size Calculator